Adopting Agency | BSC | BSC-CG | SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||
1 | 2 | 1-AC | AC | SS | SS/CC | 1 | 2 | 3 | 4 | ||||||||||||
Adopt Entire Chapter | X | X | X | X | X | X | X | X | X | ||||||||||||
Adopt Entire Chapter as amended (amended sections listed below) | |||||||||||||||||||||
Adopt only those sections that are listed below | |||||||||||||||||||||
Chapter / Section |
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
This chapter shall govern the materials,
design, and installation of indirect waste piping,
receptors, and connections; and provisions for discharge
and disposal of condensate wastes, chemical wastes, industrial
wastes, and clear water wastes.
Indirect waste
piping shall discharge into the building drainage system
through an air gap or air break as set forth in this code.
Where a drainage air gap is required by this code, the
minimum vertical distance as measured from the lowest
point of the indirect waste pipe or the fixture outlet to the
flood-level rim of the receptor shall be not less than 1 inch
(25.4 mm).
Establishments engaged in the storage, preparation, selling,
serving, processing, or other handling of food and beverage
involving the following equipment that requires drainage
shall provide indirect waste piping for refrigerators, refrigeration
coils, freezers, walk-in coolers, iceboxes, icemaking
machines, steam tables, egg boilers, coffee urns and
brewers, hot-and-cold drink dispensers, and similar equipment.
Except for
refrigeration coils and ice-making machines, the size of
the indirect waste pipe shall be not smaller than the
drain on the unit, but shall be not smaller than 1 inch
(25 mm), and the maximum developed length shall not
exceed 15 feet (4572 mm). Indirect waste pipe for icemaking
machines shall be not less than the drain on the
unit, and in no case less than 3/4 of an inch (20 mm).
For walk-in coolers, floor
drains shall be permitted to be connected to a separate
drainage line discharging into an outside receptor. The
flood-level rim of the receptor shall be not less than 6
inches (152 mm) lower than the lowest floor drain.
Such floor drains shall be trapped and individually
vented. Cleanouts shall be provided at 90 degree (1.57
rad) turns and shall be accessibly located. Such waste
shall discharge through an air gap or air break into a
trapped and vented receptor, except that a full-size air
gap is required where the indirect waste pipe is under
vacuum.
Food-preparation
sinks, steam kettles, potato peelers, ice cream dipper
wells, and similar equipment shall be indirectly
connected to the drainage system by means of an air
gap. Bins, sinks, and other equipment having drainage
connections and used for the storage of unpackaged ice
used for human ingestion, or used in direct contact with
ready-to-eat food, shall be indirectly connected to the
drainage system by means of an air gap. Each indirect
waste pipe from food-handling fixtures or equipment
shall be separately piped to the indirect waste receptor
and shall not combine with other indirect waste pipes.
The piping from the equipment to the receptor shall be
not less than the drain on the unit, and in no case less
than 1/2 of an inch (15 mm).
Where the sink in a bar, soda fountain, or counter is so located that the trap
serving the sink cannot be vented, the sink drain shall
discharge through an air gap or air break (see Section
801.3.3) into an approved receptor that is vented. The
developed length from the fixture outlet to the receptor
shall not exceed 5 feet (1524 mm).
Indirect waste connections shall be provided for drains,
overflows, or relief pipes from potable water pressure tanks,
water heaters, boilers, and similar equipment that is
connected to the potable water distribution system. Such
indirect waste connections shall be made by means of a
water-distribution air gap constructed in accordance with
Table 603.3.1.
Lines, devices, or apparatus such as stills, sterilizers, and similar equipment requiring waste connections
and used for sterile materials shall be indirectly
connected by means of an air gap. Each such indirect waste
pipe shall be separately piped to the receptor and shall not
exceed 15 feet (4572 mm). Such receptors shall be located
in the same room.
Appliances, devices, or apparatus not regularly classified as plumbing fixtures, but
which have drip or drainage outlets, shall be permitted to be
drained by indirect waste pipes discharging into an open
receptor through either an air gap or air break (see Section
801.3.1).
No plumbing fixtures served by indirect waste
pipes or receiving discharge therefrom shall be installed until
first approved by the Authority Having Jurisdiction.
Joints and connections
in copper and copper alloy pipe and tube shall be installed
in accordance with Section 705.3.
Except as hereinafter provided, the size of indirect waste piping shall be in accordance with other sections of this code applicable to
drainage and vent piping. No vent from indirect waste
piping shall combine with a sewer-connected vent, but shall
extend separately to the outside air. Indirect waste pipes
exceeding 5 feet (1524 mm), but less than 15 feet (4572
mm) in length shall be directly trapped, but such traps need
not be vented.
Indirect waste pipes less than 15 feet (4572 mm) in length shall be not less than the diameter of the drain outlet or tailpiece of the fixture, appliance, or equipment served, and in no case less than 1/2 of an inch (15 mm). Angles and changes of direction in such indirect waste pipes shall be provided with cleanouts so as to permit flushing and cleaning.
Indirect waste pipes less than 15 feet (4572 mm) in length shall be not less than the diameter of the drain outlet or tailpiece of the fixture, appliance, or equipment served, and in no case less than 1/2 of an inch (15 mm). Angles and changes of direction in such indirect waste pipes shall be provided with cleanouts so as to permit flushing and cleaning.
Plumbing fixtures or other
receptors receiving the discharge of indirect waste pipes
shall be approved for the use proposed and shall be of such
shape and capacity as to prevent splashing or flooding and
shall be located where they are readily accessible for
inspection and cleaning. No standpipe receptor for a clothes
washer shall extend more than 30 inches (762 mm), or not
less than 18 inches (457 mm) above its trap. No trap for a
clothes washer standpipe receptor shall be installed below
the floor, but shall be roughed in not less than 6 inches (152
mm) and not more than 18 inches (457 mm) above the
floor. No indirect waste receptor shall be installed in a toilet
room, closet, cupboard, or storeroom, nor in a portion of a
building not in general use by the occupants thereof; except
standpipes for clothes washers shall be permitted to be
installed in toilet and bathroom areas where the clothes
washer is installed in the same room.
Indirect waste connections shall be
provided for drains, overflows, or relief vents from the
water supply system, and no piping or equipment carrying
wastes or producing wastes or other discharges under pressure
shall be directly connected to a part of the drainage
system.
The foregoing shall not apply to an approved sump pump or to an approved pressure-wasting plumbing fixture or device where the Authority Having Jurisdiction has been satisfied that the drainage system is adequately sized to accommodate the anticipated discharge thereof.
The foregoing shall not apply to an approved sump pump or to an approved pressure-wasting plumbing fixture or device where the Authority Having Jurisdiction has been satisfied that the drainage system is adequately sized to accommodate the anticipated discharge thereof.
Appliances, devices, or apparatus such as
stills, sterilizers, and similar equipment requiring water and
waste and used for sterile materials shall be drained through
an air gap.
Commercial dishwashing
machines, silverware washing machines, and other appliances,
devices, equipment, or other apparatus not regularly
classed as plumbing fixtures, which are equipped with
pumps, drips, or drainage outlets, shall be permitted to be
drained by indirect waste pipes discharging into an
approved type of open receptor.
Where undiluted
condensate waste from a fuel-burning condensing appliance
is discharged into the drainage system, the material in the
drainage system shall be cast-iron, galvanized iron, plastic,
or other materials approved for this use.
Exceptions:
Exceptions:
- Where the above condensate is discharged to an exposed fixture tailpiece and trap, such tailpiece and trap shall be permitted to be copper alloy.
- Materials approved in Section 701.0 shall be permitted to be used where data is provided that the condensate waste is adequately diluted.
No domestic dish washing machine shall be directly connected to a drainage
system or food waste disposer without the use of an
approved dishwasher air gap fitting on the discharge side of
the dishwashing machine. Listed air gaps shall be installed
with the flood-level (FL) marking at or above the flood
level of the sink or drainboard, whichever is higher.
Where permitted by the Authority Having
Jurisdiction, clean running water used exclusively as a
cooling medium in an appliance, device, or apparatus shall
be permitted to discharge into the drainage system through
the inlet side of a fixture trap in the event that a suitable
fixture is not available to receive such discharge. Such trap
connection shall be by means of a pipe connected to the
inlet side of an approved fixture trap, the upper end terminating
in a funnel-shaped receptacle set adjacent, and not
less than 6 inches (152 mm) above the overflow rim of the
fixture.
Drinking fountains shall be permitted to be
installed with indirect wastes.
No steam pipe shall
be directly connected to a plumbing or drainage system, nor
shall water having a temperature above 140°F (60°C) be
discharged under pressure directly into a drainage system.
Pipes from boilers shall discharge by means of indirect
waste piping, as determined by the Authority Having Jurisdiction
or the boiler manufacturer's recommendations. Such
pipes shall be permitted to be indirectly connected by
discharging into an open or closed condenser or an intercepting
sump of an approved type that will prevent the
entrance of steam or such water under pressure into the
drainage system. Closed condensers or sumps shall be
provided with a vent that shall be taken off the top and
extended separately, full size above the roof. Condensers
and sumps shall be properly trapped at the outlet with a deep seal trap extending to within 6 inches (152 mm) of the
bottom of the tank. The top of the deep seal trap shall have
a 3/4 of an inch (19.1 mm) opening located at the highest
point of the trap to serve as a siphon breaker. Outlets shall
be taken off from the side in such a manner as to allow a
waterline to be maintained that will permanently occupy not
less than one-half the capacity of the condenser or sump.
Inlets shall enter above the waterline. Wearing plates or
baffles shall be installed in the tank to protect the shell. The
sizes of the blowoff line inlet, the water outlets, and the
vent shall be as shown in Table 810.1. The contents of
condensers receiving steam or hot water under pressure
shall pass through an open sump before entering the
drainage system.
For SI units: 1 inch = 25.4 mm
* To be used only with boilers of 100 square feet (9.29 m2) of heating surface or less.
BOILER BLOWOFF | WATER OUTLET | VENT |
---|---|---|
3/4* | 3/4* | 2 |
1 | 1 | 21/2 |
11/4 | 11/4 | 3 |
11/2 | 11/2 | 4 |
2 | 2 | 5 |
21/2 | 21/2 | 6 |
* To be used only with boilers of 100 square feet (9.29 m2) of heating surface or less.
Sumps, condensers, or intercepting tanks that are
constructed of concrete shall have walls and bottom not less
than 4 inches (102 mm) in thickness, and the inside shall be
cement plastered not less than 1/2 of an inch (12.7 mm) in
thickness. Condensers constructed of metal shall be not less
than No.12 U.S. standard gauge (0.109 inch) (2.77 mm),
and such metal condensers shall be protected from external
corrosion by an approved bituminous coating.
Sumps and condensers shall be provided
with suitable means of access for cleaning and shall contain
a volume of not less than twice the volume of water
removed from the boiler or boilers connected thereto where
the normal water level of such boiler or boilers is reduced
not less than 4 inches (102 mm).
An indirect waste interceptor receiving
discharge-containing particles that would clog the receptor
drain shall have a readily removable beehive strainer.
Chemical or industrial liquid wastes
that are likely to damage or increase maintenance costs on
the sanitary sewer system, detrimentally affect sewage
treatment, or contaminate surface or subsurface waters shall
be pretreated to render them innocuous prior to discharge
into a drainage system. Detailed construction documents of
the pretreatment facilities shall be required by the Authority
Having Jurisdiction.
Piping conveying industrial, chemical, or process wastes from their point of origin to sewer-connected pretreatment facilities shall be of such material and design as to adequately perform its intended function to the satisfaction of the Authority Having Jurisdiction. Drainage discharge piping from pretreatment facilities or interceptors shall be in accordance with standard drainage installation procedures.
Copper or copper alloy tube shall not be used for chemical or industrial wastes as defined in this section.
Piping conveying industrial, chemical, or process wastes from their point of origin to sewer-connected pretreatment facilities shall be of such material and design as to adequately perform its intended function to the satisfaction of the Authority Having Jurisdiction. Drainage discharge piping from pretreatment facilities or interceptors shall be in accordance with standard drainage installation procedures.
Copper or copper alloy tube shall not be used for chemical or industrial wastes as defined in this section.
Each waste pipe receiving or
intended to receive the discharge of a fixture into which
acid or corrosive chemical is placed, and each vent pipe
connected thereto, shall be constructed of chlorinated
polyvinyl chloride (CPVC), polypropylene (PP),
polyvinylidene fluoride (PVDF), chemical-resistant glass,
high-silicon iron pipe, or lead pipe with a wall thickness of
not less than 1/8 of an inch (3.2 mm); an approved type of
ceramic glazed or unglazed vitrified clay; or other approved
corrosion-resistant materials. PP pipe and fittings shall
comply with ASTM F1412 or CSA B181.3. PVDF pipe and
fittings shall comply with ASTM F1673 or CSA B181.3.
Chemical-resistant glass pipe and fittings shall comply with
ASTM C1053. High-silicon iron pipe and fittings shall
comply with ASTM A861.
Joining materials shall be of
approved type and quality.
Where practicable, piping shall be readily
accessible and installed with the maximum of clearance
from other services.
The owner shall make and keep
a permanent record of the location of piping and venting
carrying chemical waste.
The provisions in this section
relative to materials and methods of construction shall not
apply to installations such as photographic or x-ray darkrooms
or research or control laboratories where minor
amounts of adequately diluted chemicals are discharged.
Water lifts, expansion tanks, cooling
jackets, sprinkler systems, drip or overflow pans, or similar
devices that discharge clear wastewater into the building
drainage system shall discharge through an indirect waste.
Condensate from air washers, air-cooling coils, condensing appliances, and the overflow
from evaporative coolers and similar water-supplied equipment
or similar air-conditioning equipment shall be
collected and discharged to an approved plumbing fixture
or disposal area. Where discharged into the drainage
system, equipment shall drain by means of an indirect waste
pipe. The waste pipe shall have a slope of not less than 1/8
inch per foot (10.4 mm/m) or 1 percent slope and shall be
of approved corrosion-resistant material not smaller than
the outlet size in accordance with Section 814.3 or Section
814.4 for air-cooling coils or condensing appliances,
respectively. Condensate or wastewater shall not drain over
a public way.
Where approved by the Authority Having Jurisdiction, condensate pumps shall
be installed in accordance with the manufacturer's
installation instructions. Pump discharge shall rise
vertically to a point where it is possible to connect to a
gravity condensate drain and discharged to an approved
disposal point. Each condensing unit shall be provided
with a separate sump and interlocked with the equipment
to prevent the equipment from operating during a
failure. Separate pumps shall be permitted to connect to
a single gravity indirect waste where equipped with
check valves and approved by the Authority Having
Jurisdiction.
Where an equipment or appliance
is installed in a space where damage is capable of
resulting from condensate overflow, other than damage to
replaceable lay-in ceiling tiles, a drain line shall be
provided and shall be drained in accordance with Section
814.1. An additional protection method for condensate
overflow shall be provided in accordance with one of the
following:
- A water level detecting device that will shut off the equipment or appliance in the event the primary drain is blocked.
- An additional watertight pan of corrosion-resistant material, with a separate drain line, installed beneath the cooling coil, unit, or the appliance to catch the overflow condensate due to a clogged primary condensate drain.
- An additional drain line at a level that is higher than the primary drain line connection of the drain pan.
- An additional watertight pan of corrosion-resistant material with a water level detection device installed beneath the cooling coil, unit, or the appliance to catch the overflow condensate due to a clogged primary condensate drain and to shut off the equipment.
Where insulation or appurtenances are installed where damage is
capable of resulting from a condensate drain pan overfill,
such installations shall occur above the rim of the
drain pan with supports. Where the supports are in
contact with the condensate waste, the supports shall be
of approved corrosion-resistant material.
Condensate waste pipes from air-cooling coils shall be
sized in accordance with the equipment capacity as specified
in Table 814.3. The material of the piping shall comply
with the pressure and temperature rating of the appliance or
equipment, and shall be approved for use with the liquid
being discharged.
For SI units: 1 ton of refrigerant = 3.52 kW, 1 inch = 25 mm
The size of condensate waste pipes is for one unit or a combination of units, or as recommended by the manufacturer. The capacity of waste pipes assumes a 1/8 inch per foot (10.4 mm/m) or 1 percent slope, with the pipe running three-quarters full at the following pipe conditions:
For SI units: °C = (°F-32)/1.8
Condensate drain sizing for other slopes or other conditions shall be approved by the Authority Having Jurisdiction.
Air-conditioning waste pipes shall be constructed of materials specified in Chapter 7.
EQUIPMENT CAPACITY IN TONS OF REFRIGERATION |
MINIMUM CONDENSATE PIPE DIAMETER (inches) |
---|---|
Up to 20 | 3/4 |
21 - 40 | 1 |
41 - 90 | 11/4 |
91 - 125 | 11/2 |
126 - 250 | 2 |
The size of condensate waste pipes is for one unit or a combination of units, or as recommended by the manufacturer. The capacity of waste pipes assumes a 1/8 inch per foot (10.4 mm/m) or 1 percent slope, with the pipe running three-quarters full at the following pipe conditions:
Outside Air - 20% | Room Air - 80% | ||||
---|---|---|---|---|---|
DB | WB | DB | WB | ||
90°F | 73°F | 75°F | 62.5°F |
Condensate drain sizing for other slopes or other conditions shall be approved by the Authority Having Jurisdiction.
Air-conditioning waste pipes shall be constructed of materials specified in Chapter 7.
Condensate drain lines shall be
configured or provided with a cleanout to permit the
clearing of blockages and for maintenance without
requiring the drain line to be cut.
Condensate drain
lines from individual condensing appliances shall be sized
as required by the manufacturer's instructions. Condensate
drain lines serving more than one appliance shall be
approved by the Authority Having Jurisdiction prior to installation.
Air-conditioning condensate waste pipes shall connect indirectly, except where permitted
in Section 814.6, to the drainage system through an air gap
or air break to trapped and vented receptors, dry wells,
leach pits, or the tailpiece of plumbing fixtures. A condensate
drain shall be trapped in accordance with the appliance
manufacturer's instructions or as approved.
Where the condensate waste from air-conditioning coils
discharges by direct connection to a lavatory tailpiece or to
an approved accessible inlet on a bathtub overflow, the
connection shall be located in the area controlled by the
same person controlling the air-conditioned space.
Female plastic screwed fittings shall
be used with plastic male fittings and plastic threads.