Heads up:
There are no amended sections in this chapter.
Adopting Agency | BSC | BSC-CG | SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | 1 | 1-AC | AC | SS | SS/CC | 1 | 2 |
3 | 4 | ||||||||||||
Adopt Entire Chapter | X | ||||||||||||||||||||
Adopt Entire Chapter as amended (amended sections listed below) | |||||||||||||||||||||
Adopt only those sections that are listed below | X | X | X | X | |||||||||||||||||
Chapter / Section | |||||||||||||||||||||
1304.1.2 | X | X | X | X |
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
This chapter applies to the special
fixtures and systems in health care facilities; the special
plumbing requirements for such facilities; and the installation,
testing, and verification of Categories 1, 2, and 3
medical gas and medical vacuum piping systems, except as
otherwise indicated in this chapter, from the central supply
system to the station outlets or inlets in hospitals, clinics,
and other health care facilities. Other plumbing in such
facilities shall comply with other applicable sections of this
code. For Category 3 medical gas systems, only oxygen
and nitrous oxide shall be used.
This chapter does not apply to the following except as otherwise addressed in this
chapter:
- Cylinder and container management, storage, and reserve requirements
- Bulk supply systems
- Electrical connections and requirements
- Motor requirements and controls
- Systems having nonstandard operating pressures
- Waste anesthetic gas disposal (WAGD) systems
- Surface-mounted medical gas rail systems
- Breathing air replenishment (BAR) systems
- Portable compressed gas systems
- Medical support gas systems
- Gas-powered device supply systems
- Scavenging systems
The requirements of
this chapter shall not be interpreted to conflict with the
requirements of NFPA 99. For requirements of portions of
medical gas and medical vacuum systems not addressed in
this chapter or medical gas and medical vacuum systems
beyond the scope of this chapter refer to NFPA 99.
Where the term "medical gas" occurs, the
provisions shall apply to piped systems for oxygen, nitrous oxide, medical air, carbon dioxide, helium, nitrogen, instrument
air, and mixtures thereof. Where the name of a
specific gas service occurs, the provision shall apply to that
gas. [NFPA 99:5.1.1.2]
Where the tenn "medical vacuum" occurs, the provisions shall apply to systems for piped medical-surgical vacuum. Where the name of a specific vacuum service occurs, the provision shall apply to that vacuum service. [NFPA 99:5.1.1.3]
Where the tenn "medical vacuum" occurs, the provisions shall apply to systems for piped medical-surgical vacuum. Where the name of a specific vacuum service occurs, the provision shall apply to that vacuum service. [NFPA 99:5.1.1.3]
Construction and equipment requirements shall be applied to new construction and new
equipment, except as otherwise addressed in this chapter. [NFPA 99:1.3.2]
The altered, renovated, or modernized portion of an existing system or individual
component shall be required to meet the installation and
equipment requirements stated in this chapter. Where the
alteration, renovation, or modernization adversely impacts
existing performance requirements of a system or component,
additional upgrading shall be required. An existing
system that does not comply with the provisions of this
chapter shall be permitted to be continued in use where the
Authority Having Jurisdiction has determined that such lise
does not constitute a distinct hazard to life. [NFPA
99:1.3.2.1 - 1.3.2.3]
Building systems
in health care facilities shall be designed in accordance with
Category 1 through Category 3 requirements as detailed in
this chapter. [NFPA 99:4.1]
The governing body of the
facility or its designee shall establish the following areas in
accordance with the type of patient care anticipated:
- Critical care rooms
- General care rooms
- Basic care rooms [NFPA 99:1.3.4.1]
It shall be the responsibility
of the governing body of the health care organization
to designate anesthetizing locations. [NFPA 99:1.3.4.2]
Exception: Deep sedation and general anesthesia shall not be administered where using a Category 3 medical gas system. [NFPA 99:5.3.1.5]
Exception: Deep sedation and general anesthesia shall not be administered where using a Category 3 medical gas system. [NFPA 99:5.3.1.5]
It shall be the responsibility
of the governing body of the health care organization
to designate wet procedure locations. [NFPA 99:1.3.4.3]
Drinking
fountain control valves shall be flush-mounted or fully
recessed where installed in corridors or other areas where
patients are transported on a gurney, bed, or wheelchair.
Ice makers or ice storage containers shall be located in nursing stations or
similarly supervised areas to minimize potential contamination.
Sterilizers and
bedpan steamers shall be installed in accordance with the
manufacturer's installation instructions and comply with
Section 1303.4.1 and Section 1303.4.2.
Sterilizers and
bedpan steamers shall be connected to the sanitary
drainage system through an air gap in accordance with
Section 801.2. The size of indirect waste piping shall
be not less than the size of the drain connection on the
fixture. Each such indirect waste pipe shall not exceed
15 feet (4572 mm) in length and shall be separately
piped to a receptor. Such receptors shall be located in
the same room as the equipment served. Except for
bedpan steamers, such indirect waste pipes shall not
require traps. A trap having a seal of not less than 3
inches (76 mm) shall be provided in the indirect waste
pipe for a bedpan steamer.
Where a sterilizer or bedpan steamer has provision for a vapor vent
and such a vent is required by the manufacturer, the
vent shall be extended to the outdoors above the roof. Sterilizer and bedpan steamer vapor vents shall be
installed in accordance with the manufacturer's installation
instructions and shall not be connected to a
drainage system vent.
Provisions for aspirators or other
water-supplied suction devices shall be installed with the
specific approval of the Authority Having Jurisdiction.
Where aspirators are used for removing body fluids, they
shall include a collection container to collect liquids and
solid particles. Aspirators shall indirectly discharge to the
sanitary drainage system through an air gap in accordance with Section 806.1. The potable water supply to an aspirator
shall be protected by a vacuum breaker or equivalent backflow protection device in accordance with Section 603.5.9.
Drains shall be installed on dryers, after-coolers,
separators, and receivers.
Clinical sinks shall be installed in
accordance with the manufacturer's installation instructions
and shall comply with Section 1303.7.1.
Clinical sinks shall be
directly connected to the sanitary drainage system, and
shall be provided with approved flushing devices
installed in accordance with Section 413.1.
Hospitals shall be
provided with not less than two approved potable water
sources that are installed in such a manner as to prevent the
interruption of water service.
The installation of medical gas and medical vacuum piping systems shall comply with the
requirements of this chapter.
[OSHPD 1, 2, 3 & 4] Medical gas systems for
health care facilities that are regulated by OSHPD
(hospitals, skilled nursing facilities, and intermediate
care facilities, licensed clinics, and correctional treatment centers) shall be in accordance with NFPA 99,
Standard for Health Care Facilities. See California
Building Code Table 1224.4.6.1 for location and number
of station outlets for oxygen, vacuum, and medical air.
The installation of individual components shall comply with the manufacturer's installation instructions. Such instructions shall
include directions and information deemed by the manufacturer
to be adequate for attaining proper operation, testing,
and maintenance of the medical gas and medical vacuum systems. Copies of the manufacturer's instructions shall be
left with the system owner. [NFPA 99:5.1.10.11.8]
Medical gas and medical vacuum systems shall be supplied from a central supply
source of not less than two units, primary and secondary,
consisting of one of the following:
- Two cylinder banks with not less than two cylinders in each bank.
- Not less than two air compressors.
- Not less than two vacuum pumps.
- A proportioning system for medical air USP.
Certification of medical gas and medical vacuum systems shall comply with
the requirements of Section 1320.0.
Before a medical gas or medical vacuum system is installed or altered in a
hospital, medical facility, or clinic, duplicate construction documents shall be filed with the Authority Having Jurisdiction.
Approval of the plans shall be obtained prior to
issuance of a permit by the Authority Having Jurisdiction.
Construction documents shall show the following:
- Plot plan of the site, drawn to scale, indicating the location of existing or new cylinder storage areas, property lines, driveways, and existing or proposed buildings.
- Piping layout of the proposed piping system or alteration, including alarms, valves, origin of gases, user outlets, and user inlets. The demand and loading of a piping, existing or future, shall also be indicated.
- Complete specification of materials.
Construction documents submitted to the Authority Having Jurisdiction shall
clearly indicate the nature and extent of the work
proposed and shall show in detail that such work will
be in accordance with the provisions of this chapter.
A record of as-built plans and valve identification records shall remain on the site.
Medical gas and
medical vacuum systems shall be capable of delivering
service in the pressure ranges listed in Table 1305.1.
For SI units: 1 pound-force per square inch = 6.8947 kPa, 1 inch of mercury vacuum (HgV) = 3.386 kPa
GAS SERVICE | ABBREVIATED NAME |
COLORS (BACKGROUND/TEXT) |
STANDARD GAUGE PRESSURE |
Medical air | Med Air | Yellow/black | 50-55 psi |
Carbon dioxide | CO2 | Gray/black or gray/white | 50-55 psi |
Helium | He | Brown/white | 50-55 psi |
Nitrogen | N2 | Black/white | 160-185 psi |
Nitrous oxide | N2O | Blue/white | 50-55 psi |
Oxygen | O2 | Green/white or white/green | 50-55 psi |
Oxygen/carbon dioxide mixtures | O2/CO2 n% (n = % of CO2) |
Green/white | 50-55 psi |
Medical-surgical vacuum | Med Vac | White/black | 15 inch to 30 inch HgV |
Waste anesthetic gas disposal | WAGD | Violet/white | Varies with system type |
Other mixtures | Gas A%/ Gas B% | Colors as above; major gas for background/minor gas for text |
None |
Nonmedical air ( Category 3 gas-powered device) |
- | Yellow-and-white diagonal stripe/black |
None |
Nonmedical and Category 3 vacuum |
- | White-and-black diagonal stripe/black boxed |
None |
Laboratory air | - | Yellow-and-white checker- board/black |
None |
Laboratory vacuum | - | White-and-black checkerboard/black boxed |
None |
Instrument air | - | Red/white | 160-185 psi |
Medical gas and medical
vacuum systems shall be capable of supplying the flow
rates listed in Table 1305.2.
For SI units: 1 cubic foot per minute (CFM) = 0.47 L/s
Notes:
MEDICAL SYSTEM | FLOW RATE |
Oxygen | .71 CFM per outlet1 |
Nitrous Oxide | .71 CFM per outlet1 |
Medical Compressed Air | .71 CFM per outlet1 |
Nitrogen | 15 CFM free air per outlet |
Vacuum | 1 SCFM per inlet2 |
Carbon Dioxide | .71 CFM per outlet1 |
Helium | .71 CFM per outlet |
Notes:
1 A room designed for a permanently located respiratory ventilator or anesthesia machine shall have an outlet capable of a flow rate of 6.36 CFM (3.0 L/s)
at the station outlet.
2 For testing and certification purposes, individual station inlets shall be capable of a flow rate of 3 SCFM, while maintaining a system pressure of not less
than 12 inches of mercury (41 kPa) at the nearest adjacent vacuum inlet.
Station outlets and inlets for medical gas and medical vacuum
systems shall be provided as listed in Table 1305.3.
Notes:
1 Includes pediatric nursery.
2 Includes obstetric recovery.
LOCATION | OXYGEN | MEDICAL VACUUM |
MEDICAL AIR |
NITROUS OXIDE |
NITROGEN | HELIUM | CARBON DIOXIDE |
Patient rooms for medical/surgical, obstetrics, and pediatrics |
1/bed | 1/bed | 1/bed | - | - | - | - |
Examination/treatment for nursing units | 1/bed | 1/bed | - | - | - | - | - |
Intensive care (all) | 3/bed | 3/bed | 2/bed | - | - | - | - |
Nursery1 |
2/bed | 2/bed | 1/bed | - | - | - | - |
General operating rooms | 2/room | 3/room4 | 2/room | 1/room | 1/room | - | - |
Cystoscopic and invasive special procedures | 2/room | 3/room4 | 2/room | - | - | - | - |
Recovery delivery and labor/delivery/recovery rooms2 |
2/bed 2/room |
2/bed 3/room4 |
1/bed 1/room |
- | - | - | - |
Labor rooms | 1/bed | 1/bed | 1/bed | - | - | - | - |
First aid and emergency treatment3 |
1/bed | 1/bed4 | 1/bed | - | - | - | - |
Autopsy | - | 1/station | 1/station | - | - | - | - |
Anesthesia workroom |
1/station | - | 1/station | - | - | - | - |
1 Includes pediatric nursery.
2 Includes obstetric recovery.
3 Emergency trauma rooms used for surgical procedures shall be classified as general operating rooms.
4 Vacuum inlets required are in addition to inlets used as part of a scavenging system for removal of anesthetizing gases.
The installation of medical gas and medical vacuum systems shall be made by qualified, competent technicians who are experienced in performing
such installations. Installers of medical gas and medical
vacuum piped distribution systems, appurtenant piping
supporting pump and compressor source systems, and
appurtenant piping supporting source gas manifold systems
not including permanently installed bulk source systems,
shall be certified in accordance with ASSE 6010. [NFPA
99:5.1.10.11.10.1, 5.1.10.11.10.2]
Brazing shall be performed by individuals who are qualified in accordance with Section 1307.0.
[NFPA 99:5.1.10.11.10.4]
Prior to installation work, the installer of medical gas and medical vacuum piping
shall provide and maintain documentation on the job
site for the qualification of brazing procedures and
individual brazers that are required in accordance with
Section 1307.0. [NFPA 99:5.1.10.11.10.5]
Health
care organization personnel shall be permitted to install piping systems where the requirements of Section 1306.1
through Section 1306.2.1 are met during the installation.
[NFPA 99:5.1.10.11.10.6]
Brazing procedures and brazer performance
for the installation of medical gas and medical
vacuum piping shall be qualified in accordance with
Section IX of the ASME Boiler and Pressure Vessel Code
or AWS B2.2, both as modified in Section 1307.2 through
Section 1307.7. [NFPA 99:5.1.10.11.11.1, 5.3.6.3.1]
Brazers shall be qualified by visual examination of the test coupon followed by sectioning.
[NFPA 99:5.1.10.11.11.2, 5.3.6.3.2]
The brazing procedure specification shall address cleaning, joint clearance, overlap, internal purge gas, purge gas flow rate, and
filler metal. [NFPA 99:5.1.10.11.11.3, 5.3.6.3.3]
The brazing procedure qualification record and the record of brazer performance qualification
shall document the filler metal used, cleaning, joint
clearance, overlap, internal purge gas, and flow rate during
brazing of the coupon, and absence of internal oxidation in
the completed coupon. [NFPA 99:5.1.10.11.11.4, 5.3.6.3.4]
Brazing procedures qualified by a technically competent group or agency shall be permitted under the following conditions:
- The brazing procedure specification and the procedure qualification record meet the requirements of this code.
- The employer obtains a copy of both the brazing procedure specification and the supporting qualification record from the group or agency and signs and dates these records, thereby accepting responsibility for the qualifications that were performed by the group or agency.
- The employer qualifies not less than one brazer following each brazing procedure specification used. [NFPA 99:5.1.10.11.11.5, 5.3.6.3.5]
An employer shall be permitted to accept brazer qualification records of a
previous employer under the following conditions:
- The brazer has been qualified following the same or an equivalent procedure that the new employer uses.
- The new employer obtains a copy of the record of brazer performance qualification tests from the previous employer and signs and dates this record, thereby accepting responsibility for the qualifications performed by the previous employer. [NFPA 99:5.1.10.11.11.6, 5.3.6.3.6]
Performance qualifications of brazers
shall remain in effect indefinitely, unless the brazer does not
braze with the qualified procedure for a period exceeding 6
months or there is a specific reason to question the ability of
the brazer. [NFPA 99:5.1.10.11.11.7, 5.3.6.3.7]
The provisions of this section shall apply to field-installed piping for the distribution of medical gases
and medical vacuum systems.
Tubes, valves, fittings, station outlets, and
other piping components in medical gas systems shall have
been cleaned for oxygen service by the manufacturer prior to
installation in accordance with CGA G-4.1 except that fittings
shall be permitted to be cleaned by a supplier or agency other
than the manufacturer. [NFPA 99:5.1.10.1.1, 5.3.6.2.2]
Where tube ends, fittings, or other components become contaminated before installation they shall be recleaned in accordance with Section 1311.0.
Where tube ends, fittings, or other components become contaminated before installation they shall be recleaned in accordance with Section 1311.0.
Each length of tube shall be delivered
plugged or capped by the manufacturer and kept sealed until
prepared for installation. Fittings, valves, and other components
shall be delivered sealed, labeled, and kept sealed until
prepared for installation. [NFPA 99:5.1.10.1.2, 5.1.10.1.3]
Tubes shall be hard-drawn seamless copper ASTM B819 medical gas
tube, Type L, except Type K shall be used where operating
pressures exceed a gauge pressure of 185 psi (1276 kPa)
and the pipe sizes exceed DN80 [(NPS 3) (31/8 inches
O.D.)]. [NFPA 99:5.1.10.1.4]
ASTM B819 medical gas tube shall be identified by the manufacturer's markings "OXY," "MED," "OXY/MED," "OXY/ACR," or "ACR/MED" in blue (Type L) or green (Type K). [NFPA 99:5.1.10.1.5]
ASTM B819 medical gas tube shall be identified by the manufacturer's markings "OXY," "MED," "OXY/MED," "OXY/ACR," or "ACR/MED" in blue (Type L) or green (Type K). [NFPA 99:5.1.10.1.5]
Piping for
medical vacuum systems shall be constructed of one of the
following:
- Hard-drawn seamless copper tube in accordance with
one of the following:
- ASTM E88 copper tube (Type K, L, or M)
- ASTM B280 copper ACR tube
- ASTM B819 copper medical gas tubing (Type K or L)
- Stainless steel tube [NFPA 99:5.1.10.2.1]
- Schedule 40 or Schedule 80 PVC plastic piping manufactured in accordance with ASTM D1785. [NFPA 99:5.3.8.2.3(1)]
- Schedule 40 or Schedule 80 CPVC IPS (iron pipe size) plastic piping manufactured in accordance with ASTM F441. [NFPA 99:5.3.8.2.4(1)]
- CPVC CTS (copper tube size) plastic pipe manufactured in accordance with ASTM D2846, 1/2 of an inch (15 mm) through 2 inches (50 mm) in diameter. [NFPA 99:5.3.8.2.4(3)]
This section sets forth the requirements for pipe joint installations for a medical gas or medical
vacuum system.
Medical gas and medical vacuum systems shall have turns, offsets, and other changes
in direction made using the following fittings or joining
methods:
- Brazed in accordance with Section 1309.3.
- Memory metal fittings in accordance with Section 1309.4.1.
- Axially swaged, elastic preload fittings in accordance with Section 1309.4.2.
- Threaded in accordance with Section 1309.4.3.
- Welded in accordance with Section 1309.5. [NFPA 99:5.1.10.3.1]
- Flared fittings that comply with ASME B16.26. [NFPA 99:5.3.7.2.2(4)]
- Compression fittings that do not exceed 3/4 of an inch (20 mm) in size. [NFPA 99:5.3.7.2.2(5)]
- Soldered joints shall be made in accordance with ASTM B828 using a lead-free solder filler metal containing not more than 0.2 percent lead by volume in accordance with ASTM B32. [NFPA 99:5.3.7.2.3.3]
- Schedule 40 or Schedule 80 PVC plastic pipe fittings manufactured in accordance with ASTM D2466 or ASTM D2467. Joints shall be solvent-cemented in accordance with ASTM D2672. [NFPA 99:5.3.8.2.3(2), 5.3.8.2.3(3)]
- Schedule 40 or Schedule 80 CPVC IPS plastic pipe fittings manufactured in accordance with ASTM F438 or ASTM F439, or CPVC CTS plastic pipe fittings manufactured in accordance with ASTM D2846, 1/2 of an inch (15 mm) through 2 inches (50 mm) in diameter. Solvent cement used for joints shall be in accordance with ASTM F493. [NFPA 99:5.3.8.2.4(2) - 5.3.8.2.4(4)]
Medical vacuum systems shall be permitted to have branch connections made using mechanically formed, drilled,
and extruded tee-branch connections that are formed in
accordance with the tool manufacturer's instructions.
Such branch connections shall be joined by brazing in
accordance with Section 1309.3. [NFPA 99:5.1.10.3.2]
Brazed joints shall be
made using a brazing alloy that exhibits a melting temperature
in excess of 1000°F (538°C) to retain the integrity of
the piping system in the event of fire exposure. [NFPA
99:5.1.10.4.1.3, 5.3.6.4.2]
Fittings for tubes, turns, offsets, and other changes in direction shall be made with wrought-copper capillary fittings in accordance with ASME B16.22 or brazed fittings in accordance with ASME B16.50. [NFPA 99:5.1.10.4.1.1, 5.3.6.2.3]
Cast-copper alloy fittings shall not be permitted. [NFPA 99:5.1.10.4.1.2, 5.3.6.2.4]
Fittings for tubes, turns, offsets, and other changes in direction shall be made with wrought-copper capillary fittings in accordance with ASME B16.22 or brazed fittings in accordance with ASME B16.50. [NFPA 99:5.1.10.4.1.1, 5.3.6.2.3]
Cast-copper alloy fittings shall not be permitted. [NFPA 99:5.1.10.4.1.2, 5.3.6.2.4]
Brazed tube joints shall be the
socket type. [NFPA 99:5.1.10.4.1.4, 5.3.6.4.1]
Filler metals shall bond with
and be metallurgically compatible with the base metals
being joined. [NFPA 99:5.1.10.4.1.5, 5.3.6.4.3]
Filler metals shall comply with AWS A5.8. [NFPA 99:5.1.10.4.1.6, 5.3.6.4.4]
Filler metals shall comply with AWS A5.8. [NFPA 99:5.1.10.4.1.6, 5.3.6.4.4]
Copper-to-copper
joints shall be brazed using a copper-phosphorus or
copper-phosphorus-silver brazing filler metal (BCuP
series) without flux. [NFPA 99:5.1.10.4.1.7, 5.3.6.4.5]
Joints to be brazed in place shall
be accessible for necessary preparation, assembly,
heating, filler application, cooling, cleaning, and
inspection. [NFPA 99:5.1.10.4.1.9, 5.3.6.4.6]
Tube ends shall be cut square
using a sharp tubing cutter to avoid deforming the tube.
[NFPA 99:5.1.10.4.2.1, 5.3.6.5.1]
The cutting wheels on
tubing cutters shall be free from grease, oil, or
other lubricant not approved for oxygen service.
[NFPA 99:5.1.10.4.2.2, 5.3.6.5.2]
The cut ends of the tube
shall be rolled smooth or deburred with a sharp,
clean deburring tool, taking care to prevent chips
from entering the tube. [NFPA 99:5.1.10.4.2.3,
5.3.6.5.3]
The interior
surfaces of tubes, fittings, and other components that
are cleaned for oxygen service shall be stored and
handled to avoid contamination prior to assembly and
brazing. [NFPA 99:5.1.10.4.3.1, 5.3.6.6.1]
The exterior
surfaces of tube ends shall be cleaned prior to
brazing to remove surface oxides. [NFPA
99:5.1.10.4.3.2, 5.3.6.6.2]
Where cleaning the exterior surfaces of tube ends, no matter shall be permitted to enter the tube. [NFPA 99:5.1.10.4.3.3]
Where cleaning the exterior surfaces of tube ends, no matter shall be permitted to enter the tube. [NFPA 99:5.1.10.4.3.3]
Where the interior
surfaces of fitting sockets become contaminated
prior to brazing, they shall be recleaned for oxygen
in accordance with Section 1311.0 and shall be
cleaned for brazing with a clean, oil-free wire
brush. [NFPA 99:5.1.10.4.3.4]
Clean, nonshedding,
abrasive pads shall be used to clean the exterior
surfaces of the tube ends. [NFPA 99:5.1.10.4.3.5]
Exception: For Category 3 systems, nonabrasive pads shall be used to clean the exterior surfaces of tube ends. [NFPA 99:5.3.6.6.3]
Exception: For Category 3 systems, nonabrasive pads shall be used to clean the exterior surfaces of tube ends. [NFPA 99:5.3.6.6.3]
The use of steel wool or
sand cloth shall be prohibited. [NFPA
99:5.1.10.4.3.6]
For Category 3 systems, the use of wire brushes shall also be prohibited.
The cleaning process shall not result in grooving of the surfaces to be joined. [NFPA 99:5.1.10.4.3.7, 5.3.6.6.5]
For Category 3 systems, the use of wire brushes shall also be prohibited.
The cleaning process shall not result in grooving of the surfaces to be joined. [NFPA 99:5.1.10.4.3.7, 5.3.6.6.5]
After being abraded, the
surfaces shall be wiped using a clean, lint-free
white cloth. [NFPA 99:5.1.10.4.3.8, 5.3.6.6.6]
Tubes, fittings, valves,
and other components shall be visually examined
internally before being joined to verify that they
have not become contaminated for oxygen service
and that they are free of obstructions or debris.
[NFPA 99:5.1.10.4.3.9, 5.3.6.6.7]
The interior
surfaces of tube ends, fittings, and other components
that were cleaned for oxygen service by the
manufacturer, but become contaminated prior to
being installed, shall be permitted to be recleaned
in accordance with Section 1311.0.
Material that has
become contaminated shall be cleaned in accordance
with Section 1311.0.
Joints shall
be brazed within 8 hours after the surfaces are
cleaned for brazing. [NFPA 99:5.1.10.4.3.13,
5.3.6.6.9]
Flux shall only be used where brazing dissimilar metals, such as
copper and bronze or brass, using a silver (BAg series)
brazing filler metal. [NFPA 99:5.1.10.4.4.1, 5.3.6.7.1]
Cast metals shall not be field-brazed. [NFPA 99:5.3.6.7.2]
Cast metals shall not be field-brazed. [NFPA 99:5.3.6.7.2]
Surfaces shall be
cleaned for brazing in accordance with Section
1309.3.6. [NFPA 99:5.1.10.4.4.2, 5.3.6.7.3]
Flux shall be applied sparingly to
minimize contamination of the inside of the tube
with flux. [NFPA 99:5.1.10.4.4.3, 5.3.6.7.4]
The flux shall be applied and worked over the cleaned surfaces to be brazed using a stiff bristle brush to ensure complete coverage and wetting of the surfaces with flux. [NFPA 99:5.1.10.4.4.4, 5.3.6.7.5]
The flux shall be applied and worked over the cleaned surfaces to be brazed using a stiff bristle brush to ensure complete coverage and wetting of the surfaces with flux. [NFPA 99:5.1.10.4.4.4, 5.3.6.7.5]
Short
sections of copper tube shall be brazed onto the
non-copper component, and the interior of the
subassembly shall be cleaned of flux prior to
installation in the piping system. [NFPA
99:5.1.10.4.4.5, 5.3.6.7.6]
On joints
DN20 (NPS 3/4) (7/8 of an inch O.D.) size and
smaller, flux-coated brazing rods shall be permitted
to be used in lieu of applying flux to the surfaces
being joined. [NFPA 99:5.1.10.4.4.6, 5.3.6.7.7]
Where being brazed, joints
shall be continuously purged with oil-free, dry nitrogen
NF to prevent the formation of copper oxide on the
inside surfaces of the joint. [NFPA 99:5.1.10.4.5.1,
5.3.6.8.1]
The source of the purge gas
shall be monitored, and the installer shall be
audibly alerted where the source content is low.
[NFPA 99:5.1.10.4.5.2, 5.3.6.8.2]
The purge gas
flow rate shall be controlled by the use of a pressure
regulator and a flowmeter, or a combination
thereof. [NFPA 99:5.1.10.4.5.3, 5.3.6.8.4]
Pressure regulators alone shall not be used to control purge gas flow rates. [NFPA 99:5.1.10.4.5.4, 5.3.6.8.5]
For Category 3 systems, the nitrogen purge gas flow rate shall not be high enough to produce a positive pressure in the piping system. [NFPA 99:5.3.6.8.3]
Pressure regulators alone shall not be used to control purge gas flow rates. [NFPA 99:5.1.10.4.5.4, 5.3.6.8.5]
For Category 3 systems, the nitrogen purge gas flow rate shall not be high enough to produce a positive pressure in the piping system. [NFPA 99:5.3.6.8.3]
In order to assure
that ambient air has been removed from the
pipeline prior to brazing, an oxygen analyzer shall
be used to verify the effectiveness of the purge.
The oxygen analyzer shall read below 1 percent
oxygen concentration before brazing begins.
[NFPA 99:5.1.10.4.5.5]
During and after
installation, openings in the piping system shall be
kept sealed to maintain a nitrogen atmosphere
within the piping to prevent debris or other
contaminants from entering the system. [NFPA
99:5.1.10.4.5.6, 5.3.6.8.6]
While a joint is
being brazed, a discharge opening shall be
provided on the opposite side of the joint from
where the purge gas is being introduced. [NFPA
99:5.1.10.4.5.7, 5.3.6.8.7]
The flow of
purge gas shall be maintained until the joint is cool
to the touch. [NFPA 99:5.1.10.4.5.8, 5.3.6.8.8]
After the joint
has cooled, the purge discharge opening shall be
sealed to prevent contamination of the inside of the
tube and maintain the nitrogen atmosphere within
the piping system. [NFPA 99:5.1.10.4.5.9, 5.3.6.8.9]
The final
brazed connection of new piping to an existing
pipeline containing the system gas shall be
permitted to be made without the use of a nitrogen
purge. [NFPA 99:5.1.10.4.5.10]
After a final brazed
connection in a positive-pressure medical gas
pipeline is made without a nitrogen purge, an
outlet in the immediate downstream zone of the
affected portions of both the new and existing
piping shall be tested in accordance with the
following [NFPA 99:5.1.10.4.5.11]:
- Each joint in the final connection between the new work and the existing system shall be leak-tested with the gas of system designation at the normal operating pressure by means of a leak detectant that is safe for use with oxygen and does not contain ammonia. [NFPA 99:5.1.12.3.9.2]
- Vacuum joints shall be tested using an ultrasonic leak detector or other means that will allow detection of leaks in an active medical vacuum system. [NFPA 99:5.1.12.3.9.3]
- For pressure gases, immediately after the final brazed connection is made and leak-tested, an outlet in the new piping and an outlet in the existing piping that are immediately downstream from the point or area of intrusion shall be purged in accordance with Section 1309.3.8.9(4). [NFPA 99:5.1.12.3.9.4]
- Where traces of particulate matter have been deposited in the pipelines as a result of construction, a heavy, intermittent purging of the pipeline shall be done. [NFPA 99:5.1.12.3.6]
- Before the new work is used for patient care, positive-pressure gases shall be tested for operational pressure and gas concentration in accordance with Section 1319.10 and Section 1319.11. [NFPA 99:5.1.12.3.9.5]
- Permanent records of these tests shall be maintained. [NFPA 99:5.1.12.3.9.6]
Where using the autogenous orbital
welding process, joints shall be continuously
purged inside and outside with inert gas(es) in
accordance with the qualified welding procedure.
[NFPA 99:5.1.10.4.5.12]
Tube ends shall be inserted fully into the
socket or to a mechanically limited depth that is not less than the minimum cup depth (overlap) in accordance
with ASME B16.50. [NFPA 99:5.1.10.4.6.1,
5.3.6.9.1]
Where flux is
permitted, the joint shall be heated slowly until the
flux has liquefied. [NFPA 99:5.1.10.4.6.2, 5.3.6.9.2]
After flux is liquefied, or where flux is not permitted to be used, the joint shall be heated quickly to the brazing temperature, taking care not to overheat thc joint. [NFPA 99:5.1.10.4.6.3, 5.3.6.9.3]
After flux is liquefied, or where flux is not permitted to be used, the joint shall be heated quickly to the brazing temperature, taking care not to overheat thc joint. [NFPA 99:5.1.10.4.6.3, 5.3.6.9.3]
After brazing,
the outside of joints shall be cleaned by washing with
water and a wire brush to remove residue and permit
clear visual inspection of the joint. [NFPA
99:5.1.10.4.7.1, 5.3.6.10.1]
Where flux has
been used, the wash water shall be hot. [NFPA
99:5.1.10.4.7.2, 5.3.6.10.2]
Each brazed joint
shall be visually inspected after cleaning the
outside surfaces. [NFPA 99:5.1.10.4.7.3,
5.3.6.10.3]
Joints
exhibiting the following conditions shall not be
permitted:
- Flux or flux residue (where flux or flux-coated BAg series rods are used with dissimilar metals).
- Base metal melting or erosion.
- Unmelted filler metal.
- Failure of the filler metal to be clearly visible around the joint at the interface between the socket and the tube.
- Cracks in the tube or component.
- Cracks in the braze filler metal.
- Failure of the joint to hold the test pressure under the installer-performed initial pressure test in accordance with Section 1319.5 and the standing pressure test in accordance with Section 1319.7 or Section 1319.8. [NFPA 99:5.1.10.4.7.4, 5.3.6.10.4]
Brazed
joints that are identified as defective under the
conditions of Section 1309.3.10.3(2) or Section
1309.3.10.3(5) shall be replaced. [NFPA
99:5.1.10.4.7.5,5.3.6.10.5]
Brazed joints that are identified as defective under the conditions of Section 1309.3.10.3(1), Section 1309.3.10.3(3), Section 1309.3.10.3(4), Section 1309.3.10.3(6), or Section 1309.3.10.3(7) shall be permitted to be repaired, except that no joint shall be reheated more than once before being replaced. [NFPA 99:5.1.10.4.7.6, 5.3.6.10.6]
Brazed joints that are identified as defective under the conditions of Section 1309.3.10.3(1), Section 1309.3.10.3(3), Section 1309.3.10.3(4), Section 1309.3.10.3(6), or Section 1309.3.10.3(7) shall be permitted to be repaired, except that no joint shall be reheated more than once before being replaced. [NFPA 99:5.1.10.4.7.6, 5.3.6.10.6]
The special fittings in Section 1309.4.1 through Section 1309.4.5 shall be permitted to be
used in lieu of brazed joints.
Memory metal
fittings having a temperature rating not less than 1000°F (538°C) and a pressure rating not less than 300
psi (2068 kPa) shall be permitted to be used to join
copper or stainless steel tube. Such fittings shall be
installed by qualified technicians in accordance with
the manufacturer's installation instructions. [NFPA
99:5.1.10.6]
Axially swaged,
elastic strain preload fittings providing metal-to-metal
seals, having a temperature rating not less than 1000°F
(538°C) and a pressure rating not less than 300 psi
(2068 kPa), and where complete, are permanent and
nonseparable shall be permitted to be used to join
copper or stainless steel tube. Such fittings shall be
installed by qualified technicians in accordance with
the manufacturer's installation instructions. [NFPA
99:5.1.10.7]
Threaded fittings shall comply with the following requirements:
- Be limited to connections for pressure and vacuum indicators, alarm devices, check valves, and source equipment on the source side of the source valve.
- Be tapered pipe threads in accordance with ASME B1.20.1.
- Be made up with polytetrafluroethylene tape or other thread sealant recommended for oxygen service, with the sealant applied to the male threads only and care taken to ensure sealant does not enter the pipe. [NFPA 99:5.1.10.8, 5.3.6.2.5]
Dielectric fittings shall
comply with the following requirements, and shall only
be permitted where required by the manufacturer of
special medical equipment to electrically isolate the
equipment from the system distribution piping:
- Be of brass or copper construction with an approved dielectric.
- Be permitted to be a union.
- Be clean for oxygen where used for medical gases. [NFPA 99:5.1.10.9.2]
Approved metallic
gas tube fittings that provide a permanent joint having
the mechanical, thermal, and scaling integrity of a
brazed joint shall be permitted to be used. [NFPA
99:5.1.10.9.1]
Welded joints for medical gas and
medical-surgical vacuum systems shall be permitted to be
made using a gas tungsten arc welding (GTAW) autogenous
orbital procedure. [NFPA 99:5.1.10.5.1.1]
Welders shall be qualified in
accordance with Section IX of the ASME Boiler and
Pressure Vessel Code. [NFPA 99:5.1.10.5.2.2]
The
GTAW autogenous orbital procedure and the welder
qualification procedure shall be qualified in accordance
with Section IX of the ASME Boiler and Pressure
Vessel Code. Welder qualification procedures shall
include a bend test and a tensile test in accordance with
Section IX of the ASME Boiler and Pressure Vessel
Code on each tube size diameter. [NFPA 99:5.1.10.5.1.2,
5.1.10.5.1.3]
GTAW autogenous
orbital welded joints shall be purged during
welding with a commercially available mixture of
75 percent helium (+/- 5 percent) and 25 percent
argon (+/- 5 percent). [NFPA 99:5.1.10.5.1.5]
Test coupons shall be
welded and inspected, as a minimum, at the start of
work and every 4 hours thereafter, or where the
machine is idle for more than 30 minutes, and at the
end of the work period. Test coupons shall be
inspected on the I.D. and O.D. by a qualified quality
control inspector, and shall be welded at change of
operator, weld head, welding power supply, or gas
source. [NFPA 99:5.1.10.5.1.7 - 5.1.10.5.1.9]
Stainless tube
shall be welded using metal inert gas (MIG) welding,
tungsten inert gas (TIG) welding, or other welding
techniques approved for joining stainless tube. [NFPA
99:5.1.10.5.2.1]
The following joints shall be prohibited throughout medical gas and medical vacuum
distribution pipeline systems [NFPA 99:5.1.10.10, 5.3.6.2.6]:
- Flared and compression-type connections, including connections to station outlets and inlets, alarm devices, and other components. [NFPA 99:5.1.10.10(1), 5.3.6.2.6(1)]
- Other straight-threaded connections, including unions. [NFPA 99:5.1.10.10(2), 5.3.6.2.6(3)]
- The use of pipe-crimping tools to permanently stop the flow of medical gas and medical vacuum piping. [NFPA 99:5.1.10.10(3)]
- Removable and nonremovable push-fit fittings that employ a quick assembly push fit connector. [NFPA 99:5.1.10.10(4)]
- Push-lock connections for Category 3 medical gas systems. [NFPA 99:5.3.6.2.6(2)]
The installer shall furnish documentation
certifying that installed piping materials for medical gas or
medical vacuum systems are in accordance with Section
1308.0. [NFPA 99:5.1.10.1.6]
Medical gas and medical
vacuum piping systems shall be designed and sized to
deliver the required flow rates at the utilization pressures in
accordance with Section 1310.2.1 through Section
1310.2.3. [NFPA 99:5.1.10.11.1.1, 5.3.6.11.1]
In no case, shall pipe sizing be less than as follows:
In no case, shall pipe sizing be less than as follows:
- Mains and branches in medical gas piping systems shall be not less than DN 15 (NPS 1/2) (5/8 of an inch O.D.) size. [NFPA 99:5.1.10.11.1.2]
- Mains and branches in medical-surgical vacuum systems shall be not less than DN20 (NPS 3/4) (7/8 of an inch O.D.) size. [NFPA 99:5.1.10.11.1.3]
- Drops to individual station outlets and inlets shall be not less than DN15 (NPS 1/2) (5/8 of an inch O.D.) size. [NFPA 99:5.1.10.11.1.4]
- Runouts to alarm panels and connecting tubing for gauges and alarm devices shall be permitted to be DN8 (NPS 1/4) (3/8 of an inch O.D.) size. [NFPA 99:5.1.10.11.1.5]
- Category 3 medical gas piping systems that utilize oxygen shall be not less than DN10 (NPS 3/8) (1/2 of an inch O.D.) size, and systems that utilize nitrous oxide shall be not less than DN8 (NPS 1/4) (3/8 of an inch O.D.) size. [NFPA 99:5.3.6.11.2]
Where the maximum demand for each medical gas or medical vacuum system
does not exceed the values in Table 1310.2.1(2) through
Table 1310.2.1(7), the size of pipe of each section of the
system shall be determined in accordance with Section
1310.2.2. The size for systems beyond the range of
Table 1310.2.1(2) through Table 1310.2.1(7) shall be
determined in accordance with Section 1310.2.3.
For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25
mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 55 psig (379 kPa) at 68°F (20°C).
For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25
mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 55 psig (379 kPa) at 68°F (20°C).
For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25
mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 55 psig (379 kPa) at 68°F (20°C).
For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25
mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 55 psig (379 kPa) at 68°F (20°C).
For SI units: 1 standard cubic foot per minute = 2832 SLPM, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 inch of mercury = 3.386 kPa
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 19 inches of mercury gauge vacuum (64 kPa) at 68°F (20°C).
TABLE 1310.2.1(7)
PRESSURE LOSS FOR VACUUM (CATEGORY 3)
For SI units: 1 standard cubic foot per minute = 2832 SLPM, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 inch of mercury = 3.386 kPa
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 19 inches of mercury gauge vacuum (64 kPa) at 68°F (20°C).
FLOW RATE (SCFM)1 |
PRESSURE DROP (psi) PER 100 FEET2 | ||
---|---|---|---|
1/2 INCH PIPE | 3/4 INCH PIPE | 1 INCH PIPE | |
0.35 | 0.004 | 0.001 | - |
0.71 | 0.012 | 0.003 | - |
1.06 | 0.023 | 0.005 | - |
1.41 | 0.037 | 0.007 | - |
1.77 | 0.055 | 0.011 | - |
2.12 |
0.075 | 0.015 | - |
2.47 | 0.097 | 0.019 | - |
2.82 | 0.123 | 0.024 | - |
3.18 | 0.151 | 0.029 |
- |
3.53 | 0.181 | 0.035 | - |
4.24 | 0.249 | 0.048 | - |
4.94 |
0.326 | 0.063 | - |
5.65 |
0.413 | 0.080 | - |
6.36 |
0.507 | 0.098 | - |
7.06 |
0.611 | 0.118 | 0.030 |
7.77 |
0.723 | 0.139 | 0.035 |
8.47 | 0.843 | 0.139 | 0.041 |
9.18 | 0.969 | 0.187 | 0.047 |
9.89 | 1.108 | 0212 | 0053 |
10.59 | 1.252 | 0.240 | 0.060 |
12.36 | 1.647 | 0.315 | 0.079 |
14.12 | 2.090 | 0.398 | 0.100 |
15.89 | 2.580 | 0.490 | 0.123 |
17.66 | 3.116 | 0.591 | 0.148 |
19.42 | - | 0.701 | 0.176 |
21.19 | - | 0.818 | 0.205 |
22.95 | - | 0.944 | 0.236 |
24.72 | - | 1.078 | 0.268 |
28.25 | - | 1.369 | 0.341 |
31.78 | - | 1.690 | 0.421 |
35.31 | - | 2.043 | 0.509 |
38.84 | - | 2.425 | 0.603 |
42.37 | - | 2.838 | 0.705 |
45.90 | - | 3.280 | 0.814 |
49.43 | - | 3.751 | 0.929 |
52.97 | - | 4.249 | 1.052 |
56.50 | - | - | 1.181 |
60.03 | - | - | 1.318 |
63.56 | - | - | 1.461 |
67.09 | - | - | 1.611 |
70.62 | - | - | 1.768 |
81.21 | - | - | 2.276 |
88.28 | - | - | 2.647 |
95.34 | - | - | 3.044 |
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 55 psig (379 kPa) at 68°F (20°C).
FLOW RATE (SCFM)1 |
PRESSURE DROP (psi) PER 100 FEET2 | ||
---|---|---|---|
1/2 INCH PIPE | 3/4 INCH PIPE | 1 INCH PIPE | |
5.30 | 0.126 | 0.024 | - |
10.59 | 0.430 | 0.082 | - |
15.89 | 0.886 | 0.168 | - |
21.19 | 1.485 | 0.281 | - |
26.48 | 2.220 | 0.419 | - |
31.48 | 3.089 | 0.581 | - |
37.08 | 4.087 | 0.766 | - |
42.37 | - | 0.975 | - |
47.67 | - | 1.206 | - |
52.97 | - | 1.460 | 0.361 |
58.26 | - | 1.736 | 0.429 |
63.56 | - | 2.033 | 0.502 |
68.85 | - | 2.352 | 0.580 |
74.15 | - | 2.692 | 0.663 |
79.45 | - | 3.054 | 0.752 |
84.74 | - | 3.436 | 0.845 |
90.04 | - | 3.840 | 0.943 |
95.34 | - | 4.264 | 1.046 |
100.63 | - | 4.709 | 1.154 |
105.93 | - | - | 1.267 |
116.52 | - | - | 1.508 |
127.12 | - | - | 1.768 |
137.71 | - | - | 2.046 |
148.30 | - | - | 2.344 |
158.90 | - | - | 2.660 |
169.49 | - | - | 2.994 |
180.08 | - | - |
3.347 |
190.67 | - | - | 3.719 |
201.27 | - | - | 4.108 |
211.86 | - | - | 4.516 |
222.45 | - | - | 4.942 |
233.05 | - | - | - |
243.64 | - | - | - |
254.23 | - | - | - |
264.83 | - | - | - |
275.42 | - | - | - |
286.01 | - | - | - |
296.60 | - | - | - |
307.20 | - | - | - |
317.79 | - | - | - |
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 55 psig (379 kPa) at 68°F (20°C).
FLOW RATE (SCFM)1 |
PRESSURE DROP (psi) PER 100 FEET2 | ||
---|---|---|---|
1/2 INCH PIPE | 3/4 INCH PIPE | 1 INCH PIPE | |
0.35 | 0.004 | - | - |
0.71 | 0.014 | - | - |
1.06 | 0.029 | - | - |
1.41 | 0.047 | - | - |
1.77 | 0.070 | - | - |
2.12 | 0.096 | - | - |
2.47 | 0.125 | - | - |
2.82 | 0.159 |
- | - |
3.18 | 0.195 | - | - |
3.53 | 0.235 | 0.045 | - |
4.24 | 0.324 | 0.062 | - |
4.94 | 0.425 | 0.081 | - |
5.65 | 0.539 | 0.103 | - |
6.36 | 0.664 | 0.127 | - |
7.06 | 0.802 | 0.153 | 0.038 |
7.77 | 0.950 | 0.181 | 0.045 |
8.47 | 1.110 | 0.211 | 0.053 |
9.18 | 1.281 | 0.243 | 0.061 |
9.89 | 1.463 | 0.278 | 0.070 |
10.59 | 1.656 | 0.314 | 0.079 |
12.36 | 2.186 | 0.413 | 0.103 |
14.12 | 2.752 | 0.525 | 0.131 |
15.89 | 3.442 | 0.648 | 0.162 |
17.66 | 4.166 | 0.783 | 0.195 |
19.42 | - | 0.929 | 0.231 |
21.19 | - | 0.744 | 0.270 |
22.95 | - | 0.858 | 0.312 |
24.72 | - | 0.980 | 0.356 |
28.25 | - | 1.244 | 0.453 |
31.78 | - | 1.537 | 0.560 |
35.31 | - | 1.858 | 0.677 |
38.84 | - | 2.205 | 0.804 |
42.37 | - | 2.581 | 0.941 |
45.90 | - | 2.982 | 1.088 |
49.43 | - | 3.411 | 1.245 |
52.97 | - | 4.249 | 1.411 |
56.50 | - | - | 1.587 |
60.03 | - | - | 1.772 |
63.56 | - | - | 1.967 |
67.09 | - | - | 2.174 |
70.62 | - | - | 2.385 |
79.45 | - | - | 2.959 |
88.28 | - | - | 3.589 |
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 55 psig (379 kPa) at 68°F (20°C).
FLOW RATE (SCFM)1 |
PRESSURE DROP (psi) PER 100 FEET2 | ||
---|---|---|---|
1/2 INCH PIPE | 3/4 INCH PIPE | 1 INCH PIPE | |
0.35 | 0.004 | - | - |
0.71 | 0.013 | 0.003 | - |
1.06 | 0.025 | 0.005 | - |
1.41 | 0.041 | 0.008 | - |
1.77 | 0.060 | 0.012 | - |
2.12 | 0.082 | 0.016 | - |
2.47 | 0.107 | 0.021 | - |
2.82 | 0.135 | 0.026 | - |
3.18 | 0.166 | 0.032 | - |
3.53 | 0.199 | 0.038 | - |
4.24 | 0.274 | 0.053 | - |
4.94 | 0.359 | 0.069 | - |
5.65 | 0.454 | 0.087 | - |
6.36 | 0.558 | 0.107 | - |
7.06 | 0.672 | 0.129 | 0.033 |
7.77 | 0.795 | 0.153 | 0.039 |
8.47 | 0.927 | 0.179 | 0.045 |
9.18 |
1.066 | 0.205 | 0.052 |
9.89 | 1.218 | 0.233 | 0.059 |
10.59 | 1.377 | 0.263 | 0.066 |
12.36 | 1.811 | 0.346 | 0.087 |
14.12 | 2.298 | 0.438 | 0.110 |
15.89 | 2.837 | 0.539 | 0.135 |
17.66 | 3.456 | 0.650 | 0.163 |
19.42 | - | 0.771 |
0.193 |
21.19 | - | 0.900 | 0.225 |
22.95 | - | 1.038 | 0.260 |
24.72 | - | 1.185 | 0.295 |
28.25 | - | 1.505 | 0.375 |
31.78 | - | 1.859 | 0.463 |
35.31 | - | 2.247 |
0.559 |
38.84 | - | 2.667 | 0.663 |
42.37 | - | 3.121 | 0.775 |
45.90 | - | 3.607 | 0.895 |
49.43 | - | 4.125 | 1.022 |
52.97 | - | - | 1.157 |
56.50 | - | - | 1.299 |
60.03 | - | - | 1.449 |
63.56 | - | - | 1.607 |
67.09 | - | - | 1.772 |
70.62 | - | - | 1.944 |
81.21 | - | - | 2.503 |
91.81 | - | - | 3.127 |
102.40 | - | - | 3.813 |
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 55 psig (379 kPa) at 68°F (20°C).
FLOW RATE (SCFM)1 |
VACUUM LOSS (inch of mercury) PER 100 FEET FOR COPPER TUBE2 | ||||
3/4 INCH TUBE |
1 INCH TUBE |
11/4 INCH TUBE | 11/2 INCH TUBE | 2 INCH TUBE | |
0.35 | 0.019 | - | - | - | - |
0.71 | 0.061 | - | - | - | - |
1.06 | 0.120 | - | - | - | - |
1.41 | 0.194 | - | - | - | - |
1.77 | 0.284 | - | - | - | - |
2.12 | 0.387 | - | - | - | - |
2.47 | 0.504 | - | - | - | - |
2.82 | 0.634 | - | - | - | - |
3.18 | 0.777 | - | - | - | - |
3.53 | 0.932 | 0.238 | - | - | - |
4.24 | 1.277 | 0.325 | - | - | - |
4.94 | 1.669 | 0.424 | - | - | - |
5.65 | 2.106 | 0.534 | - | - | - |
6.36 | 2.586 | 0.655 | - | - | - |
7.06 | 3.110 | 0.787 | 0.272 | - | - |
7.77 | 3.674 | 0.929 | 0.321 | - | - |
8.47 | 4.280 | 1.081 | 0.373 | - | - |
9.18 | 4.927 | 1.243 | 0.429 | - | - |
9.89 | - | 1.416 | 0.488 | - | - |
10.59 | - | 1.597 | 0.551 | 0.242 | - |
11.30 | - | 1.789 | 0.616 | 0.270 | - |
12.01 | - | 1.990 | 0.685 | 0.300 | - |
12.71 | - | 2.200 | 0.757 | 0.332 | - |
13.42 | - | 2.419 | 0.832 | 0.365 | - |
14.12 | - | 2.648 | 0.911 | 0.399 | - |
14.83 | - | 2.886 | 0.992 | 0.435 | - |
15.54 | - | 3.132 | 1.077 | 0.471 | - |
16.24 | - | 3.388 | 1.164 | 0.510 | - |
16.95 | - | 3.652 | 1.254 | 0.549 | - |
17.66 | - | 3.925 | 1.348 | 0.590 | - |
18.36 | - | 4.207 | 1.444 | 0.632 | 0.167 |
19.07 | - | 4.498 | 1.543 | 0.675 | 0.179 |
19.77 | - | 4.797 | 1.646 | 0.720 | 0.190 |
20.48 | - | - | 1.751 | 0.766 | 0.202 |
21.19 | - | - | 1.859 | 0.813 | 0.214 |
24.72 | - | - | 2.441 | 1.066 | 0.281 |
28.25 | - | - | 3.092 | 1.350 | 0.356 |
31.78 | - | - | 3.811 | 1.662 | 0.438 |
35.31 | - | - | 4.596 | 2.004 | 0.527 |
38.84 | - | - | - | 2.373 | 0.624 |
42.37 | - | - | - | 2.770 | 0.728 |
45.90 | - | - | - | 3.194 | 0.838 |
49.43 | - | - | - | 3.645 | 0.956 |
52.97 | - | - | - | 4.122 | 1.081 |
56.50 | - | - | - | 4.626 | 1.212 |
63.56 | - | - | - | - | 1.495 |
70.62 | - | - | - | - | 1.803 |
77.68 | - | - | - | - | 2.138 |
84.74 | - | - | - | - | 2.497 |
91.81 | - | - | - | - | 2.882 |
98.87 | - | - | - | - | 3.291 |
105.93 | - | - | - | - | 3.724 |
112.99 | - | - | - | - | 4.181 |
Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 19 inches of mercury gauge vacuum (64 kPa) at 68°F (20°C).
PRESSURE LOSS FOR VACUUM (CATEGORY 3)


Notes:
1 Based on pressure of 14.7 psig (101 kPa) at 68°F (20°C).
2 Based on pressure of 19 inches of mercury gauge vacuum (64 kPa) at 68°F (20°C).
The size of each section of pipe in a system within the range of Table
1310.2.1(2) through Table 1310.2.1(7) shall be determined
in accordance with the following:
Notes:
1 Flow rates of station outlets and inlets in accordance with Table 1305.2.
For SI units: 1 pound-force per square inch = 6.8947 kPa, 1 inch of
mercury = 3.386 kPa
- Determine the total flow rate and number of outlets or inlets for each section of pipe in accordance with Table 1305.2 and Table 1305.3.
- Measure the length of the section of pipe to each station outlet or inlet on the system. Multiply the measured pipe length by 1.5 (150 percent), to account for the number of fittings in the system, to determine the pipe equivalent length.
- Beginning with the most remote outlet or inlet, multiply the total flow rate by the diversity factor specified in Table 1310.2.1(1) for each section of pipe to determine the sizing flow rate for the piping.
- Select Table 1310.2.1(2) through Table 1310.2.1(7) based on the medical gas or medical vacuum being transported through the piping.
- Select an estimated pipe size for determining the system pressure loss. Multiply the pipe equivalent length, for a given section of pipe, by the pressure loss for the sizing flow rate in the applicable table. Divide that number by 100 to determine the system pressure loss for the section of pipe.
- Add the pressure loss for each section of piping, from the source equipment location to the outlet or inlet, to determine the total system pressure loss to each outlet or inlet. The total system pressure loss in the piping to each outlet or inlet shall not exceed the values specified in Table 1310.2.2(1).
NUMBER OF OUTLETS AND INLETS TERMINAL UNITS PER FACILITY |
DIVERSITY PERCENTAGE OF AVERAGE FLOW PER OUTLETS AND INLETS TERMINAL UNITS |
MINIMUM PERMISSIBLE SYSTEM FLOW OF ALL PRESSURIZED MEDICAL GAS SYSTEMS2 (standard cubic feet per minute) |
1-10 | 100% | Actual Demand |
11-25 | 75% | 7.0 |
26-50 | 50% | 13.1 |
51-100 | 50% | 17.5 |
1 Flow rates of station outlets and inlets in accordance with Table 1305.2.
2 The minimum system flow is the average outlets and inlets flow times the number of station outlets and inlets times the diversity percentage.
TYPE OF SYSTEM | MAXIMUM ALLOWABLE SYSTEM PRESSURE LOSS (psi) |
---|---|
Medical Air |
5 |
Nitrogen | 15 |
Nitrous Oxide |
5 |
Carbon Dioxide |
5 |
Oxygen | 5 |
Medical Vacuum |
4 inches of mercury |
For conditions
other than those covered by Section 1310.2.1, such as
longer runs of greater gas or vacuum demands, the size
of each medical gas or medical vacuum piping system
shall be determined by standard engineering methods
acceptable to the Authority Having Jurisdiction, and
each system shall be so designed that the total pressure
drop or gain between the source equipment and an
outlet or inlet shall not exceed the allowable pressures
shown in Table 1305.1.
Piping shall be protected against
freezing, corrosion, and physical damage . [NFPA 99:5.1.10.11.2, 5.3.6.11.4.1]
Piping exposed in corridors
and other areas where subject to physical damage
from the movement of carts, stretchers, beds, portable
equipment, or vehicles shall be protected. [NFPA 99:5.1.1 0.11.2.1, 5.3.6.11.4.2]
Piping underground
within buildings or embedded in concrete floors or walls shall be installed in a continuous conduit. [NFPA
99:5.1.10.11.2.2]
Exception: Category 3 medical gas piping shall not be installed within floor slabs. [NFPA 99:5.3.6.15]
Exception: Category 3 medical gas piping shall not be installed within floor slabs. [NFPA 99:5.3.6.15]
Buried piping outside of
buildings shall be installed below the local level of
frost penetration. [NFPA 99:5.1.10.11.5.1, 5.3.6.13.1]
Piping shall not be
installed in kitchens, elevator shafts, elevator machine
rooms, areas with open flames, electrical service equipment
exceeding 600 volts, and areas prohibited under
California Electrical Code except for the following
locations:
- Room locations for medical air compressor supply systems and medical-surgical vacuum pump supply systems.
- Room locations for secondary distribution circuit panels and breakers having a voltage rating not exceeding 600 volts. [NFPA 99:5.1.10.11.3.2]
- Medical gas piping, including oxygen and nitrous oxide piping, shall not be located where subject to contact with oil, including a possible flooding area in the case of a major oil leak. [NFPA 99:5.1.10.11.3.4, 5.3.6.11.3]
Medical gas piping shall
be permitted to be installed in the same service trench or
tunnel with fuel gas lines, fuel oil lines, electrical lines,
steam lines, and similar utilities provided that the space is
ventilated (naturally or mechanically) and the ambient
temperature around the medical gas piping does not
exceed 130°F (54°C). [NFPA 99:5.1.10.11.3.3]
Piping shall be supported from the building structure. [NFPA 99:5.1.10.11.4.1, 5.3.6.12.1]
Maximum support
spacing for metallic piping shall be in accordance with
Table 1310.5.4(1). [NFPA 99:5.1.10.11.4.5, 5.3.6.12.5]
Maximum support spacing for plastic pipe shall be in
accordance with Table 1310.5.4(2). [NFPA 99:5.3.8.3.4]
PIPE SIZE |
HANGER SPACING (feet) |
||
---|---|---|---|
DN8 | (NPS 1/4) | (3/8 of an inch O.D.) | 5 |
DN10 | (NPS 3/8) | (1/2 of an inch O.D.) | 6 |
DN15 | (NPS 1/2) | (5/8 of an inch O.D.) | 6 |
DN20 | (NPS 3/4) | (7/8 of an inch O.D.) | 7 |
DN25 | (NPS 1) | (11/8 of an inch O.D.) | 8 |
DN32 | (NPS 11/2) | (13/8 of an inch O.D.) | 9 |
DN40 and larger |
(NPS 11/2) | (15/8 of an inch O.D.) | 10 |
Vertical risers, all sizes, every floor, but not to exceed: |
15 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
PIPE SIZE |
HANGER SPACING (feet) |
||
---|---|---|---|
DN15 | (NPS 1/2) | (5/8 of an inch O.D.) | 4 |
DN20 | (NPS 3/4) | (7/8 of an inch O.D.) | 4 |
DN25 | (NPS 1 | (11/8 of an inch O.D.) | 4.33 |
DN32 | (NPS 11/4) | (13/8 of an inch O.D.) | 4.33 |
DN40 | (NPS 11/2) | (15/8 of an inch O.D.) | 4.67 |
DN50 | (NPS 2) | (23/8 of an inch O.D.) | 4.67 |
DN65 and larger |
(NPS 21/2) | (27/8 of an inch O.D.) | 5 |
Vertical risers, all sizes, every floor, but not to exceed: |
10 |
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
Where required, medical gas and medical vacuum piping shall be seismically restrained against earthquakes in accordance with
the applicable building code. [NFPA 99:5.1.10.11.4.6]
The installation procedure
for underground piping shall protect the piping from
physical damage while being backfilled. [NFPA
99:5.1.10.11.5.2, 5.3.6.13.2]
Underground
piping shall comply with the following where protected
by a conduit, cover, or other enclosure:
- Access shall be provided at the joints for visual inspection and leak testing.
- The conduit, cover, or enclosure shall be self-draining and not retain groundwater in prolonged contact with the pipe. [NFPA 99:5.1.10.11.5.3, 5.3.6.13.3]
Buried piping that will be
subject to surface loads shall be buried at a depth that
will protect the piping or its enclosure from excessive
stresses. [NFPA 99:5.1.10.11.5.4, 5.3.6.13.4]
The minimum backfilled
cover above the top of the piping or its enclosure for
buried piping outside of buildings shall be 36 inches
(914 mm), except that the minimum cover shall be permitted to be reduced to 18 inches (457 mm) where
there is no potential for damage from surface loads or
surface conditions. [NFPA 99:5.1.10.11.5.5, 5.3.6.13.5]
Trenches shall be excavated so
that the piping or its enclosure has firm, substantially
continuous bearing on the bottom of the trench. [NFPA
99:5.1.10.11.5.6, 5.3.6.13.6]
Backfill shall be
clean, free from material that is capable of damaging
the pipe, and compacted. [NFPA 99:5.1.10.11.5.7,
5.3.6.13.7]
A continuous warning tape or
marker placed immediately above the piping or its
enclosure shall clearly identify the pipeline by specific
name. [NFPA 99:5.1.10.11.5.8, 5.3.6.13.8]
A continuous warning means shall
be provided above the pipeline at approximately one-half
the depth of burial. [NFPA 99:5.1.10.11.5.9,
5.3.6.13.9]
Where underground piping is
installed through a wall sleeve, the outdoor end of the
sleeve shall be sealed watertight to prevent the entrance
of groundwater into the building. [NFPA
99:5.1.10.11.5.10, 5.3.6.13.10]
Hose and flexible connectors, both metallic and nonmetallic, shall not be longer than necessary
and shall not penetrate or be concealed in walls, floors, ceilings,
or partitions. [NFPA 99:5.1.10.11.6.1, 5.3.6.16.1]
Hose and flexible connectors for Category 3 medical gas shall be gas specific and not be permitted to conduct any other gas, gas mixture, or liquid. [NFPA 99:5.3.6.16.5]
Exception: Flexible connectors, used in Category 3 systems, of other than all-metal construction that connect manifolds to the gas distribution piping shall not exceed 5 feet (1524 mm) in length. [NFPA 99:5.3.6.21.9]
Hose and flexible connectors for Category 3 medical gas shall be gas specific and not be permitted to conduct any other gas, gas mixture, or liquid. [NFPA 99:5.3.6.16.5]
Exception: Flexible connectors, used in Category 3 systems, of other than all-metal construction that connect manifolds to the gas distribution piping shall not exceed 5 feet (1524 mm) in length. [NFPA 99:5.3.6.21.9]
Hose and flexible
connectors, metallic or nonmetallic, shall have a burst
gauge pressure of not less than 1000 psi (6895 kPa).
[NFPA 99:5.1.10.11.6.2, 5.3.6.16.2]
Metallic flexible
joints shall be permitted in the pipeline where required
for expansion joints, seismic protection, thermal expansion,
or vibration control and shall be as follows:
- For wetted surfaces, made of bronze, copper, or stainless steel.
- Cleaned at the factory for oxygen service and received on the job site with certification of cleanliness.
- Approved for service at 300 psig (2068 kPa) or more and able to withstand temperatures of 1000°F (538°C).
- Provided with brazing extensions to allow brazing into the pipeline in accordance with Section 1309.3.
- Supported with pipe hangers and supports as required for their additional weight. [NFPA 99:5.1.10.11.6.3]
Two or
more medical gas or medical vacuum piping systems shall
not be interconnected for installation, testing, or other
reason. [NFPA 99:5.1.10.11.7.1]
Leak testing shall be accomplished
by separately charging and testing each individual
piping system. [NFPA 99:5.1.10.11.7.2]
Where a positive-pressure
medical gas piping distribution system, originally
used or constructed for the use at one pressure and for one
gas, is converted for operation at another pressure or for
another gas, the provisions of Section 1308.0 shall apply as
if the system were new. [NFPA 99:5.1.10.11.9.1]
A medical vacuum
system shall not be permitted to be converted for use as a
medical gas system. [NFPA 99:5.1.10.11.9.2]
Positive pressure patient medical gas piping shall not be
breached or penetrated by any means or process that will
result in residual copper particles or other debris remaining
in the piping or affect the oxygen-clean interior of the
piping. The breaching or penetrating process shall ensure
that debris created by the process remains contained within
the work area. [NFPA 99:5.1.10.11.12]
Color and pressure requirements shall be in accordance with Table 1305.1.
Medical gas piping shall not be painted. [NFPA
99:5.1.11.1.3]
Piping shall be labeled by stenciling or adhesive markers that identify the patient medical gas or medical vacuum system and include the
following:
- The name of the medical gas or medical vacuum system or the chemical symbol shall comply with Table 1305.1.
- The medical gas or medical vacuum system color code shall comply with Table 1305.1.
- Where positive-pressure gas piping systems operate at pressures other than the standard gauge pressure in Table 1305.1, the pipe labeling shall include the operating pressure in addition to the name of the gas. [NFPA 99:5.1.11.1.1]
The interior surfaces of tube ends,
fittings, and other components that were cleaned for oxygen
service by the manufacturer, but become contaminated prior
to being installed, shall be permitted to be recleaned on-site
by the installer by thoroughly scrubbing the interior
surfaces with a clean, hot water-alkaline solution, such as sodium carbonate or trisodium phosphate, using a solution
of 1 pound (0.5 kg) of sodium carbonate or trisodium phosphate
to 3 gallons (11 L) of potable water and thoroughly
rinsing them with clean, hot potable water. Other aqueous
cleaning solutions shall be permitted to be used for on-site recleaning provided that they are as recommended in CGA
G-4.1. [NFPA 99:5.1.10.4.3.10, 5.1.10.4.3.11]
Material that has become
contaminated internally and is not clean for oxygen service
shall not be installed. [NFPA 99:5.1.10.4.3.12, 5.3.6.6.8]
New or replacement shutoff valves for
medical gas or medical vacuum systems shall be as follows:
- Quarter tum, full ported, ball type.
- Brass or bronze construction.
- Have extensions for brazing.
- Have a handle indicating open or closed.
- Consist of three pieces permitting in-line serviceability. [NFPA 99:5.1.4.3]
Shutoff valves, except valves in
zone valve box assemblies, shall be located in secured
areas such as locked piped chases, or be locked or
latched in their operating position. [NFPA 99:5.1.4.2]
Shutoff valves accessible to other than authorized personnel shall be installed in
valve boxes with frangible or removable windows large
enough to permit manual operation of valves. Shutoff
valves for use in certain areas, such as psychiatric or
pediatric areas, shall be permitted to be secured with the
approval of the Authority Having Jurisdiction to prevent
inappropriate access. [NFPA 99:5.1.4.2.1, 5.1.4.2.2]
Where a central
Category 3 medical gas (oxygen and nitrous oxide)
supply is remote from a single treatment facility, the
main supply line shall be provided with an emergency
shutoff valve so located in the single treatment facility
as to be accessible from all use-point locations in an
emergency. Where a central Category 3 medical gas
(oxygen and nitrous oxide) supply system supplies two
treatment facilities, each facility shall be provided with
an emergency shutoff valve so located in the treatment
facility as to be accessible from all use-point locations
in an emergency. [NFPA 99:5.3.6.19.1, 5.3.6.19.2]
A remotely activated
shutoff valve at a supply manifold shall not
be used for emergency shutoff. For clinical
purposes, such a remote valve actuator shall not fail-closed
in the event of a loss of electric power. Where
remote actuators are the type that fail-open, it shall
be mandatory that cylinder shutoff valves be close
where the system is not in use. [NFPA 99:5.3.6.19.4]
Shutoff valves shall be labeled in
accordance with Section 1312.9.
A shutoff valve shall be placed at
the immediate connection of each source system to the
piped distribution system to permit the entire source, including accessory devices to be isolated from the facility.
[NFPA 99:5.1.4.4]
The source valve shall be located in the immediate vicinity of the source equipment.
[NFPA 99:5.1.4.4.1]
A shutoff valve shall be provided in the main supply line inside of the building, except where
one or more of the following conditions exist:
- The source and source valve are located inside the building served.
- The source system is physically mounted to the wall of the building served, and the pipeline enters the building in the immediate vicinity of the source valve. [NFPA 99:5.1.4.5]
The main line valve shall be located to permit access by authorized personnel only. [NFPA 99:5.1.4.5.1]
The main line valve shall be located on the facility side of the source valve and
outside of the source room, enclosure, or where the
main line first enters the building. [NFPA 99:5.1.4.5.2]
Riser valves shall be permitted to
be located above ceilings, but shall remain accessible
and not be obstructed. [NFPA 99:5.1.4.6.1]
Not more than one service
valve shall be required for each branch off of a riser
regardless of how many zone valve boxes are installed
on that lateral. [NFPA 99:5.1.4.7.1]
Service valves shall be placed in the branch piping prior to a zone valve box assembly on that branch. [NFPA 99:5.1.4.7.2]
Service valves shall be placed in the branch piping prior to a zone valve box assembly on that branch. [NFPA 99:5.1.4.7.2]
Service valves shall be located in
one of the following areas:
- Behind a locked access door
- Locked open above a ceiling
- Locked open in a secure area [NFPA 99:5.1.4.7.3]
Station outlets and inlets shall be
supplied through a zone valve as follows:
- The zone valve shall be placed such that a wall intervenes between the valve and outlets or inlets that it controls.
- The zone valve shall serve only outlets and inlets located on that same story.
- The zone valve shall not be located in the same room with the station outlets or inlets that it controls. [NFPA 99:5.1.4.8]
Zone valves shall be
readily operable from a standing position in the
corridor on the same floor they serve. [NFPA
99:5.1.4.8.1]
Zone valves shall be so
arranged that shutting off the supply of medical gas or
medical vacuum to one zone, operating room, or anesthetizing
location will not affect the supply of medical
gas or medical vacuum to another zone, room, location,
or the rest of the system. [NFPA 99:5.1.4.8.2, 5.1.4.8.7.2]
A pressure or vacuum indicator
shall be provided on the station outlet or inlet side of
each zone valve. [NFPA 99:5.1.4.8.3]
A zone valve shall be located
immediately outside each vital life-support area, critical
care area, and anesthetizing location of moderate sedation,
deep sedation, or general anesthesia, in each medical gas,
medical vacuum line, or both, and located so as to be
readily accessible in an emergency. [NFPA 99:5.1.4.8.7]
Gas-delivery
columns, hose reels, ceiling tracks, control panels,
pendants, booms, or other special installations shall be located downstream of the zone valve.
[NFPA 99:5.1.4.8.7.1]
In-line shutoff valves intended for use to isolate piping for maintenance or modification
shall meet the following requirements:
- Be located in a restricted area
- Be locked or latched open
- Be identified in accordance with Section 1312.9 [NFPA 99:5.1.4.9.1]
Shutoff valves provided for the connection of future piping shall meet the following
requirements:
- Be located in a restricted area
- Be locked or latched closed
- Be identified in accordance with Section 1312.9 [NFPA 99:5.1.4.10]
Downstream piping shall be closed with a brazed cap with tubing allowance
for cutting and rebrazing. [NFPA 99:5.1.4.10.2]
Shutoff valves shall be identified as follows:
- The name or chemical symbol for the specific medical gas or medical vacuum system.
- The room or areas served.
- A caution to not close or open valve except in emergency. [NFPA 99:5.1.11.2.1]
Where
positive pressure gas piping systems operate at pressures
other than the standard gauge pressure of 50 psi (345
kPa) to 55 psi (379 kPa), or a gauge pressure of 160 psi
(1103 kPa) to 185 psi (1276 kPa) for nitrogen, the
shutoff valve identification shall also include the
nonstandard operating pressure. [NFPA 99:5.1.11.2.2]
Shutoff valves shall be labeled in
substance as follows:
Source valve(s) shall be labeled in substance as follows:
SOURCE VALVE FOR THE (SOURCE NAME)
[NFPA 99:5.1.11.2.3]
Main line valve(s) shall be labeled in substance as follows:
MAIN LINE VALVE FOR THE
(MEDICAL GAS/VACUUM NAME)
SERVING (NAME OF BUILDING)
[NFPA 99:5.1.11.2.4]
Riser valve(s) shall be labeled in substance as follows:
RISER FOR THE (MEDICAL GAS/
VACUUM NAME) SERVING (NAME OF THE
AREA/BUILDING SERVED BY THE
PARTICULAR RISER)
[NFPA 99:5.1.11.2.5]
Service valve(s) shall be labeled in substance as follows:
SERVICE VALVE FOR THE
(MEDICAL GAS/VACUUM NAME) SERVING
(NAME OF THE AREA/BUILDING
SERVED BY THE PARTICULAR VALVE)
[NFPA 99:5.1.11.2.6]
In-line shutoff valve(s) shall be labeled in substance as follows:
CAUTION
IN-LINE SHUTOFF VALVE FOR THE
(MEDICAL GAS/VACUUM NAME)
DO NOT CLOSE EXCEPT IN EMERGENCY
THIS VALVE CONTROLS SUPPLY TO
(NAME OF THE AREA/BUILDING SERVED
BY THE PARTICULAR VALVE)
Source valve(s) shall be labeled in substance as follows:
SOURCE VALVE FOR THE (SOURCE NAME)
[NFPA 99:5.1.11.2.3]
Main line valve(s) shall be labeled in substance as follows:
MAIN LINE VALVE FOR THE
(MEDICAL GAS/VACUUM NAME)
SERVING (NAME OF BUILDING)
[NFPA 99:5.1.11.2.4]
Riser valve(s) shall be labeled in substance as follows:
RISER FOR THE (MEDICAL GAS/
VACUUM NAME) SERVING (NAME OF THE
AREA/BUILDING SERVED BY THE
PARTICULAR RISER)
[NFPA 99:5.1.11.2.5]
Service valve(s) shall be labeled in substance as follows:
SERVICE VALVE FOR THE
(MEDICAL GAS/VACUUM NAME) SERVING
(NAME OF THE AREA/BUILDING
SERVED BY THE PARTICULAR VALVE)
[NFPA 99:5.1.11.2.6]
In-line shutoff valve(s) shall be labeled in substance as follows:
CAUTION
IN-LINE SHUTOFF VALVE FOR THE
(MEDICAL GAS/VACUUM NAME)
DO NOT CLOSE EXCEPT IN EMERGENCY
THIS VALVE CONTROLS SUPPLY TO
(NAME OF THE AREA/BUILDING SERVED
BY THE PARTICULAR VALVE)
Central supply systems and medical gas
outlets for oxygen, medical air, nitrous oxide, carbon
dioxide, and other patient medical gases shall be piped into
areas where the gases will be used under the direction of
licensed medical professionals for purposes congruent with
the following:
- Direct respiration by patients.
- Clinical application of the gas to a patient.
- Medical device applications directly related to respiration.
- Power for medical devices used directly on patients.
- Calibration of medical devices used in accordance with Section 1313.1 (1) through Section 1313.1(4). [NFPA 99:5.1.3.5.2]
Materials used in central supply
systems shall comply with the following requirements:
- In those portions of systems intended to handle oxygen at gauge pressures that exceed 350 pounds-force per square inch (psi) (2413 kPa), the interconnecting hose shall contain no polymeric materials.
- In those portions of systems intended to handle oxygen or nitrous oxide material, construction shall be compatible with oxygen under the temperatures and pressures to which the components are capable of being exposed in the containment and use of oxygen, nitrous oxide, mixtures of these gases, or mixtures containing more than 23.5 percent oxygen. [NFPA 99:5.1.3.5.4 - 5.1.3.5.4(2), 5.3.6.21.8 - 5.3.6.21.8(2)]
Pressure-relief valves shall be installed in accordance
with Section 1316.2. Each central supply system shall
have a pressure-relief valve set at 50 percent above
normal line pressure, installed downstream of the pressure regulator and upstream of the shutoff valve. This
pressure-relief valve shall be permitted to be set at a
higher pressure, provided another pressure-relief valve
set at 50 percent above normal line pressure is installed
in the main supply line.
Medical air compressors shall be installed in a well-lit, ventilated, and
clean location and shall be accessible. The location shall be
provided with drainage facilities in accordance with this code. The medical air compressor area shall be located
separately from medical gas cylinder system sources, and
shall be readily accessible for maintenance.
Medical air compressors shall be sufficient to serve the peak calculated demand with the
largest single compressor out of service. In no case
shall there be less than two compressors. [NFPA
99:5.1.3.6.3.10(B)]
Medical air compressor systems shall consist of the components listed in Section 1314.1.2.1 or Section 1314.1.2.2.
Category 1 and Category 2 medical air compressor systems shall consist of the following:
- Components shall be arranged to permit service and a continuous supply of medical air in the event of a single fault failure. Component arrangement shall be permitted to very in accordance with the technology(ies) employed, provided an equal level of operating redundancy and medical air quality is maintained. [NFPA 99:5.1.3.6.3.10(A)]
- An automatic means to prevent backflow from on-cycle compressors through off-cycle compressors. [NFPA 99:5.1.3.6.3.2(2)]
- A manual shutoff valve to isolate each compressor from the centrally piped system and from other compressors for maintenance or repair without loss of pressure in the system. [NFPA 99:5.1.3.6.3.2(3)]
- Intake filter-mufflers of the dry type. [NFPA 99:5.1.3.6.3.2(4)]
- Pressure relief valves set at 50 percent above line pressure. [NFPA 99:5.1.3.6.3.2(5)]
- Piping and components between the compressor and the source shutoff valve that do not contribute to contaminant levels. [NFPA 99:5.1.3.6.3.2(6)]
- Materials and devices used between the medical air intake and the medical air source valve shall be permitted to be of a design or construction appropriate for the service as determined by the manufacturer. [NFPA 99:5.1.3.6.3.2(7)]
Category 3 medical air compressor systems shall consist of the following:
- Disconnect switches.
- Motor-starting devices.
- Motor overload protection devices.
- One or more compressors.
- For single, duplex, or multiple compressor systems, means for activation and deactivation of each individual compressor.
- Where multiple compressors are used, manual or automatic means to alternate individual compressors.
- Where multiple compressors are used, manual or automatic means to activate the additional unite(s) where the in-service unite(s) are incapable of maintaining the required pressure.
- Intake filter-mufflers of the dry type.
- Receivers with a manual or automatic drain.
- Shutoff valves.
- Compressor discharge check valves (for multiple compressors).
- Air dryers that maintain not less than 40 percent relative humidity at operating pressure and temperature.
- In-line final particulate or coalescing filters rated at 0.01 micron (0.01 µm), with filter status indicator to ensure the delivery of compressed air with a maximum allowable 0.05 ppm liquid oil.
- Pressure regulators.
- Pressure-relief valve.
- Pressure indicator.
- Moisture indicator. [NFPA 99:5.3.7.6.1]
The medical air compressors shall draw their air from a source of clean air. [NFPA 99:5.1.3.6.3.12(A)]
Where an air source equal to or better than outside air is available, it shall be permitted to be used for the medical air compressors in accordance with the following provisions:
Where an air source equal to or better than outside air is available, it shall be permitted to be used for the medical air compressors in accordance with the following provisions:
- This alternate source of supply air shall be available on a continuous 24 hours-per-day, 7 days-per-week basis.
- Ventilating systems having fans with motors or drive belts located in the air stream shall not be used as a source of medical air intake. [NFPA 99:5.1.3.6.3.12(E)]
Air sources for a compressor(s) located inside a building shall
comply with the following provisions:
- Be located within a space where no chemical based materials are stored or used.
- Be located in a space that is not used for patient medical treatment.
- Not be taken from a room or space in which there is an open or semi-open discharge from a medical vacuum or scavenging system. [NFPA 99:5.3.7.6.5.1]
Compressor intake piping shall be constructed in accordance with Section 1308.5. [NFPA 99:5.1.3.6.3.12(F)]
Compressor air intakes shall be located as follows:
- Not less than 25 feet (7620 mm) from ventilating system exhausts, fuel storage vents, combustion vents, plumbing vents, medical vacuum and WAGD discharges, or areas that are capable of collecting vehicular exhausts or other noxious fumes. [NFPA 99:5.1.3.6.3.12(B)]
- Not less than 20 feet (6096 mm) above ground level. [NFPA 99:5.1.3.6.3.12(C)]
- Not less than 10 feet (3048 mm) from a door, window, or opening in the building. [NFPA 99:5.1.3.6.3.12(D)]
Air intakes for separate compressors shall be permitted to be
joined together to one common intake where the following conditions are met:
- The common intake is sized to minimize backpressure in accordance with the manufacturer's instructions.
- Each compressor is capable of being isolated by manual or check valve, blind flange, or tube cap to prevent open inlet piping where the compressor(s) is removed for service from the consequent backflow of room air into the other compressor(s). [NFPA 99:5.1.3.6.3.12(G)]
The end of the intake shall be turned down and screened or otherwise protected against the entry of vermin, debris, or precipitation by screening fabricated or composed of a noncorroding material. [NFPA 99:5.1.3.6.3.12(H)]
Receivers for medical air shall meet the following requirements [NFPA 99:5.1.3.6.3.6]:
- Be made of corrosion-resistant materials or otherwise be made corrosion resistant. [NFPA 99:5.1.3.6.3.6(1)]
- Comply with Section VIII of the ASME Boiler and Pressure Vessel Code. [NFPA 99:5.1.3.6.3.6(2), 5.3.7.6.2.2]
- Be equipped with a pressure-relief valve, automatic drain, manual drain, sight glass, and pressure indicator. [NFPA 99:5.1.3.6.3.6(3)]
- Be of a capacity sufficient to prevent the compressor from short cycling. [NFPA 99:5.1.3.6.3.6(4), 5.3.7.6.2.1]
Medical air receivers shall be provided with approved valves to allow the flow of compressed air to enter and exit out of separate receiver ports during normal operation and allow the receiver to
be bypassed during service without shutting down the supply of medical air. [NFPA 99:5.1.3.6.3.10(D)]
The vacuum plant shall be installed in a well-lit, ventilated, and clean location with accessibility. The location shall be provided with drainage facilities in accordance with this code. The vacuum plant, where installed as a source, shall be located separately from other medical vacuum system sources, and shall be readily accessible for maintenance.
Medical surgical vacuum sources shall consist of the following:
- Two or more vacuum pumps sufficient to serve the peak calculated demand with the largest single vacuum pump out of service.
- An automatic means to prevent back flow from on cycle vacuum pumps through off-cycle vacuum pumps.
- A shutoff valve or other isolation means to isolate each vacuum pump from the centrally piped system and other vacuum pumps for maintenance or repair without loss of vacuum in the system.
- A vacuum receiver.
- Piping between the vacuum pump(s), discharge(s), receiver(s), and the vacuum source shutoff valve shall be in accordance with Section 1308.5, except that brass, galvanized, or black steel pipe shall be permitted to be used in accordance with the manufacturer's instructions.
- Materials and devices used between the medical vacuum exhaust and the medical vacuum source shall be permitted to be of a design or construction appropriate for the service, as determined by the manufacturer's instructions. [NFPA 99:5.1.3.7.1.2]
Additional pumps shall automatically activate when the pump(s) in operation is incapable of maintaining the required vacuum. [NFPA 99:5.1.3.7.6.1]
Automatic or manual alternation of pumps shall allow division of operating time. Where automatic alternation of pumps is not provided, the facility staff shall arrange a schedule for manual alternation. [NFPA 99:5.1.3.7.6.2]
Automatic or manual alternation of pumps shall allow division of operating time. Where automatic alternation of pumps is not provided, the facility staff shall arrange a schedule for manual alternation. [NFPA 99:5.1.3.7.6.2]
Receivers for vacuum shall meet the following requirements:
- Be made of materials approved by the manufacturer.
- Comply with Section VIII of the ASME Boiler and Pressure Vessel Code.
- Withstand a gauge pressure of 60 psi (414 k Pa) and 30 inch gauge HgV (102 kPa).
- Be equipped with a manual drain.
- Be of a capacity based on the technology of the pumps. [NFPA 99:5.1.3.7.3]
Medical-surgical vacuum pumps shall exhaust in a manner and location that will minimize the hazards of noise and contamination to the facility and its environment. [NFPA 99:5.1.3.7.7.1]
The exhaust shall be located as follows:
- Outdoors.
- Not less than 10 feet (3048 mm) from a door, window, air intake, or other openings in buildings or places of public assembly.
- At a level different from air intakes.
- Where prevailing winds, adjacent buildings, topography, or other influences that will not divert the exhaust into occupied areas or prevent dispersion of the exhaust. [NFPA 99:5.1.3.7.7.2]
The end of the exhaust shall be turned down and screened or otherwise be protected against the entry of vermin, debris, or precipitation by screening fabricated or composed of a noncorroding material. [NFPA 99:5.1.3.7.7.3]
The exhaust shall be free of dips and loops that are capable of trapping condensate or oil, or provided with a drip leg and valved drain at the bottom of the low point. [NFPA 99:5.1.3.7.7.4]
Vacuum exhausts from multiple pumps shall be permitted to be joined together to one common exhaust where in accordance with the following [NFPA 99:5.1.3.7.7.5]:
- The common exhaust is sized to minimize backpressure in accordance with the pump manufacturer's instructions. [NFPA 99:5.1.3.7.7.5(1), 5.3.8.3.11(7)]
- Each pump shall be isolated by manual or check valve, blind flange, or tube cap to prevent open exhaust piping where the pump(s) is removed for service and consequent flow of exhaust air into the room. [NFPA 99:5.1.3.7.7.5(2), 5.3.8.3.11(8)]
Pressure-regulating equipment shall be installed in the supply main upstream of the final line-pressure valve. Where multiple piping systems for the same gas at different operating pressures are required, separate pressure-regulating equipment, relief valves, and source shutoff valves shall be provided for each pressure.
Pressure-relief valves shall close automatically where excess pressure has been released.
Pressure-relief valves set at 50 percent shall be vented to the outside from gas systems, except medical air, or where the total capacity of the supply system is in excess of 3000 cubic feet (84.95 m3) of gas.
Pressure-relief valves shall be brass, bronze, or stainless steel and designed for the gas service. [NFPA 99:5.3.6.21.6]
A pressure-relief valve shall not be isolated from its intended use by a valve.
Pressure and vacuum indicators shall be readable from a standing position. Pressure and vacuum indicators shall be provided at the following locations:
- Adjacent to the alarm-initiating device for source mainline pressure and vacuum alarms in the master alarm system.
- At or in area alarm panels to indicate the pressure, vacuum, or both at the alarm activating device for each system that is monitored by the panel.
- On the station outlet or inlet side of zone valves.
[NFPA 99:5.1.8.2.1, 5.1.8.2.2]
Station outlets and inlets shall be installed in strict accordance with the manufacturer's installation instructions. Each station outlet and inlet for medical gases and medical vacuums shall be gas-specific. [NFPA 99:5.1.5.1, 5.3.6.17.1]
Each station outlet shall consist of a primary and secondary valve (or assembly). [NFPA 99:5.1.5.2, 5.3.6.17.2]
Each station inlet shall consist of a primary valve (or assembly). [NFPA 99:5.1.5.3]
Each station inlet shall consist of a primary valve (or assembly). [NFPA 99:5.1.5.3]
The secondary valve (or assembly) shall close automatically to stop the flow of medical gas (or medical vacuum, where provided)
where the primary valve (or assembly) is removed. [NFPA 99:5.1.5.4, 5.3.6.17.3]
After installation of the piping, but before installation of the station outlets and inlets and other medical gas and medical gas system components (e.g., pressure-actuating switches for alarms, manifolds, pressure gauges, or pressure relief valves), the line shall be blown clear by means of oil-free, dry nitrogen NF.
Station outlets and inlets shall be identified as to the name or chemical symbol for the specific medical gas or medical vacuum provided. [NFPA 99:5.1.11.3.1]
Master, area, and local alarm systems used for medical gas and medical vacuum systems shall include the following:
- Separate visual indicators for each condition monitored, except as permitted for local alarms that are displayed on master alarm panels.
- Visual indicators that remain in alarm until the situation that has caused the alarm is resolved.
- A cancelable audible indication of each alarm condition that produces a sound level of not less than 80 decibels at 3 feet (914 mm).
- A means to visually identify a lamp or LED failure.
- Visual and audible indication that the communication with an alarm initiating device is disconnected.
- Labeling of each indicator, indicating the condition monitored.
- Labeling of each alarm panel for its area of surveillance.
- Reinitiation of the audible signal where another alarm condition occurs while the audible alarm is silenced.
- Power for master, area alarms. sensors, and switches from the life safety branch of the emergency electrical system as described in NFPA 99.
- Power for local alarms, dew point sensors, and carbon monoxide sensors permitted to be from the same essential electrical branch as is used to power the air compressor system.
- Where used for communications, wiring from switches
or sensors that is supervised or protected as required by
Section 517.30(c)(3) of California Electrial Code for
life safety and critical branch circuits in which protection
is one of the following types:
- Conduit
- Free air
- Wire
- Cable tray
- Raceways
- Communication devices that do not use electrical wiring for signal transmission shall be supervised such that failure of communication shall initiate an alarm.
- Assurance by the responsible authority of the facility that the labeling of alarms, where room numbers or designations are used, is accurate and up-to-date.
- Provisions for automatic restart after a power loss of 10 seconds (e.g., during generator startup) without giving false signals or requiring manual reset
- Alarm switches, sensors, or both installed so as to be removable. [NFPA 99:5.1.9.1]
Warning systems for medical gas systems (oxygen and nitrous oxide) in Category 3 facilities shall include the following:
- Alarms for the following:
- Warning systems shall have not less than one single alarm panel in each treatment facility served by the medical gas source equipment.
- Alarm panels shall be located in an area of continuous surveillance while the facility is in operation.
- Pressure switches, sensors, or both that monitor main line pressure shall be mounted at the source equipment with pressure alarm indicators (lamp or LED) at the alarm panel.
- Audible and noncancelable alarm visual signals shall indicate where the pressure in the main line increases or decreases 20 percent from the normal operating pressure.
- Visual indications shall remain until the situation that caused the alarm is resolved.
- Pressure switches, sensors, or both shall be installed downstream of emergency shutoff valves, and other shutoff valves in the system, and shall cause an alarm for the medical gas where the pressure decreases or increases 20 percent from the normal operating pressure.
- A cancelable audible indication of each alarm condition that produces a sound at the alarm panel shall reinitiate the audible signal where another alarm condition occurs while the audible signal is silenced. [NFPA 99:5.3.6.22]
Functioning of alarm components shall be verified in accordance with the testing and monitoring requirements of the manufacturer and the Authority Having Jurisdiction.
Inspection and testing shall be performed on components, or portions thereof, of new piped medical gas or vacuum systems, additions, renovations, temporary installations, or repaired systems in accordance with Section 1319.2 through Section 1319.12.2, and certified in accordance with Section 1320.0.
Systems that are breached and components that are subject to additions, renovations, or replacement shall be inspected and tested. Systems shall be deemed breached at the point of pipeline intrusion by physical separation or by system component removal, replacement, or addition. Breached portions of the systems subject
to inspection and testing shall be confined to the specific
altered zone and components in the immediate zone or area that is located upstream for medical vacuum systems and downstream for pressure gases at the point or area of intrusion.
[NFPA 99:5.1.12.1.3 - 5.1.12.1.5]
Inspection and testing reports shall be submitted directly to the party that contracted for the testing, who shall submit the report through channels to the responsible facility authority and others that are required. Reports shall contain detailed listings of findings and results. [NFPA 99:5.1.12.1.6, 5.1.12.1.7]
Piping in medical gas and medical vacuum distribution systems shall be blown clear by means of oil-free, dry nitrogen NF after installation of the distribution piping, and before installation of station outlet and inlet rough-in assemblies and other system
components. [NFPA 99:5.1.12.2.2, 5.3.6.23.2.2]
Each section of the piping in medical gas and medical vacuum systems shall be pressure tested by a party qualified in accordance with Section 1306.1, and using oil-free, dry nitrogen NF. [NFPA 99:5.1.12.2.3.1, 5.3.6.23.2.3(A)]
Initial pressure tests shall be conducted in accordance with the following:
Initial pressure tests shall be conducted in accordance with the following:
- After blow down of the distribution piping.
- After installation of station outlet and inlet rough-in assemblies. Test caps shall be permitted to be used.
- Prior to the installation of components of the distribution piping system that would be damaged by the test pressure. [NFPA 99:5.1.12.2.3.2, 5.3.6.23.2.3(B)]
The source shutoff valve for the piping system shall remain closed during tests. [NFPA 99:5.1.12.2.3.3, 5.3.6.23 .2.3(C)]
The test pressure for pressure medical gases and medical vacuum
systems shall be one and one-half times the system working pressure, and not less than a gauge pressure of 150 psi (10 34 kPa). [NFPA 99:5.1.12.2.3.4, 5.3.6.23.2.3(D)] The test pressure shall be maintained until each joint has been examined for leakage by means of a leak detectant that is safe for use with oxygen and does not contain ammonia. [NFPA 99:5.1.12.2.3 .5, 5.3.6.23.2.3(E)]
Leaks shall be located, repaired (where permitted), replaced (where required), and retested. [NFPA 99:5.1.12.2.3.6, 5.3.6.23.2.3(F)]
A party qualified in accordance with Section 1306.1 shall determine that no cross-connections exist between medical gas and medical vacuum piping systems. [NFPA 99:5.1.12.2.4, 5.3.6.23.2.4]
Piping systems shall be reduced to atmospheric pressure. [NFPA
99:5.1.12.2.4.1, 5.3.6.23.2.4(A)]
Sources of test gas shall be disconnected from piping systems except for the one system being tested. [NFPA 99:5.1.12.2.4.2,
5.3.6.23.2.4(D)]
The system under test shall be charged with oil-free, dry nitrogen NF to a gauge pressure of 50 psi (345 kPa). [NFPA 99:5.1.12.2.4.3, 5.3.6.23.2.4(C), 5.3.6.23.2.4(E)]
After the installation of the individual faceplates with approved adapters matching outlet and inlet labels, each individual outlet
and inlet (in each installed medical gas and medical vacuum piping system) shall be checked to determine that the test gas is being dispensed from the piping system being tested. [NFPA 99:5.1.12.2.4.4, 5.3.6.23.2.4(F)]
The cross-connection test shall be repeated for each installed medical gas and medical vacuum piping system. [NFPA 99:5.1.12.2.4.5, 5.3.6.23.2.4(G)]
The proper labeling and identification of system outlets and inlets shall be confirmed during these tests. [NFPA 99:5.1.12.2.4.6, 5.3.6.23.2.4(H)]
After successful completion of the initial pressure tests in accordance with Section 1319.5, medical gas distribution piping shall be subjected to a standing pressure test by a party qualified in accordance with Section 1306.1. [NFPA 99:5.1.12.2.6, 5.3.6.23.2.6]
Tests shall be conducted after the final installation of station outlet valve bodies, face plates, and other distribution system
components. [NFPA 99:5.1.12.2.6.1, 5.3.6.23.2.6(A)]
The source valve shall be closed during testing. [NFPA 99:5.1.12.2.6.2, 5.3.6.23.2.6(B)]
The piping systems shall be subjected to a 24 hour standing pressure test using oil-free , dry nitrogen NF. [NFPA 99:5.1.12.2.6.3, 5.3.6.23.2.6(C)]
At the conclusion of the tests, there shall not be a change in the test pressure except that attributed to changes in ambient temperature. [NFPA 99:5.1.12.2.6.5]
For Category 3 systems, there shall not be a change in the test pressure that exceeds a gauge pressure of 5 psi (34 kPa). [NFPA 99:5.3.6.23.2.6(E)]
For Category 3 systems, there shall not be a change in the test pressure that exceeds a gauge pressure of 5 psi (34 kPa). [NFPA 99:5.3.6.23.2.6(E)]
Leaks shall be located, repaired (where permitted), or replaced (where required), and retested. [NFPA 99:5.1.12.2.6.6, 5.3.6.23.2.6(F)]
The 24 hour standing pressure test shall be witnessed by the Authority Having Jurisdiction or its designee. A form indicating that this test has been performed and witnessed shall be provided to the verifier at the start of the tests required Section 1319.12. [NFPA 99:5.1.12.2.6.7]
Tests shall be conducted after installation of all components of the medical vacuum system. [NFPA 99:5.1.12.2.7.1]
The piping systems shall be subjected to a 24 hour standing vacuum test. [NFPA 99:5.1.12.2.7.2]
During the test, the source of test vacuum shall be disconnected
from the piping system. [NFPA 99:5.1.12.2.7.4]
At the conclusion of the test, there shall not be a change in the vacuum except that attributed to changes in ambient temperature.
[NFPA 99:5.1.12.2.7.5]
Leaks shall be located, repaired (where permitted), or replaced (where required), and retested. [NFPA 99:5.1.12.2.7.7]
The 24 hour standing pressure test of the medical vacuum system shall be witnessed by the Authority Having Jurisdiction or its
designee. A form indicating that this test has been performed and witnessed shall be provided to the verifier at the start of the tests required in Section 1319.12. [NFPA 99:5.1.12.2.7.6]
The outlets in each medical gas piping system shall be purged by a party qualified in accordance with Section 1306.1, using oil-free, dry nitrogen NF to remove particulate matter from the piping. [NFPA 99:5.1.12.2.5, 5.3.6.23.2.5]
Using appropriate adapters, each outlet shall be purged with an intermittent high-volume flow of test gas until the purge produces no discoloration in a clean white cloth. [NFPA 99:5.1.12.2.5.1,
5.3.6.23.2.5(B)]
Purging shall start at the closest outlet or inlet to the zone valve and continue to the furthest outlet or inlet within the zone. [NFPA 99:5.1.12.2.5.2]
Exception: For Category 3 medical gas piping systems, purging shall start at the furthest outlet in the system and proceed toward the source equipment. [NFPA 99:5.3.6.23.2.5(C)]
Exception: For Category 3 medical gas piping systems, purging shall start at the furthest outlet in the system and proceed toward the source equipment. [NFPA 99:5.3.6.23.2.5(C)]
Operational pressure tests shall be performed at each station outlet and inlet or terminal where the user makes connections and disconnections. [NFPA 99:5.1.12.3.10]
Tests shall be performed with the gas of system designation or the operating vacuum. [NFPA 99:5.1.12.3.10.1]
Gas outlets with a gauge pressure of 50 psi (345 kPa), including, but not limited to, oxygen, nitrous oxide, medical air, and
carbon dioxide, shall deliver 3.5 standard cubic feet per minute (SCFM) (100 SLPM) with a pressure drop of not more than 5 psi (34 kPa) and static pressure of 50 psi (345 kPa) to 55 psi (379 kPa). [NFPA 99:5.1.12.3.10.2]
Medical surgical vacuum inlets shall draw 3 SCFM (85 Nl/min)
without reducing the vacuum pressure below 12 inch mercury gauge (HgV) (41 kPa) at any adjacent station inlet. [NFPA 9:5.1.12.3.10.4]
Oxygen and medical air outlets serving critical care areas shall
allow a transient flow rate of 6 SCFM (170 SLPM) for 3 seconds. [NFPA 99:5.1.12.3.10.5]
After purging each system in accordance with Section 1319.9, the
following shall be performed:
- Each pressure gas source and outlet shall be analyzed for concentration of gas, by volume.
- Analysis shall be conducted with instruments designed to measure the specific gas dispensed.
- Allowable concentrations shall be as indicated in Table 1319.11. [NFPA 99:5.1.12.3.11]
MEDICAL GAS | CONCENTRATION |
Oxygen | >99% oxygen |
Nitrous oxide | >99% nitrous oxide |
Nitrogen | <1% oxygen or >99% nitrogen |
Medical air | 19.5% - 23.5% oxygen |
Other gases | As specified by +/-1%, unless otherwise specified |
Verification tests shall be performed after tests in accordance with Section 1319.5 through Section 1319.11 have been completed. [NFPA 99:5.1.12.3.1.1, 5.3.6.23.3.1(C)]
The test gas shall be oil-free, dry nitrogen NF or the system gas where permitted. [NFPA 99:5.1.12.3.1.2, 5.3.6.23.3.1(D)]
Verification testing shall be conducted by a party technically competent and experienced in the field of medical gas and medical
vacuum pipeline testing and meeting the requirements of ASSE 6030. [NFPA 99:5.1.12.3.1.3, 5.3.6.23.3.1(A)]
Testing shall be performed by a party other than the installing contractor, the system supplier, or the system manufacturer. [NFPA 99:5.1.12.3.1.4, 5.3.6.23.3.1(B)]
Where systems have not been installed by in-house personnel, testing shall be permitted by personnel of that organization who meet the requirements of this section. [NFPA 99:5.1.12.3.1.5]
Testing shall be performed by a party other than the installing contractor, the system supplier, or the system manufacturer. [NFPA 99:5.1.12.3.1.4, 5.3.6.23.3.1(B)]
Where systems have not been installed by in-house personnel, testing shall be permitted by personnel of that organization who meet the requirements of this section. [NFPA 99:5.1.12.3.1.5]
Prior to a medical gas or medical vacuum system being placed in service, such system shall be certified in accordance with Section 1320.2.
Certification tests, verified and attested to by the certification agency, shall include the following:
- Verifying in accordance with the installation requirements.
- Testing and checking for leakage, correct zoning, and identification of control valves.
- Checking for identification and labeling of pipelines, station outlets, and control valves.
- Testing for cross-connection, flow rate, system pressure drop, and system performance.
- Functional testing of pressure relief valves and safety valves.
- Functional testing of sources of supply.
- Functional testing of alarm systems, including accuracy of system components.
- Purge flushing of system and filling with specific source gases.
- Testing for purity and cleanliness of source gases.
- Testing for specific gas identity at each station outlet.
A report that includes the specific items addressed in Section 1320.2, and other information required by this chapter, shall be delivered to the Authority Having Jurisdiction prior to acceptance of the system.