Heads up: There are no amended sections in this chapter.
The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

CALIFORNIA MECHANICAL CODE — MATRIX ADOPTION TABLE
APPENDIX B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT IN OPERATION
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting Agency BSC BSC-CG SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
1
2
1-AC
AC
SS
SS/CC
1
1R
2
3
4
5
Adopt Entire Chapter
X
               
X
X
X
X
X
X
               
Adopt Entire Chapter as
amended (amended sections listed below)
                                             
Adopt only those sections
that are listed below
                                             
Chapter/Section                                              
                                               
This state agency does not adopt sections identified with the following symbol:
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
The input rate of the burner shall be adjusted to the proper value in accordance with the appliance manufacturer's instructions. Firing at a rate in excess of the nameplate rating shall be prohibited. The input rate can be adjusted by either changing the size of a fixed orifice, changing the adjustment of an adjustable orifice, or readjusting the appliance's gas pressure regulator outlet pressure (where a regulator is provided in the appliance). [NFPA 54:11.1.1, 11.1.1.1]
Gas input ratings of appliances shall be used for elevations up to 2000 feet (610 m). The input ratings of appliances operating at elevations above 2000 feet (610 m), shall be reduced in accordance with one of the following methods:
  1. At the rate of 4 percent for each 1000 feet (305 m) above sea level before selecting appropriately sized appliances.
  2. As permitted by the Authority Having Jurisdiction.
  3. In accordance with the manufacturer's installation instructions. [NFPA 54:11.1.2]
The primary air for injection (Bunsen)-type burners shall be adjusted for proper flame characteristics in accordance with the appliance manufacturer's instructions. After setting the primary air, the adjustment means shall be secured in position. [NFPA 54:11.2]
Where a safety shutoff device is provided, it shall be checked for proper operation and adjustment in accordance with the appliance manufacturer's instructions. Where the device does not function properly to turn off the gas supply in the event of pilot outage or other improper operation, it shall be properly serviced or replaced with a new device. [NFPA 54:11.3]
Appliances supplied with means for automatic ignition shall be checked for operation within the parameters provided by the manufacturer. Any adjustments made shall be in accordance with the manufacturer's installation instructions. [NFPA 54:11.4]
Where required by the manufacturer's installation instructions, all protective devices furnished with the appliance such as a limit control, fan control to blower, temperature and pressure relief valve, low-water cutoff device, or manual operating features, shall be checked for operation within the parameters provided by the manufacturer. Any adjustments made shall be in accordance with the manufacturer's installation instructions. [NFPA 54:11.5]
Draft hood-equipped appliances shall be checked to verify that there is no draft hood spillage after 5 minutes of main burner operation. [NFPA 54:11.6]
Operating instructions shall be furnished and shall be left in a prominent position near the appliance for use by the consumer. [NFPA 54:11.7]
Linked Resources
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Bookmarks
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More