The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
This chapter shall apply to hydronic
piping systems that are part of heating, cooling, ventilation, refrigeration, and air conditioning systems. Such piping systems
include steam, hot water, chilled water, steam condensate, condenser water, and ground source heat pump systems.
The regulations of this chapter shall govern the construction,
location, and installation of hydronic piping systems.
Surfaces within reach of building occupants
shall not exceed 140°F (60°C). Where sleeves are
installed, the insulation shall continue full size through them.
Coverings and insulation used for piping shall be of material approved for the operating temperature of the system and the installation environment. Where installed in a plenum, the insulation, jackets, and lap-seal adhesives, including pipe coverings and linings, shall have a flame-spread index not to exceed 25 and a smoke-developed index not to exceed 50 where tested in accordance with ASTM E84 or UL 723.
Coverings and insulation used for piping shall be of material approved for the operating temperature of the system and the installation environment. Where installed in a plenum, the insulation, jackets, and lap-seal adhesives, including pipe coverings and linings, shall have a flame-spread index not to exceed 25 and a smoke-developed index not to exceed 50 where tested in accordance with ASTM E84 or UL 723.
The piping system shall be
designed to prevent water hammer.
Terminal units, valves, and flow
control devices shall be installed in accordance with the manufacturer's
installation instructions.
Where a minimum return-water temperature to the heat
source is specified by the manufacturer, the heating system
shall be designed and installed to meet or exceed the minimum
return-water temperature during the normal operation
of the heat source.
Hydronic systems or parts
thereof shall be constructed in such a manner that polluted,
contaminated water or substances shall not enter a portion of
the potable water system either during normal use or where
the system is subject to pressure that exceeds the operating
pressure in the potable water system. Piping, components and
devices in contact with the potable water shall be approved
for such use and where an additive is used it shall not affect
the performance of the system.
Where systems include an
additive, chemical injection or provisions for such injection,
the potable water supply shall be protected by a reduced-pressure
principle backflow prevention assembly listed or labeled
in accordance with ASSE 1013. Such additive or chemical
shall be compatible with system components.
Fluids used in hydronic systems
shall be compatible with all components that will contact the
fluid. Where a heat exchanger is installed with a dual purpose
water heater, such application shall comply with the requirements
for a single wall heat exchanger in Section 1218.1.
The heat source shall be sized to the
design load.
Water heaters utilized for combined space-heating and water-heating applications shall be listed or labeled in accordance with the standards referenced in Table 1203.2, and shall be installed in accordance with the manufacturer's installation instructions. The total heating capacity of a dual purpose water heater shall be based on the sum of the potable hot water requirements and the space heating design requirements corrected for hot water first-hour draw recovery.
For SI units: 1000 British thermal units per hour = 0.293kW
TYPE
|
|
Gas, 75 000 Btu/h or less |
CSA Z21.10.1
|
Gas, Above 75 000 Btu/h |
CSA Z21.10.3
|
Electric, Space Heating |
UL 834
|
Solid Fuel |
UL 2523
|
Tankless water heaters
shall be rated by the manufacturer for space-heating applications,
and the output performance shall be determined by
the temperature rise and flow rate of water through the unit.
The ratings shall be expressed by the water temperature rise
at a given flow rate. Manufacturers flow rates shall not be
exceeded.
In buildings where potable water and nonpotable
water systems are installed, each system shall be
clearly identified in accordance with Section 1204.2 through
Section 1204.5.
Each system shall be identified
with a colored pipe or band and coded with paint,
wraps, and materials compatible with the piping.
Potable water systems shall be identified with a green background with white lettering. The minimum size of letters and length of the color field shall be in accordance with Table 1204.3.
For SI units: 1 inch = 25.4 mm
OUTSIDE DIAMETER OF PIPE OR COVERING (inches) |
MINIMUM LENGTH OF COLOR FIELD (inches) |
MINIMUM SIZE OF LETTERS (inches) |
1/2 to 11/4 | 8 | 1/2 |
11/2 to 2 | 8 | 3/4 |
21/2 to 6 | 12 | 11/4 |
8 to 10 | 24 | 21/2 |
over 10 | 32 | 31/2 |
Nonpotable water systems
shall have a yellow background with black uppercase lettering,
with the words "CAUTION: NONPOTABLE WATER,
DO NOT DRINK." Each nonpotable system shall be identified
to designate the liquid being conveyed, and the direction
of normal flow shall be clearly shown. The minimum size of
the letters and length of the color field shall comply with
Table 1204.3.
The background
color and required information shall be indicated every
20 feet (6096 mm) but not less than once per room, and shall
be visible from the floor level.
Flow directions shall be indicated
on the system.
Operating and maintenance
information shall be provided to the building owner.
System piping and components
shall be tested with a pressure of not less than one and one-half
times the operating pressure but not less than 100 psi (689
kPa). Piping shall be tested with water or air except that plastic
pipe shall not be tested with air. Test pressures shall be held
for a period of not less than 30 minutes with no perceptible
drop in pressure. These tests shall be made in the presence of
the Authority Having Jurisdiction.
Exception: For PEX, PP-R, PP-RCT, PEX-AL-PEX, PE-RT,
and PE-AL-PE piping systems, testing with air shall be permitted
where authorized by the manufacturer's instructions for
the PEX, PP-R, PP-RCT, PEX-AL-PEX, PE-RT, and PE-AL-PE
pipe and fittings products, and air testing is not prohibited
by applicable codes, laws, or regulations outside this code.
Note: [HCD 1 & HCD 2] PEX-AL-PEX is not adopted in the California Plumbing Code for use in potable water supply and distribution systems.
Note: [HCD 1 & HCD 2] PEX-AL-PEX is not adopted in the California Plumbing Code for use in potable water supply and distribution systems.
Heating and cooling sources, system piping
and tubing shall be flushed after installation with water or
a cleaning solution. Cleaning and flushing of the heating and
cooling sources shall comply with the manufacturer's instructions.
The cleaning solution shall be compatible with all system
components and shall be used in accordance with the manufacturer's instructions.
Each closed hydronic system shall be protected
against pressures exceeding design limitations with not
less than one pressure relief valve. Each closed section of the
system containing a heat source shall have a relief valve
located so that the heat source is not capable of being isolated
from a relief device. Pressure relief valves shall be installed in
accordance with their listing and the manufacturer's installation
instructions.
The discharge piping serving a temperature relief valve, pressure relief valve, or combination
of both shall have no valves, obstructions, or means of isolation
and be provided with the following:
- Equal to the size of the valve outlet and shall discharge full size to the flood level of the area receiving the discharge and pointing down.
- Materials shall be rated at not less than the operating temperature of the system and approved for such use.
- Discharge pipe shall discharge independently by gravity through an air gap into the drainage system or outside of the building with the end of the pipe not exceeding 2 feet (610 mm) and not less than 6 inches (152 mm) above the ground and pointing downwards.
- Discharge in such a manner that does not cause personal injury or structural damage.
- No part of such discharge pipe shall be trapped or subject to freezing.
- The terminal end of the pipe shall not be threaded.
- Discharge from a relief valve into a water heater pan shall be prohibited.
Heating appliances, equipment, safety and
operational controls shall be listed for its intended use in a
hydronic heating system and installed in accordance with the
manufacturer's installation instructions.
Boilers and their control systems shall comply
with Section 1002.0.
A condensing boiler,
in which the heat exchanger and venting system are
designed to operate with condensing flue gases, shall be
permitted to be connected directly to the panel heating
system without a protective mixing device.
Where the heat
exchanger and venting system are not designed to operate
with condensed flue gases, the boiler shall be permitted to
connect directly to the panel heating system where protected
from flue gas condensation. The operating temperature
of the boiler shall be more than the fluid temperature
in accordance with the manufacturer's instructions.
Water heaters used
for combined space- and water-heating applications shall be in
accordance with the standards referenced in Table 1203.2, and
shall be installed in accordance with the manufacturer's installation
instructions. Water used as the heat transfer fluid in the
hydronic heating system shall be isolated from the potable
water supply and distribution in accordance with Section
312.1, Section 1202.0, and Section 1218.0.
Where a combined
space- and water-heating application requires water
for space heating at temperatures exceeding 140°F
(60°C), a thermostatic mixing valve that is in accordance
with ASSE 1017 shall be installed to temper the water
supplied to the potable water distribution system to a temperature
of 140°F (60°C) or less.
Solar water heating
systems used in hydronic panel radiant heating systems
shall be installed in accordance with the Uniform Solar Energy
Code and Hydronics Code (USEHC).
Circulators and pumps shall be selected for
their intended use based on the heat transfer fluid, intended
operating temperature range and pressure. Circulators and
pumps shall be installed to allow for service and maintenance.
The manufacturer's installation instructions shall be followed
for correct orientation and installation. Motor Operated pumps
rated 600V or less shall be listed and labeled in accordance
with UL 778.
The circulator or pump shall be installed
in such a way that strain from the piping is not transferred to
the circulator or pump housing. The circulator or pump shall
be permitted to be directly connected to the piping, provided
the piping is supported on each side of the circulator or pump.
Where the installation of a circulator or pump will cause
strain on the piping, the circulator or pump shall be installed
on a mounting bracket or base plate. Where means for controlling vibration of a circulator or pump is required, an
approved means for support and restraint shall be provided.
The selection and sizing of a circulator or
pump shall be based on all of the following:
- Loop or system head pressure, feet of head (m)
- Capacity, gallons per minute (L/s)
- Maximum and minimum temperature, °F (°C)
- Maximum working pressure, pounds per square inch (kPa)
- Fluid type
An expansion tank shall be installed in each
closed hydronic system to control system pressure due to thermal
expansion. Expansion tanks shall be of the closed or open
type. Tanks shall be rated for the pressure of the system.
Expansion tanks shall be accessible for
maintenance and shall be installed in accordance with the manufacturer's installation instructions. Each tank shall be
equipped with a shutoff device that will remain open during
operation of the heating system. Valve handles shall be locked
open or removed to prevent from being inadvertently shut off.
Provisions shall be made for draining the tank without emptying
the system. Expansion tanks shall be securely fastened to
the structure. Supports shall be capable of carrying twice the
weight of the tank filled with water without placing a strain on
connecting piping. Hot-water-heating systems incorporating
hot water tanks or fluid relief columns shall be installed to prevent freezing under normal operating conditions.
Open type expansion
tanks shall be located not less than 3 feet (914 mm) above
the highest point of the system. An overflow with a diameter of
not less than one-half the size of the supply or not less than 1
inch (25 mm) in diameter shall be installed at the top of the tank. The overflow shall discharge through an air gap into the
drainage system.
Closed-type expansion tanks
shall be designed for a hydrostatic test pressure of two and
one-half times the allowable working pressure of the system.
Expansion tanks for systems designed to operate at more than
30 pounds-force per square inch (psi) (207 kPa) shall comply
with ASME BPVC Section VIII.
Expansion tanks shall be sized to accept the
full expansion volume of the fluid in the system. The minimum
capacity of a closed-type expansion tank shall be sized
in accordance with Section 1004.4.
Hydronic pipe and tubing shall comply with the applicable standards referenced in Table 1210.1 and shall be approved for use based on the intended purpose. Materials shall be rated for the operating temperature and pressure of the system and shall be compatible with the type of heat transfer fluid. Pipe fittings and valves shall be approved for the specific installation with the piping, materials to be installed and shall comply with the applicable standards referenced in Table 1210.1. Where required, exterior piping shall be protected against freezing, UV radiation, corrosion and degradation. Embedded pipe or tubing shall comply with Section 1221.2.
Note:
MATERIAL
|
||
PIPING/TUBING
|
FITTINGS
|
|
Copper/Copper Alloy |
ASTM B42, ASTM B43, ASTM B75, ASTM B88, ASTM B135,ASTM B2512, ASTM B302, ASTM B447
|
ASME B16.15, ASME B16.18, ASME B16.22, ASME B16.23, ASME B16.24, ASME B16.26, ASME B16.29, ASME B16.51, ASSE 1061
|
Ductile Iron |
AWWA C115/A21.15, AWWA C151/A21.51
|
AWWA C110/A21.101, AWWA C153/A21.53
|
Steel |
ASTM A53, ASTM A106, ASTM A254
|
ASME B16.5, ASME B16.9, ASME B16.11, ASTM A420
|
Gray Iron |
—
|
ASTM A126
|
Malleable Iron |
—
|
ASME B16.3
|
Chlorinated Polyvinyl Chloride (CPYC) |
ASTM D2846, ASTM F441, ASTM F442, CSA B137.6
|
ASSE 1061, ASTM D2846, ASTM F437, ASTM F438, ASTM F439, ASTM F1970, CSA B137.6
|
Polyethylene (PE) |
ASTM D1693, ASTM D2513, ASTM D2683, ASTM D2737, ASTM D3035, ASTM D3350, ASTM F714, AWWA C901, CSA B137.1, NSF 358-1
|
ASTM D2609, ASTM D2683, ASTM D3261, ASTM F1055, CSA B137.1, NSF 358-1
|
Cross-Linked Polyethylene (PEX) |
ASTM F876, CSA B137.5, NSF 358-3
|
ASSE 1061, ASTM F877, ASTM F1807, ASTM F1960, ASTM F1961, ASTM F2080, ASTM F2098, ASTM F2159, ASTM F2735, CSA B137.5, NSF 358-3
|
Polypropylene (PP) |
ASTM F2389, NSF 358-2
|
ASTM F2389, NSF 358-2
|
Polyvinyl Chloride (PVC) |
ASTM D1785, ASTM D2241, CSA B137.3
|
ASTM D2464, ASTM D2466, ASTM D2467, ASTM F1970, CSA B137.2, CSA B137.3
|
Raised Temperature Polyethylene (PE-RT) |
ASTM F2623, ASTM F2769, CSA B137.18
|
ASSE 1061, ASTM F1807, ASTM F2159, ASTM F2735, ASTM F2769, ASTM D3261, ASTM F1055, CSA B137.18
|
Cross-Linked Polyethylene/Aluminum/Cross-Linked Polyethylene (PEX-AL-PEX) |
ASTM F1281, ASTM F2262, CSA B137.10
|
ASTM F1281, ASTM F1974, ASTM F2434, CSA B137.10
|
Polyethylene/Aluminum/Polyethylene (PE-AL-PE) |
ASTM F1282, CSA B137.9
|
ASTM F1282, ASTM F1974, CSA B137.9
|
Chlorinated Polyvinyl Chloride/Aluminum/Chlorinated Polyvinyl Chloride (CPVC/AL/CPVC) |
ASTM F2855
|
ASTM D2846
|
- 1 Ductile and gray iron.
- 2 Only type K, L, or M tubing allowed to be installed.
Pipe and tubing shall be so installed that it will not be subject to undue strains or stresses, and provisions shall be made for expansion, contraction, and structural settlement. [OSHPD 1, 1R, 2, 4 & 5] Pipe connections less than 21/2 inches (64 mm) to heating coils, cooling coils, humidifiers, and similar equipment shall have flexible connectors or three (3) 90-degree offsets in close proximity of the connection.
Pipe and tubing shall be
supported in accordance with Section 313.3. Equipment that is
part of the piping system shall be provided with additional support
in accordance with this code and manufacturer's installation
instructions.
PEX and PE-RT tubing in closed hydronic systems shall contain an oxygen barrier.
Exception: Closed hydronic systems without ferrous components in contact with the hydronic fluid.
Joints and connections shall be of an
approved type. Joints shall be gas and watertight and designed
for the pressure of the hydronic system. Changes in direction
shall be made by the use of fittings or with pipe bends. Pipe
bends shall have a radius of not less than six times the outside
diameter of the tubing or shall be in accordance with the manufacturer's
installation instructions. Joints between pipe and
fittings shall be installed in accordance with the manufacturer's
installation instructions.
Joints between chlorinated polyvinyl chloride (CPVC) pipe or
fittings shall be installed in accordance with one of the following
methods:
- Mechanical joints shall include flanged, grooved, and push fit fittings. Removable and non-removable push fit fittings with an elastomeric o-ring that employ quick assembly push fit connectors shall be in accordance with ASSE 1061.
- Solvent cement joints for CPVC pipe and fittings shall be clean from dirt and moisture. Solvent cements in accordance with ASTM F493, requiring the use of a primer shall be orange in color. The primer shall be colored and be in accordance with ASTM F656. Listed solvent cement in accordance with ASTM F493 that does not require the use of primers, yellow or red in color, shall be permitted for pipe and fittings manufactured in accordance with ASTM D2846, 1/2 of an inch (15 mm) through 2 inches (50 mm) in diameter or ASTM F442, 1/2 of an inch (15 mm) through 3 inches (80 mm) in diameter. Apply primer where required inside the fitting and to the depth of the fitting on pipe. Apply liberal coat of cement to the outside surface of pipe to depth of fitting and inside of fitting. Place pipe inside fitting to forcefully bottom the pipe in the socket and hold together until joint is set.
- Threaded joints for CPVC pipe shall be made with pipe threads in accordance with ASME B1.20.1. A minimum of Schedule 80 shall be permitted to be threaded, and the pressure rating shall be reduced by 50 percent. The use of molded fittings shall not result in a 50 percent reduction in the pressure rating of the pipe provided that the molded fittings shall be fabricated so that the wall thickness of the material is maintained at the threads. Thread sealant compound that is compatible with the pipe and fitting, insoluble in water, and nontoxic shall be applied to male threads. Caution shall be used during assembly to prevent over tightening of the CPVC components once the thread sealant has been applied. Female CPVC threaded fittings shall be used with plastic male threads only.
Joints
between chlorinated polyvinyl chloride/aluminum/chlorinated
polyvinyl chloride (CPVC/AL/CPVC) pipe or fittings shall be
installed in accordance with one of the following methods:
- Mechanical joints shall include flanged and grooved.
- Solvent cement joints for CPVC/AL/CPVC pipe and fittings shall be clean from dirt and moisture. Solvent cements in accordance with ASTM F493, requiring the use of a primer shall be orange in color. The primer shall be colored and be in accordance with ASTM F656. Listed solvent cement in accordance with ASTM F493 that does not require the use of primers, yellow in color, shall be permitted for pipe and fittings manufactured in accordance with ASTM D2846, 1/2 of an inch (15 mm) through 2 inches (50 mm) in diameter,1/2 of an inch (15 mm) through 3 inches (80 mm) in diameter. Apply primer where required inside the fitting and to the depth of the fitting on pipe. Apply liberal coat of cement to the outside surface of pipe to depth of fitting and inside of fitting. Place pipe inside fitting to forcefully bottom the pipe in the socket and hold together until joint is set.
Joints between copper pipe, tubing, or fittings shall be
installed in accordance with one of the following methods:
- Brazed joints between copper or copper alloy pipe, tubing, or fittings shall be made with brazing alloys having a liquid temperature above 1000°F (538°C). The joint surfaces to be brazed shall be cleaned bright by either manual or mechanical means. Tubing shall be cut square and reamed to full inside diameter. Brazing flux shall be applied to the joint surfaces where required by manufacturer's recommendation. Brazing filler metal in accordance with AWS A5.8 shall be applied at the point where the pipe or tubing enters the socket of the fitting.
- Flared joints for soft copper or copper alloy tubing shall be made with fittings that are in accordance with the applicable standards referenced in Table 1210.1. Pipe or tubing shall be cut square using an appropriate tubing cutter. The tubing shall be reamed to full inside diameter, resized to round, and expanded with a proper flaring tool.
- Mechanically formed tee fittings shall have extracted collars that shall be formed in a continuous operation consisting of drilling a pilot hole and drawing out the pipe or tube surface to form a collar having a height not less than three times the thickness of the branch tube wall. The branch pipe or tube shall be notched to conform to the inner curve of the run pipe or tube and shall have two dimple depth stops to ensure that penetration of the branch pipe or tube into the collar is of a depth for brazing and that the branch pipe or tube does not obstruct the flow in the main line pipe or tube. Dimple depth stops shall be in line with the run of the pipe or tube. The second dimple shall be 1/4 of an inch (6.4 mm) above the first and shall serve as a visual point of inspection. Fittings and joints shall be made by brazing. Soldered joints shall not be permitted.
- Pressed fittings for copper or copper alloy pipe or tubing shall have an elastomeric o-ring that forms the joint. The pipe or tubing shall be fully inserted into the fitting, and the pipe or tubing marked at the shoulder of the fitting. Pipe or tubing shall be cut square, chamfered, and reamed to full inside diameter. The fitting alignment shall be checked against the mark on the pipe or tubing to ensure the pipe or tubing is inserted into the fitting. The joint shall be pressed using the tool recommended by the manufacturer.
- Removable and nonremovable push fit fittings for copper or copper alloy tubing or pipe that employ quick assembly push fit connectors shall be in accordance with ASSE 1061. Push fit fittings for copper pipe or tubing shall have an approved elastomeric o-ring that forms the joint. Pipe or tubing shall be cut square, chamfered, and reamed to full inside diameter. The tubing shall be fully inserted into the fitting, and the tubing marked at the shoulder of the fitting. The fitting alignment shall be checked against the mark on the tubing to ensure the tubing is inserted into the fitting and gripping mechanism has engaged on the pipe.
- Soldered joints between copper or copper alloy pipe, tubing, or fittings shall be made in accordance with ASTM B828. Pipe or tubing shall be cut square and reamed to the full inside diameter including the removal of burrs on the outside of the pipe or tubing. Surfaces to be joined shall be cleaned bright by manual or mechanical means. Flux shall be applied to pipe or tubing and fittings and shall be in accordance with ASTM B813, and shall become noncorrosive and nontoxic after soldering. Insert pipe or tubing into the base of the fitting and remove excess flux. Pipe or tubing and fitting shall be supported to ensure a uniform capillary space around the joint. Solder in accordance with ASTM B32 shall be applied to the joint surfaces until capillary action draws the molten solder into the cup. Joint surfaces shall not be disturbed until cool, and any remaining flux residue shall be cleaned.
- Threaded joints for copper or copper alloy pipe shall be made with pipe threads in accordance with ASME B1.20.1. Thread sealant tape or compound shall be applied only on male threads, and such material shall be of approved types, insoluble in water, and nontoxic.
Joints between cross-linked polyethylene (PEX) pipe or fittings
shall be installed with fittings for PEX tubing that comply
with the applicable standards referenced in Table 1210.1.
PEX tubing labeled in accordance with ASTM F876 shall be
marked with the applicable standard designation for the fittings
specified for use with the tubing. Mechanical joints shall
be installed in accordance with the manufacturer's installation
instructions.
Joints
between cross-linked polyethylene/aluminum/cross-linked
polyethylene (PEX-AL-PEX) pipe or fittings shall be
installed in accordance with one of the following methods:
- Mechanical joints between PEX-AL-PEX pipe or fittings shall include mechanical and compression type fittings and insert fittings with a crimping ring. Insert fittings utilizing a crimping ring shall be in accordance with ASTM F1974 or ASTM F2434. Crimp joints for crimp insert fittings shall be joined to PEX-AL-PEX pipe by the compression of a crimp ring around the outer circumference of the pipe, forcing the pipe material into annular spaces formed by ribs on the fitting.
- Compression joints shall include compression insert fittings
and shall be joined to PEX-AL-PEX pipe through the
compression of a split ring or compression nut around the
outer circumference of the pipe, forcing the pipe material
into the annular space formed by the ribs on the fitting.
Note: [HCD 1 & HCD 2] PEX-AL-PEX is not adopted in the California Plumbing Code for use in potable water supply and distribution systems.
Joints between ductile iron pipe
or fittings shall be installed in accordance with one of the following
methods:
- Mechanical joints for ductile iron pipe or fittings shall consist of a bell that is cast integrally with the pipe or fitting and provided with an exterior flange having bolt holes and a socket with annular recesses for the sealing gasket and the plain end of the pipe or fitting. The elastomeric gasket shall comply with AWWA C111. Lubricant recommended for the application by the pipe manufacturer shall be applied to the gasket and plain end of the pipe.
- Push-on joints for ductile iron pipe or fittings shall consist of a single elastomeric gasket that shall be assembled by positioning the elastomeric gasket in an annular recess in the pipe or fitting socket and forcing the plain end of the pipe or fitting into the socket. The plain end shall compress the elastomeric gasket to form a positive seal and shall be designed so that the elastomeric gasket shall be locked in place against displacement. The elastomeric gasket shall comply with AWWA C111. Lubricant recommended for the application by the pipe manufacturer shall be applied to the gasket and plain end of the pipe.
Joints
between polyethylene (PE) plastic pipe, tubing, or fittings
shall be installed in accordance with one of the following:
- Butt-fusion joints shall be installed in accordance with ASTM F2620 and shall be made by heating the squared ends of two pipes, pipe and fitting, or two fittings by holding ends against a heated element. The heated element shall be removed where the proper melt is obtained, and joined ends shall be placed together with applied force.
- Electro-fusion joints shall be heated internally by a conductor at the interface of the joint. Align and restrain fitting to pipe to prevent movement and apply electric current to the fitting. Turn off the current when the proper time has elapse to heat the joint. The joint shall fuse together and remain undisturbed until cool.
- Socket-fusion joints shall be installed in accordance ASTM F2620 and shall be made by simultaneously heating the outside surface of a pipe end and the inside of a fitting socket. Where the proper melt is obtained, the pipe and fitting shall be joined by inserting one into the other with applied force. The joint shall fuse together and remain undisturbed until cool.
- Mechanical joints between PE pipe, tubing, or fittings shall include insert and mechanical compression fittings that provide a pressure seal resistance to pullout. Joints for insert fittings shall be made by cutting the pipe square, using a cutter designed for plastic piping, and removal of sharp edges. Two stainless steel clamps shall be placed over the end of the pipe. Fittings shall be checked for proper size based on the diameter of the pipe. The end of pipe shall be placed over the barbed insert fitting, making contact with the fitting shoulder. Clamps shall be positioned equal to 180 degrees (3.14 rad) apart and shall be tightened to provide a leak tight joint. Compression type couplings and fittings shall be permitted for use in joining PE piping and tubing. Stiffeners that extend beyond the clamp or nut shall be prohibited. Bends shall be not less than 30 pipe diameters or the coil radius where bending with the coil. Bends shall not be permitted closer than 10 pipe diameters of a fitting or valve. Mechanical joints shall be designed for their intended use.
Joints between polyethylene/aluminum/polyethylene
(PE-AL-PE) pipe or fittings shall be installed in accordance
with one of the following methods:
- Mechanical joints for PE-AL-PE pipe, tubing, or fittings shall be either of the metal insert fittings with a split ring and compression nut or metal insert fittings with copper crimp rings. Metal insert fittings shall comply with ASTM F1974. Crimp insert fittings shall be joined to the pipe by placing the copper crimp ring around the outer circumference of the pipe, forcing the pipe material into the space formed by the ribs on the fitting until the pipe contacts the shoulder of the fitting. The crimp ring shall then be positioned on the pipe so the edge of the crimp ring is 1/8 of an inch (3.2 mm) to 1/4 of an inch (6.4 mm) from the end of the pipe. The jaws of the crimping tool shall be centered over the crimp ring and tool perpendicular to the barb. The jaws shall be closed around the crimp ring and shall not be crimped more than once.
- Compression joints for PE-AL-PE pipe, tubing, or fittings shall be joined through the compression of a split ring, by a compression nut around the circumference of the pipe. The compression nut and split ring shall be placed around the pipe. The ribbed end of the fitting shall be inserted onto the pipe until the pipe contacts the shoulder of the fitting. Position and compress the split ring by tightening the compression nut onto the insert fitting.
Joints between polyethylene of raised temperature (PE-RT)
tubing or fittings shall be installed with fittings for PE-RT tubing that comply with the applicable standards referenced in
Table 1210.1. Metal insert fittings, metal compression fittings,
and plastic fittings shall be manufactured to and marked
in accordance with the standards for fittings in Table 1210.1.
Joints between
polypropylene pipe or fittings shall be installed in accordance
with one of the following methods:
- Heat-fusion joints for polypropylene (PP) pipe shall be installed with socket-type heat-fused polypropylene fittings, butt-fusion polypropylene fittings or pipe, or electro-fusion polypropylene fittings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F2389 or CSA B137.11.
- Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's installation instructions. Polypropylene pipe shall not be threaded. Polypropylene transition fittings for connection to other piping materials shall only be threaded by the use of copper alloy or stainless steel inserts molded in the fitting.
Joints between
polyvinyl chloride pipe or fittings shall be installed in accordance
with one of the following methods:
- Mechanical joints shall be designed to provide a permanent seal and shall be of the mechanical or push-on joint. The mechanical joint shall include a pipe spigot that has a wall thickness to withstand without deformation or collapse; the compressive force exerted where the fitting is tightened. The push-on joint shall have a minimum wall thickness of the bell at any point between the ring and the pipe barrel. The elastomeric gasket shall comply with ASTM D3139, and be of such size and shape as to provide a compressive force against the spigot and socket after assembly to provide a positive seal.
- Solvent cement joints for PVC pipe or fittings shall be clean from dirt and moisture. Pipe shall be cut square and pipe shall be deburred. Where surfaces to be joined are cleaned and free of dirt, moisture, oil, and other foreign material, apply primer purple in color in accordance with ASTM F656. Primer shall be applied until the surface of the pipe and fitting is softened. Solvent cements in accordance with ASTM D2564 shall be applied to all joint surfaces. Joints shall be made while both the inside socket surface and outside surface of pipe are wet with solvent cement. Hold joint in place and undisturbed for 1 minute after assembly.
- Threads shall comply with ASME B1.20.1. A minimum of Schedule 80 shall be permitted to be threaded; however, the pressure rating shall be reduced by 50 percent. The use of molded fittings shall not result in a 50 percent reduction in the pressure rating of the pipe provided that the molded fittings shall be fabricated so that the wall thickness of the material is maintained at the threads. Thread sealant compound that is compatible with the pipe and fitting, insoluble in water, and nontoxic shall be applied to male threads. Caution shall be used during assembly to prevent over tightening of the PVC components once the thread sealant has been applied. Female PVC threaded fittings shall be used with plastic male threads only.
Joints between steel pipe, tubing, or fittings shall be installed in accordance with one of
the following methods:
- Mechanical joints shall be made with an approved and listed elastomeric gasket.
- Threaded joints shall be made with pipe threads that are in accordance with ASME B1.20.1. Thread sealant tape or compound shall be applied only on male threads, and such material shall be of approved types, insoluble in water, and nontoxic.
- Welded joints shall be made by electrical arc or oxygen/acetylene method. Joint surfaces shall be cleaned by an approved procedure. Joints shall be welded by an approved filler metal.
- Pressed joints shall have an elastomeric o-ring that forms the connection. The pipe or tubing shall be fully inserted into the fitting, and the pipe or tubing marked at the shoulder of the fittings. Pipe or tubing shall be cut square, chamfered, and reamed to full inside diameter. The fitting alignment shall be checked against the mark on the pipe or tubing to ensure the pipe or tubing is fully inserted into the fitting. The joint shall be pressed using the tool recommended by the manufacturer.
Joints between various materials shall be installed in accordance
with the manufacturer's installation instructions and shall
comply with Section 1211.14.1 and Section 1211.14.2.
Joints from copper or copper alloy pipe or tubing to threaded pipe shall be made by the use of copper alloy adapter, copper alloy nipple [minimum 6 inches (152 mm)], dielectric fitting, or dielectric union in accordance with ASSE 1079. The joint between the copper or copper alloy pipe or tubing and the fitting shall be a soldered, brazed, flared, or pressed joint and the connection between the threaded pipe and the fitting shall be made with a standard pipe size threaded joint.
Valves shall be rated for the operating temperature
and pressure of the system. Valves shall be compatible
with the type of heat transfer medium and piping
material.
Valves shall be installed in
hydronic piping systems in accordance with Section 1212.3
through Section 1212.11.
Isolation valves shall be installed
on the supply and return side of the heat exchanger.
Isolation valves shall be
installed on connections to pressure vessels.
Isolation valves shall
be installed on both sides of a pressure reducing valve.
Serviceable equipment, components, and appliances within
the system shall have isolation valves installed upstream and
downstream of such devices.
Isolation valves shall be installed
at connections to non-diaphragm-type expansion tanks.
Where flow balancing
valves are installed, such valves shall be capable of increasing
or decreasing the amount of flow by means of adjustment.
Where
mixing or temperature control valves are installed, such
valves shall be capable of obtaining the design water temperature
and design flow requirements.
Isolation
valves shall be installed where air removal devices or automatic
air vents are utilized to permit cleaning, inspection, or
repair without shutting the system down.
A heat source or
system of commonly connected heat sources shall be protected
by a water-temperature-activated operating control to
stop heat output of the heat source where the system water
reaches a pre-set operating temperature.
A steam heat source
or system of commonly connected steam heat sources shall be
protected by a pressure-actuated control to shut off the fuel
supply where the system pressure reaches a pre-set operating
pressure.
A primary water-level
control shall be installed on a steam heat source to
control the water level in the heat source. The control
shall be installed in accordance with the manufacturer's
installation instructions.
A temperature-sensing device
shall be installed in the occupied space to regulate the operation of the hydronic system.
Direct-fired heat sources
within a closed heating system shall have a low-water fuel
cut-off device, except as specified in Section 1214.3. Where
a low-water control is integral with the heat source as part of
the appliance's integrated control and is listed for such use, a
separate low-water control shall not be required. An external
cut-off device shall be installed in accordance with the heat-source
manufacturer's installation instructions. No valve shall be located between the external low-water fuel cut-off and
the heat-source unit. Where a pumped condensate return is
installed, a second low-water cut-off shall be provided.
Where an automatic
makeup fluid supply fill device is used to maintain the water
content of the heat-source unit, or any closed loop in the system,
the makeup supply shall be located at the expansion tank
connection or other approved location.
A pressure-reducing valve shall be installed on a makeup water feed line. The pressure of the feed line shall be set in accordance with the design of the system, and connections to potable water shall be in accordance with Section 1202.0 to prevent contamination due to backflow.
A pressure-reducing valve shall be installed on a makeup water feed line. The pressure of the feed line shall be set in accordance with the design of the system, and connections to potable water shall be in accordance with Section 1202.0 to prevent contamination due to backflow.
Provisions
shall be made to control zone flows in a multi-zone hydronic
system where the closing of some or all of the two-way zone
valves causes excess flow through the open zones or dead-heading
of a fixed-speed pump.
Where a differential pressure bypass valve is used for the
purpose specified in Section 1214.5, it shall be installed
and adjusted to provide bypass of the distribution system
when most or all of the zones are closed.
Provision shall be made for
the removal of air in the heat-distribution piping system. The
air-removal device shall be located in the area of the hydronic
piping system where air is likely to accumulate. Air-removal
devices shall be installed to facilitate their removal for examination,
repair, or replacement.
Exception: Drainback type solar thermal systems shall not
require an air-removal device.
To assist with the removal
of entrained air, an air-separation device shall be installed in
hydronic systems. The device shall be located in accordance
with the manufacturer's installation instructions or at the point
of no mechanically-induced pressure change within the distribution system.
Secondary loops that are isolated
from the primary heat-distribution loop by a heat
exchanger are closed-loop hydronic systems and shall have an
expansion tank in accordance with Section 1209.0, an air-removal
device in accordance with Section 1214.6, and an
air-separation device in accordance with Section 1214.7.
Based on the system design, the heat-distribution
units shall be selected in accordance with the manufacturer's specifications.
Heat-distribution units shall be
installed in accordance with the manufacturer's installation
instructions and this code.
Hydronic systems and components
shall be designed, installed, and protected from freezing.
System loops shall be installed so that
the design flow rates are achieved within the system.
The ignitable flash point of
heat transfer fluid in a hydronic piping system shall be a minimum
of 50°F (28°C) above the maximum system operating
temperature. The heat transfer fluid shall be compatible with
the makeup fluid supplied to the system.
Two-pipe steam
system piping and heat-distribution units shall be sloped down at not less than 1/8 inch per foot (10.4 mm/m) in the
direction of the steam flow.
System piping shall be installed to allow condensate to flow to the condensate receiver or
steam boiler either by gravity or pump-assisted.
Where multi-row elements
are installed in an enclosure, they shall be top fed and
piped in parallel down to the steam trap. A single steam trap
for each row of heating elements shall be installed. Where the
size of the return header is increased by a minimum of one
pipe size, a single steam trap shall be permitted to be installed
for multiple rows. Where multiple steam unit heaters are
installed, an individual steam trap for each unit shall be
installed.
Radiant heating and cooling systems
shall be installed in accordance with the system design.
Manifolds shall be equipped with isolation valves on the supply and return lines. Manifolds
shall be capable of withstanding the pressure and temperature
of the system. The material of the manifold shall
be compatible with the system fluid and shall be installed
in accordance with the manufacturer's installation
instructions.
Floor finished surface
temperatures shall not exceed the following temperatures for space heating applications:
- 85°F (29°C) in general occupied applications.
- 90°F (32°C) in bathrooms, foyers, distribution areas such as hallways and indoor swimming pools.
- 88°F (31°C) in industrial spaces
- 95°F (35°C) in radiant panel perimeter areas, i.e., up to 2.5 feet (762 mm) from outside walls.
Radiant cooling systems
shall be designed to minimize the potential for condensation.
To prevent condensation on any cooled radiant
surface, the supply water temperature for a radiant cooling
system shall be not less than 3°F (2°C) above the anticipated
space dewpoint temperature, or in accordance with the manufacturer's recommendation. Chilled water piping, valves,
and fittings shall be insulated and vapor sealed to prevent surface
condensation.
Hydronic radiant system tubing shall be installed in accordance with the manufacturer 's installation instructions and with the tube layout and spacing in accordance with the system design. Except for distribution mains, tube spacing and the individual loop lengths shall be installed with a variance of not more than ±10 percent from the design. The maximum loop length of continuous tubing from a supply-and-return manifold shall not exceed the lengths specified by the manufacturer or, in the absence of manufacturer's specifications, the lengths specified in Table 1217.4. Actual loop lengths shall be determined by spacing, flow rate, and pressure drop requirements as specified in the system design.
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
For the purpose of system balancing, each individual loop shall have a tag securely affixed to the manifold to indicate the length of the loop and the room(s) and area(s) served.
NOMINAL TUBE SIZE (inches) |
MAXIMUM LOOP LENGTH (feet) |
1/4 | 125 |
5/16 | 200 |
3/8 | 250 |
1/2 | 300 |
5/8 | 400 |
3/4 | 500 |
1 | 750 |
Where tubing is embedded in a
structural concrete slab such tubes shall not be larger in outside
dimension than one-third of the overall thickness of the
slab and shall be spaced not less than three diameters on center
except within 10 feet (3048 mm) of the distribution manifold. The top of the tubing shall be embedded in the slab not
less than 2 inches (51 mm) below the surface.
Where embedded in or installed under a concrete
slab, tubing shall be protected from damage at penetrations of the slab with protective sleeving approved by the
tubing manufacturer. The space between the tubing and
sleeve shall be sealed with an approved sealant compatible
with the tubing. The tubing at the location of an
expansion joint in a concrete slab shall be encased in protective
pipe sleeving that covers the tubing not less than
12 inches (305 mm) on either side of the expansion joint
or the tubing shall be installed below the slab.
Where a poured concrete radiant
floor system is installed in contact with the soil, insulation
approved for such an application with a minimum
R-value of 5 shall be placed between the soil and the concrete;
extend to the outside edges of the concrete; and be
placed on all slab edges.
[HCD 1 & HCD 2] See California Energy Code Section 110.8(g) for insulation requirements for heated slab floors.
[HCD 1 & HCD 2] See California Energy Code Section 110.8(g) for insulation requirements for heated slab floors.
Where tubing
is installed below a subfloor, the tube spacing shall be
in accordance with the system design and joist space limitations.
Where tubing is installed above or in the subfloor, the tube spacing shall not exceed 12 inches (305 mm) center-to-center for living areas.
Where tubing is installed in the joist cavity, the cavity shall be insulated with not less than R-12 material below the heated space.
An air space of not less than 1 inch (25.4 mm) and not more than 3 inches (76 mm) shall be maintained between the top of the insulation and the underside of the floor unless a conductive plate is installed in accordance with manufacturer's instructions.
Where tubing is installed in panels above or in the subfloor and not embedded in concrete, the floor assembly shall be insulated with not less than R-5 material below the tubing when installed over habitable space.
Where tubing is installed above or in the subfloor, the tube spacing shall not exceed 12 inches (305 mm) center-to-center for living areas.
Where tubing is installed in the joist cavity, the cavity shall be insulated with not less than R-12 material below the heated space.
An air space of not less than 1 inch (25.4 mm) and not more than 3 inches (76 mm) shall be maintained between the top of the insulation and the underside of the floor unless a conductive plate is installed in accordance with manufacturer's instructions.
Where tubing is installed in panels above or in the subfloor and not embedded in concrete, the floor assembly shall be insulated with not less than R-5 material below the tubing when installed over habitable space.
Where piping is
installed in the stud wall cavity or the ceiling joist cavity,
the cavity shall be insulated with not less than R-12 material.
The insulation shall be installed in such a manner as
to prevent heating or cooling loss from the space
intended to be controlled.
An air space of not less than 1 inch (25.4 mm) and not more than 3 inches (76 mm) shall be maintained between the insulation and the interior surface of the panel unless a conductive plate is installed.
[HCD 1 & HCD 2] See California Energy Code Sections 150.0(j)2 and 120.3(c) for pipe insulation requirements based on pipe diameter.
An air space of not less than 1 inch (25.4 mm) and not more than 3 inches (76 mm) shall be maintained between the insulation and the interior surface of the panel unless a conductive plate is installed.
[HCD 1 & HCD 2] See California Energy Code Sections 150.0(j)2 and 120.3(c) for pipe insulation requirements based on pipe diameter.
Clearances
for electric heating panels or between outlets, junction
boxes, mounting luminaries, ventilating, or other openings
shall comply with the California Electrical Code.
Radiant panels attached to wood, steel, masonry, or concrete
framing members shall be fastened by means of anchors,
bolts, or approved screws of sufficient size and anchorage to support the loads applied. Panels shall be installed
with corrosion-resistant fasteners. Piping systems shall
be designed for thermal expansion to prevent the load
being transmitted to the panel.
Systems utilizing heat exchangers shall
protect the potable water system from being contaminated by
the heat transfer medium. Systems that incorporate a single-wall
heat exchanger to separate potable water from the heat-transfer
fluid shall meet the following requirements:
- Heat transfer medium is either potable water or contains fluids recognized as safe by the Food and Drug Administration (FDA) as food grade.
- A tag or label shall be securely affixed to the heat source
with the word, "CAUTION" and the following statements:
- The heat transfer medium shall be water or other nontoxic fluid recognized as safe by the FDA.
- The maximum operating pressure of the heat exchanger shall not exceed the maximum operating pressure of the potable water supply.
- The word "CAUTION" and the statements listed above shall have an uppercase height of not less than 0.120 of an inch (3.048 mm). The vertical spacing between lines of type shall be not less than 0.046 of an inch (1.168 mm). Lowercase letters shall be not less than compatible with the uppercase letter size specification.
Domestic hot-water heat exchangers,
whether internal or external to the heating appliance, shall be
permitted to be used to heat water in domestic hot-water storage
tanks. Tanks used to store hot water shall be listed for the
intended use and constructed in accordance with nationally
recognized standards. A pressure- and temperature-relief
valve with a set pressure not exceeding 150 percent of the
maximum operating pressure of the system, and at a temperature
of 210°F (99°C), shall be installed on the storage tank.
Where the normal operating temperature of the boiler or dual-purpose water heater that provides heat input for domestic hot water exceeds 140°F (60°C), a thermostatically controlled mixing valve as specified in Section 1207.3.1 shall be installed to limit the water supplied to the potable hot water system to a temperature of 140°F (60°C) or less. The potability of the water shall be maintained throughout the system.
Where the normal operating temperature of the boiler or dual-purpose water heater that provides heat input for domestic hot water exceeds 140°F (60°C), a thermostatically controlled mixing valve as specified in Section 1207.3.1 shall be installed to limit the water supplied to the potable hot water system to a temperature of 140°F (60°C) or less. The potability of the water shall be maintained throughout the system.
Where auxiliary systems contain chemical additives, corrosive
fluids, or both not intended or designed for use in the
primary system, a double wall heat exchanger shall be used in
accordance with Section 1218.1. The chemical additives in
the auxiliary systems shall be compatible with auxiliary system
components and accepted for use by the heat exchanger
manufacturer.
An automatic thermostatically
operating control device that controls the supply
hydronic solution temperature to the snow and ice melt area
shall be installed in the system. Snow and ice melt systems
shall be protected from freezing with a mixture of propylene
glycol or ethylene glycol, and water or other approved fluid.
Automotive antifreeze shall not be used.
Snow and ice melt tubing shall be installed in accordance with the manufacturer's installation instructions and with the tube layout and spacing in accordance with the system design. Except for distribution mains, tube and the individual loop lengths shall be installed with a variance of not more than ±10 percent from the design.
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
Notes:
The maximum loop length of continuous tubing from a supply-and-return manifold arrangement shall not exceed the lengths specified by the manufacturer or, in the absence of manufacturer's specifications, the lengths specified in Table 1220.2.1. Actual loop lengths shall be determined by spacing, flow rate, and pressure drop in accordance with the system design.
NOMINAL TUBE SIZE (inches) |
MAXIMUM ACTIVE LOOP LENGTH (feet) |
TOTAL LOOP LENGTH (feet) |
PE-RT and PEX Tubing | ||
1/2 | 115 | 140 |
5/8 | 225 | 250 |
3/4 | 300 | 325 |
1 | 450 | 475 |
Copper Tubing3 | ||
1/2 | — | 140 |
3/4 | — | 280 |
Notes:
-
1 The total PE-RT and PEX loop lengths consist of two separate sections, the active loop, and the leader length. The active loop is installed within the heated slab. The leader length is the total distance to and from the manifold and heated slab, including any vertical distances.
-
2 The manifolds shall be installed as close to the snow melt area as possible.
Where tubes are embedded in a concrete
slab, such tubes shall not be larger in outside dimension
than one-third of the overall thickness of the slab and shall be spaced not less than three diameters on center.
The top of the tubing shall be embedded in the slab not
less than 2 inches (51 mm) below the surface.
Where embedded in or installed under a concrete
slab, tubing shall be protected from damage at
penetrations of the slab with protective sleeving
approved by the tubing manufacturer. The space between
the tubing and sleeve shall be sealed with an approved
sealant compatible with the tubing. The tubing at the
location of an expansion joint in a concrete slab shall be
encased in a protective pipe sleeve that covers the tubing
not less than 12 inches (305 mm) on either side of the
joint or the tubing shall be installed below the slab.
A solid foundation shall be prepared before the tubing is installed. Compaction
shall be used for slabs, sidewalks, and driveways.
Where a poured concrete snow melt system is installed in contact with the soil, insulation
that has a R-5 value shall be placed between the concrete
and the compacted grade; extend as close as practical to
the outside edges of the concrete; and be placed on vertical
slab edges that are in contact with plants or landscaping.
[HCD 1 & HCD 2] See California Energy Code Section 110.8(g) for insulation requirements for heated slab floors.
[HCD 1 & HCD 2] See California Energy Code Section 110.8(g) for insulation requirements for heated slab floors.
Testing and flushing of auxiliary systems shall be in accordance with Section
1205.0.
Hydronic makeup air units that are affected by freezing shall be protected
against freezing by a hydronic solution.
Piping, fittings, and connections shall be
installed in accordance with the conditions of their approval
and manufacturer's installation instructions.
Piping embedded in concrete shall be steel pipe, Type L copper
tubing or plastic pipe or tubing rated at not less than 100 psi
at 180°F (689 kPa at 82°C). Joints of pipe or tubing that are
embedded in a portion of the building, such as concrete or
plaster shall be installed in accordance with the requirements
of Section 1221.2.1 through Section 1221.2.3.
Steel pipe shall be welded by
electrical arc or oxygen/acetylene method.
Copper tubing shall be
joined by brazing with filler metals having a melting
point not less than 1000°F (538°C).
Plastic pipe and tubing shall be
installed in continuous lengths or shall be joined by heat
fusion method.
Piping to be embedded in concrete
shall be pressure-tested in accordance with Section
1205.2 prior to pouring concrete. During the pour, the pipe
system shall maintain the test pressure of not less than one
and one-half times the hydronic system operating pressure
and not less than 100 psi (689 kPa). During freezing or the
possibility of freezing conditions, testing shall be done with
air where permitted by the manufacturer.
Condensate drains from
dehumidifying coils shall be constructed and sloped for condensate
removal. Such drains shall be installed in accordance
with Section 310.0.
Hydronic piping
where the exterior temperature exceeds 250°F (121°C) shall
have a clearance of not less 1 inch (25.4 mm) to combustible
materials.