Heads up: There are no amended sections in this chapter.
CALIFORNIA MECHANICAL CODE - MATRIX ADOPTION TABLE
CHAPTER 16 - STATIONARY POWER PLANTS
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting agency BSC BSC-CG SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
1 2 1-AC AC SS SS/CC 1 1R 2 3 4 5
Adopt entire chapter X X X X X X
Adopt entire chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter / Section
This state agency does not adopt sections identified with the following symbol:
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
Fuel cell power plants with a power output of less than 50 kW shall be listed and installed in accordance with the manufacturer's instructions. Fuel cell power plants with a power output of greater than 50 kW shall be installed in accordance with NFPA 853. [NFPA 54:10.30] Stationary fuel cell power plants shall be tested in accordance with CSA FC-1.
The installation of gas engines shall conform to NFPA 37. [NFPA 54:10.23]
Stationary gas engines shall not be rigidly connected to the gas supply piping. [NFPA 54:10.23.1]
Stationary engine generators shall be tested in accordance with UL 2200, and shall be installed in accordance with NFPA 37 and the manufacturer's installation instructions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING