Adopting Agency | BSC | BSC-CG | SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||
1 | 2 | 1-AC | AC | SS | SS/CC | 1 | 2 | 3 | 4 | ||||||||||||
Adopt Entire Chapter | X | X | X | X | X | X | X | X | X | X | X | ||||||||||
Adopt Entire Chapter as amended (amended sections listed below) | |||||||||||||||||||||
Adopt only those sections that are listed below | |||||||||||||||||||||
Chapter/Section |
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
The requirements of this chapter shall
apply to the construction, installation, operation, repair, and alteration of boilers and pressure vessels. Low-pressure
boilers shall comply with this chapter and Section 904.0.
Exceptions:
Exceptions:
- Listed and approved potable water heaters with a nominal capacity not exceeding 120 gallons (454 L) and having a heat input not exceeding 200 000 British thermal units per hour (Btu/h) (58.6 kW) used for hot water supply at a pressure not exceeding 160 pounds-force per square inch (psi) (1103 kPa) and at temperatures not exceeding 210°F (99°C), in accordance with the plumbing code.
- Pressure vessels used for unheated water supply, including those containing air that serves as a cushion and is compressed by the introduction of water and tanks connected to sprinkler systems.
- Portable unfired pressure vessels and Interstate Commerce Commission (I.C.C.) containers.
- Containers for liquefied petroleum gases, bulk oxygen, and medical gas that are regulated by the fire code.
- Unfired pressure vessels in business, factory, hazardous, mercantile, residential, storage, and utility occupancies having a volume not exceeding 5 cubic feet (0.14 m3) and operating at pressures not exceeding 250 psi (1724 kPa).
- Pressure vessels used in refrigeration systems shall comply with Chapter 11.
- Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables, and other similar humidity control systems.
- A boiler or pressure vessel subject to regular inspection by federal inspectors or licensed by federal authorities.
Boiler rooms and enclosures shall comply with the building code.
Air for combustion and ventilation shall be provided in accordance with Chapter 7.
For heating or hot-water-supply boiler
applications, the boiler room shall be equipped with a floor
drain or other approved means for disposing of the accumulation
of liquid wastes incident to cleaning, recharging, and
routine maintenance. No steam pipe shall be directly
connected to a part of a plumbing or drainage system, nor
shall a water having a temperature above 140°F (60°C) be
discharged under pressure directly into a part of a drainage
system. Pipes from boilers shall discharge by means of indirect
waste piping, as determined by the Authority Having
Jurisdiction or the boiler manufacturer's instructions.
Equipment shall be set or mounted on a level base capable of supporting and distributing the weight
contained thereon. Boilers, tanks, and equipment shall be
securely anchored to the structure. Equipment requiring
vibration isolation shall be installed as designed by a registered
design professional and approved by the Authority Having Jurisdiction.
Pressure vessels shall be constructed and
designed in accordance with the ASME Boiler & Pressure
Vessel Code (BPVC) Section VIII. Boilers shall be
constructed, designed, and installed in accordance with one of
the following:
- ASME BPVC Section I
- ASME BPVC Section IV
- NFPA 85
Oil-burning boilers shall
comply with Section 1002.2. 1 and Section 1002.2.2.
The construction of boilers and pressure vessels and the installation thereof shall be in accordance
with minimum requirements for safety from structural
and mechanical failure and excessive pressures, as established
by the Authority Having Jurisdiction in accordance with
nationally recognized standards.
Required electrical, mechanical, safety, and operating controls shall carry approval of an approved testing
agency or be accepted by the Authority Having Jurisdiction.
Electrical controls shall be of such design and construction
as to be suitable for installation in the environment in which
they are located.
Automatic boilers shall be
equipped with controls and limit devices in accordance with ASME CSD-1 or Table 1003.2.1.
The Authority Having Jurisdiction shall have the authority to approve solid-fuel-fired boilers that comply with the safety requirements for automatic gas fired boilers or oil fired boilers.
For SI Units: 1000 British thermal units per hour = 0.293 kW
The Authority Having Jurisdiction shall have the authority to approve solid-fuel-fired boilers that comply with the safety requirements for automatic gas fired boilers or oil fired boilers.
BOILER GROUP |
FUEL | FUEL INPUT RANGE1 (INCLUSIVE), BTU/H |
TYPE OF PILOT2 |
SAFETY CONTROL TIMING (NOMINAL MAXIMUM TIME IN SECONDS) |
ASSURED FUEL SUPPLY CONTROL4 |
ASSURED AIR SUPPLY CONTROL5 |
LOW FIRE START UP CONTROL6 |
PRE- PURGING CONTROL7 |
HOT WATER TEMPERATURE AND LOW WATER LIMIT CONTROLS8 |
STEAM PRESSURE AND LOW WATER LIMIT CONTROLS9 |
APPROVED FUEL SHUTOFF10 |
CONTROL AND LIMIT DEVICE SYSTEM DESIGN11 |
|||
TRAIL FOR PILOT |
TRIAL FOR MAIN BURNER FRAME |
MAIN BURNER FLAME FAILURE3 |
|||||||||||||
DIRECT ELECTRIC IGNITION |
FLAME PILOT |
||||||||||||||
A | Gas | 0-400000 | Any type | 90 | Not Required |
90 | 90 | Not Required |
Required | Not Required |
Not Required |
Required | Required | Not Required |
Required |
B | Gas | 400001 - 2500000 |
Interrupted or Intermittent |
15 | 15 | 15 | 2-4 | Not Required |
Required | Not Required |
Not Required |
Required | Required | Not Required |
Required |
C | Gas | 2500001 - 5000000 |
Interrupted or Intermittent |
15 | 15 | 15 | 2-4 | Required | Required | Required | Required | Required | Required | Required | Required |
D | Gas | Over 5000000 |
Interrupted | 15 | 15 | 15 | 2-4 | Required | Required | Required | Required | Required | Required | Required | Required |
E | Oil | 0-400000 | Any type | Not Required |
90 | 90 | 90 | Not Required |
Required | Not Required |
Not Required |
Required | Required | Not Required |
Required |
F | Oil | 400001 - 1000000 |
Interrupted | Not Required |
30 | 30 | 2-4 | Required | Required | Not Required |
Not Required |
Required | Required | Not Required |
Required |
G | Oil | 1000001 - 3000000 |
Interrupted | Not Required |
15 | 15 | 2-4 | Required | Required | Not Required |
Not Required |
Required | Required | Not Required |
Required |
H | Oil | Over 3000000 |
Interrupted | 15 | 15 | 60 | 2-4 | Required | Required | Required | Required | Required | Required | Required | Required |
K | Electric | All | Not required | Not Required |
Not Required |
Not Required |
Not Required |
Not Required |
Not Required |
Not Required |
Not Required |
Required | Required | Not Required |
Required |
L | Gas, Oil and/or Coal |
12500000 or more |
Any | 10 sec Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per ASME Power Boiler Code, Section 1 and NFPA 85 |
Per ASME Power Boiler Code, Section 1 and NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
M | Heat Recovery Steam Generator |
Any | None | Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
Per ASME Boiler & Pressure Code & NFPA 85 |
Per ASME Boiler & Pressure Code & NFPA 85 |
Per NFPA 85 |
Per NFPA 85 |
1 Fuel input shall be determined by one of the following:
- The burner input shall not exceed the input shown on the burner nameplate or as otherwise identified by the manufacturer.
- The nominal boiler rating, as determined by the building official, plus 25 percent.
2 Automatic boilers shall have one name failure device on each burner, which shall prove the presence of an ignition source at the point where it will ignite
the main burner, except that boiler groups A, B, E, F, and G, which are equipped with direct electric ignition, shall monitor the main burner, and boiler groups
using interrupted pilots shall monitor the main burner after the prescribed limited trial and ignition periods. Boiler group A, equipped with continuous pilot,
shall accomplish 100 percent shutoff within 90 seconds upon pilot flame failure. The use of interrupted pilots in boiler group C is limited to approved burner
units.
3 In boiler groups B, C, and D a 90 second main burner flame failure limit shall be permitted to be applied where continuous pilots are provided on manufacturer
assembled boiler-burner units that have been approved by an approved testing agency in accordance with nationally recognized standards approved by
the building official. Boiler groups F and G equipped to re-energize their ignition systems within 0.8 second after main burner flame failure will be permitted
30 seconds for group F or 15 seconds for group G to re-establish their main burner flames.
4 Boiler groups C and D shall have controls interlocked to accomplish a non-recycling fuel shutoff upon high or low gas pressure, and boiler groups F, G, and
H using steam or air for fuel atomization shall have controls interlocked to accomplish a non-recycling fuel shutoff upon low atomizing steam or air pressure.
Boiler groups F, G, and H equipped with a preheated oil system shall have controls interlocked to provide fuel shutoff upon low oil temperature.
5 Automatic boilers shall have controls interlocked to shut off the fuel supply in the event of draft failure where forced or induced draft fans are used or, in the
event of low combustion airflow, where a gas power burner is used. Where a single motor directly driving both the fan and the oil pump is used, a separate
control is not required.
6 Boiler groups C, D, and H, where firing in excess of 400000 Btu/h (117 kW) per combustion chamber, shall be provided with low tire start of its main burner
system to permit smooth light-off. This will normally be a rate of one-third of its maximum firing rate.
7 Boiler groups C, D, and H shall not permit pilot or main burner trial for ignition operation before a purging operation of sufficient duration to permit not less
than four complete air changes through the furnace, including combustion chamber and the boiler passes. Where this is not readily determinable, five complete
air changes of the furnace, including combustion chamber up to the first pass, will be considered equivalent. An atmospheric gas burner with no mechanical
means of creating air movement or an oil burner that obtains two-thirds or more of the air required for combustion without mechanical means of creating air
movement shall not require purge by means of four air changes, so long as its secondary air openings are not provided with means of closing. Where such
burners have means of closing secondary air openings, a time delay shall be provided that puts these closures in a normally open position for four minutes
before an attempt for ignition. An installation with a trapped combustion chamber shall, in every case, be provided with a mechanical means of creating air
movement for purging.
8 An automatic hot-water-heating boiler, low-pressure hot-water-heating boiler, and power hot water boiler shall be equipped with two high-temperature limit
controls with a manual reset on the control, with the higher setting interlocked to shut off the main fuel supply, except that manual reset on the high-temperature
limit control shall not be required on an automatic package boiler not exceeding 400000 Btu/h (117 kW) input and that has been approved by an
approved testing agency. An automatic hot-water heating, power boiler, and package hot-water supply boiler shall be equipped with one low-water level
limit control with a manual reset interlocked to shut off the fuel supply, so installed as to prevent damage to the boiler and to permit testing of the control
without draining the heating system, except on boilers used in Group R Occupancies of less than six units and in Group U Occupancies and further, except
that the low-water level limit control is not required On package hot-water supply boilers approved by a nationally recognized testing agency. However, a low-water
flow limit control installed in the circulating water line shall be permitted to be used instead of the low water level limit control for the same purpose
on coil-type boilers.
9 An automatic low-pressure steam-heating boiler, small power boiler, and power steam boiler shall be equipped with two high-steam pressure limit controls
interlocked to shut off the fuel supply to the main burner with manual reset on the control, with the higher setting and two low-water-level limit controls, one
of which shall be provided with a manual reset device and independent of the feed water controller. Coil-type flash steam boilers shall be permitted to use
two high-temperature limit controls, one of which shall be manually reset in the hot water coil section of the boiler instead of the low-water level limit control.
10 Boiler groups C, D, and H shall use an approved automatic reset safety shutoff valve for the main burner fuel shutoff, which shall be interlocked to the programming control devices required. On oil burners where the safety shutoff valve will be subjected to pressures in excess of 10 psi (69 kPa) where the burner is not firing, a second safety shutoff valve shall be provided in series with the first. Boiler groups C and D using gas in excess of 1 psi (7 kPa) pressure or having a trapped combustion chamber or employing horizontal fire tubes shall be equipped with two approved safety shutoff valves, one of which shall be an automatic reset type, one of which shall be permitted to be used as an operating control, and both of which shall be interlocked to the limit-control devices required. Boiler groups C and D using gas in excess of 1 psi (7 kPa) pressure shall be provided with a permanent and ready means for making periodic
tightness checks of the main fuel safety shutoff valves.
11 Control and limit device systems shall be grounded with operating voltage not to exceed 150 volts, except that, upon approval by the building official, existing
control equipment to be reused in an altered boiler control system shall be permitted to use 220 volts single phase with one side grounded, provided such voltage
is used for all controls. Control and limit devices shall interrupt the ungrounded side of the circuit. A readily accessible means of manually disconnecting the
control circuit shall be provided with controls so arranged that where they are de-energized, the burner shall be inoperative.
A steam boilers shall be provided with a pressure
gauge and a water level glass. A water boilers shall be
provided with a pressure gauge and a temperature gauge.
Automatic boilers shall be equipped with the following
gauges:
- Oil temperature
- Oil suction pressure
- High and low gas pressure
- Stack temperature
- Windbox pressure
Stack dampers on boilers fired with
oil or solid fuel shall not close off more than 80 percent of
the stack area where closed, except on automatic boilers with
prepurge, automatic draft control, and interlock. Operative
dampers shall not be placed within a stack, flue, or vent of a
gas-fired boiler, except on an automatic boiler with prepurge,
automatic draft control, and interlock.
Welding on pressure vessels shall be done
by certified welders in accordance with nationally recognized
standards.
An expansion tank shall be installed in a hot-water-heating system as a means for controlling increased
pressure caused by thermal expansion. Expansion tanks shall
be of the closed or open type and securely fastened to the
structure. Tanks shall be rated for the pressure of the system.
Supports shall be capable of carrying twice the weight of the
tank filled with water without placing a strain on connecting
piping.
Hot-water-heating systems incorporating hot water tanks or fluid relief columns shall be installed to prevent freezing under normal operating conditions.
Hot-water-heating systems incorporating hot water tanks or fluid relief columns shall be installed to prevent freezing under normal operating conditions.
Open type expansion
tanks shall be located not less than 3 feet (914 mm) above the
highest point of the system. Such tanks shall be sized based
on the capacity of the system. An overflow with a diameter of
not less than one-half the size of the supply or not less than 1
inch (25 mm) in diameter shall be installed at the top of the
tank. The overflow shall discharge through an air gap into the
drainage system.
Closed-type systems shall
have an airtight tank or other approved air cushion that will
be consistent with the volume and capacity of the system, and
shall be designed for a hydrostatic test pressure of two and one-halftimes the allowable working pressure of the system.
Expansion tanks for systems designed to operate at more than
30 pounds-force per square inch (psi) (207 kPa) shall comply
with ASME BPVC Section VIII. Provisions shall be made for
draining the tank without emptying the system.
The minimum capacity for a gravity-type hot water system expansion
tank shall be in accordance with Table 1004.4(1). The
minimum capacity for a forced-type hot water system expansion
tank shall be in accordance with Table 1004.4(2), or
Equation 1004.4. Equation 1004.4 shall not be used for
diaphragm-type expansion tanks.
(Equation 1004.4)
Where:
For SI units: 1 gallon = 3.785 L, °C = (°F-32)/1.8, 1 foot of water = 2.99 kPa
For SI units: 1 gallon = 3.785 L, 1 square foot = 0.0929 m2
Notes:
For SI units: 1 gallons = 3.785 L
Notes:

Vt | = | Minimum volume of expansion tank, gallons |
Vs | = | Volume of system, not including expansion tank, gallons |
t | = | Average operating temperature, °F |
Pa | = | Atmospheric pressure, feet H2O absolute |
Pf | = | Fill pressure, feet H2O absolute |
Po | = | Maximum operating pressure, feet H2O absolute |
INSTALLED EQUIVALENT DIRECT RADIATION2 (square feet) |
TANK CAPACITY (gallons) |
Up to 350 | 18 |
Up to 450 | 21 |
Up to 650 | 24 |
Up to 900 | 30 |
Up to 1100 | 35 |
Up to 1400 | 40 |
Up to 1600 | 2 to 30 |
Up to 1800 | 2 to 30 |
Up to 2000 | 2 to 35 |
Up to 2400 | 2 to 40 |
Notes:
1 Based on a two-pipe system with an average operating water temperature
of 170°F (77°C), using cast-iron column radiation with a heat emission
rate of 150 British thermal units per square foot hour [Btu/(ft2•h)] (473
W/m2) equivalent direct radiation.
2 For systems that exceed 2400 square feet (222.9 m2) of installed equivalent
direct water radiation, the required capacity of the cushion tank shall
be increased on the basis of 1 gallon (4 L) tank capacity per 33 square feet
(3.1 m2) of additional equivalent direct radiation.
SYSTEM VOLUME2 (gallons) |
TANK CAPACITY DIAPHRAGM TYPE (gallons) |
TYPE CAPACITY NONDIAPHRAGM TYPE (gallons) |
100 | 9 | 15 |
200 | 17 | 30 |
300 | 25 | 45 |
400 | 33 | 60 |
500 | 42 | 75 |
1000 | 83 | 150 |
2000 | 165 | 300 |
Notes:
1 Based on an average operating water temperature of 195°F (91°C), a fill
pressure of 12 psig (83 kPa), and an operating pressure of not more than
30 psig (207 kPa).
The discharge piping serving a
temperature relief valve, pressure relief valve, or combination
of both shall have no valves, obstructions, or means of
isolation and provided with the following:
- Equal to the size of the valve outlet and shall discharge full size to the flood level of the area receiving the discharge and pointing down.
- Materials shall be rated at not less than the operating temperature of the system and approved for such use.
- Discharge pipe shall discharge independently by gravity through an air gap into the drainage system or outside of the building with the end of the pipe not exceeding 2 feet (610 mm) and not less than 6 inches (152 mm) above the ground and pointing downwards.
- Discharge in such a manner that does not cause personal injury or structural damage.
- No part of such discharge pipe shall be trapped or subject to freezing.
- The terminal end of the pipe shall not be threaded.
- Discharge from a relief valve into a water heater pan shall be prohibited.
Where the operating temperature
exceeds 212°F (100°C), the discharge pipe shall be installed
with a splash shield or centrifugal separator.
Where the discharge from
safety valves is capable of being hazardous, discharge of steam
inside the boiler room, such discharge shall be discharged to
the outside of the boiler room. Discharges from relief valves on
industrial boilers shall be discharged to an approved location.
Hot-water heating systems that are subjected to a vacuum while in operation or during shutdown
shall be protected with a vacuum relief valve. Where
the piping configuration, equipment location, and valve
outlets are located below the boiler elevation the system shall
be equipped with a vacuum relief valve at the highest point.
An approved manual shutoff valve shall be installed upstream of all control devices on the main burner
of a gas-fired boiler. The takeoff point for the gas supply to
the pilot shall be upstream of the gas shutoff valve of the main
burner and shall be valved separately. A union or other
approved means of disconnect shall be provided immediately
down-stream of these shutoff valves.
Hot water boilers and steam boilers shall be installed with a low-water cutoff. A coil-type boiler or a
water-tube boiler that requires forced circulation to prevent
overheating of the coils or tubes shall be installed with a flow-sensing device in the outlet piping in lieu of the low-water
cutoff. The low-water cutoff or the flow sensing device shall
be installed so as to prevent damage to the boiler and to
permit testing of the fuel-supply cutoff without draining the
heating system. The low-water cutoff shall shut off the
combustion at a water level set point that is in accordance
with the boiler manufacturer's instructions.
The following requirements shall be retroactive:
- Hot-water-heating boilers, other than manually fired, shall be equipped with two temperature combustion regulators in series. Steam-heating boilers, other than manually fired, shall be equipped with a pressure combustion regulator and a low-water cutoff. (See Section 1008.0)
- Boilers and pressure vessels shall be provided with the required number, size, and capacity of safety or relief valves to ensure positive relief of overpressure in accordance with nationally recognized standards, as applicable. Valves so employed shall be constructed, scaled, and installed in accordance with nationally recognized standards, as applicable.
Where boilers are installed or replaced, clearance shall be provided to allow access for inspection, maintenance, and repair. Passageways around all sides of
boilers shall have an unobstructed width of not less than 18
inches (457 mm). Clearance for repair and cleaning shall be
permitted to be provided through a door or access panel into
another area, provided the opening is of sufficient size.
Exception: Subject to the approval of the Authority Having Jurisdiction, boilers shall be permitted to be installed with a side clearance of less than 18 inches (457 mm), provided that the lesser clearance does not inhibit inspection, maintenance, or repair.
Exception: Subject to the approval of the Authority Having Jurisdiction, boilers shall be permitted to be installed with a side clearance of less than 18 inches (457 mm), provided that the lesser clearance does not inhibit inspection, maintenance, or repair.
Power boilers having a steam-generating
capacity in excess of 5000 pounds per hour (lb/h)
(0.6299 kg/s) or having a heating surface in excess of 1000
square feet (92.9 m2) or input in excess of 5000000 Btu/h
(1464 kW) shall have a clearance of not less than 7 feet (2134
mm) from the top of the boiler to the ceiling.
Steam-heating boilers and hot-water-heating
boilers that exceed one of the following limits:
- 5000000 Btu/h input (1464 kW)
- 5000 pounds steam per hour (0.6299 kg/s) capacity
- 1000 square foot (92.9 m2) heating surface
- 5000000 Btu/h input (1464 kW)
- 5000 pounds steam per hour (0.6299 kg/s) capacity
- 1000 square foot (92.9 m2) heating surface
Package boilers, steam-heating
boilers, and hot-water-heating boilers with no manhole on top
of the shell and not exceeding one of the above limits shall have
a clearance of not less than 2 feet (610 mm) from the ceiling.
The design, installation, and operation of
single burner boilers, multiple burner boilers, stokers, and
atmospheric fluidized-bed boilers with not less than a fuel
input rating of 12.5 E+09 Btu/h (3663 MW) to pulverized fuel
systems, fired or unfired steam generators used to recover
heat from combustion turbines and to other combustion
turbine exhaust systems shall be in accordance with NFPA 85.
That portion of the oil-burning system supplied on boilers and
covered within the scope of NFPA 85 shall be installed in
accordance with NFPA 85.
An installation for which a permit is required shall not be put into service until it has been
inspected and approved by the Authority Having Jurisdiction.
It shall be the duty of the owner or his authorized representative to notify the Authority Having Jurisdiction that the installation is ready for inspection and test. It also shall be the duty of the owner or his authorized representative to post in a conspicuous position on the installation a notice in substantially the following form: "Warning! This installation has not been inspected and approved by the Authority Having Jurisdiction and shall not be covered or concealed until so inspected and approved," and it shall be unlawful for anyone other than the Authority Having Jurisdiction to remove such notice. The Authority Having Jurisdiction shall require such tests as it deems necessary to determine that the installation is in accordance with the provision of this section. Such tests shall be made by the owner or his authorized representative in the presence of the Authority Having Jurisdiction.
Exception: On installations designed and supervised by a registered design professional, the Authority Having Jurisdiction shall have the authority to permit inspection and testing by such registered design professional.
Where the owner or his authorized representative requests inspection of a boiler prior to its installation, the Authority Having Jurisdiction shall make such inspection.
It shall be the duty of the owner or his authorized representative to notify the Authority Having Jurisdiction that the installation is ready for inspection and test. It also shall be the duty of the owner or his authorized representative to post in a conspicuous position on the installation a notice in substantially the following form: "Warning! This installation has not been inspected and approved by the Authority Having Jurisdiction and shall not be covered or concealed until so inspected and approved," and it shall be unlawful for anyone other than the Authority Having Jurisdiction to remove such notice. The Authority Having Jurisdiction shall require such tests as it deems necessary to determine that the installation is in accordance with the provision of this section. Such tests shall be made by the owner or his authorized representative in the presence of the Authority Having Jurisdiction.
Exception: On installations designed and supervised by a registered design professional, the Authority Having Jurisdiction shall have the authority to permit inspection and testing by such registered design professional.
Where the owner or his authorized representative requests inspection of a boiler prior to its installation, the Authority Having Jurisdiction shall make such inspection.
It shall be unlawful to operate a boiler or pressure vessel without first obtaining a valid operating
permit to do so from the Authority Having Jurisdiction.
Such permit shall be displayed in a conspicuous place adjacent
to the boiler or vessel. The operating permit shall not be
issued until the equipment has been inspected and approved
by the Authority Having Jurisdiction.
Exception: The operation of steam-heating boilers, low-pressure hot-water-heating boilers, hot water supply boilers, and pressure vessels in residential occupancies of less than six dwelling units and in utility occupancies.
Exception: The operation of steam-heating boilers, low-pressure hot-water-heating boilers, hot water supply boilers, and pressure vessels in residential occupancies of less than six dwelling units and in utility occupancies.
The Authority Having Jurisdiction shall inspect boilers and pressure vessels operated
under permit in accordance with ASHRAE/ACCA 180 at
such intervals as deemed necessary, but not less frequently than in accordance with Section 1013.4 through Section 1013.7.
Power boilers and miniature boilers shall be inspected externally annually.
Where construction and operating conditions permit, they
shall be subject to inspection internally annually.
Steam-heating boilers and hot-water-heating boilers shall be
inspected externally annually. Where construction and operating
conditions permit, they shall also be subject to inspection
internally annually.
Automatic steam-heating boilers shall be inspected externally biennially.
Where construction and operating conditions permit, they
shall be subject to inspection internally biennially.
Unfired pressure vessels
shall be inspected externally biennially. Where subject to
corrosion and construction permits, they shall be subject to
inspection internally biennially.
Inspection of boilers and pressure vessels covered by insurance shall be permitted to be made by employees of the insuring company holding commissions from the National Board of Boiler and Pressure Vessel Inspectors, subject to approval of the Authority Having Jurisdiction. Approved insuring company inspectors shall make reports on prescribed forms on inspections authorized by the Authority Having Jurisdiction. The reports shall be filed in the Authority Having Jurisdiction office. Company inspectors shall notify the Authority Having Jurisdiction of suspension of insurance because of dangerous conditions, new insurance in effect, and discontinuance of insurance coverage.
Inspection of boilers and pressure vessels covered by insurance shall be permitted to be made by employees of the insuring company holding commissions from the National Board of Boiler and Pressure Vessel Inspectors, subject to approval of the Authority Having Jurisdiction. Approved insuring company inspectors shall make reports on prescribed forms on inspections authorized by the Authority Having Jurisdiction. The reports shall be filed in the Authority Having Jurisdiction office. Company inspectors shall notify the Authority Having Jurisdiction of suspension of insurance because of dangerous conditions, new insurance in effect, and discontinuance of insurance coverage.
Boilers and pressure vessels shall be operated
and maintained in accordance with requirements for
protection of the public established by the Authority Having
Jurisdiction in accordance with nationally recognized standards.
The Authority Having Jurisdiction shall notify the owner or authorized representative of defects or deficiencies and properly corrected. Where such corrections are not made, or where the operation of the boiler or pressure vessel is deemed unsafe by the Authority Having Jurisdiction, they shall have the authority to revoke the permit to operate the boiler or pressure vessel. Where the operation of a boiler or pressure vessel is deemed by the Authority Having Jurisdiction to constitute an immediate danger, the pressure on such boiler or pressure vessel shall be permitted to be relieved at the owner's cost and the boiler or pressure vessel shall not thereafter be operated without approval of the Authority Having Jurisdiction.
The Authority Having Jurisdiction shall notify the owner or authorized representative of defects or deficiencies and properly corrected. Where such corrections are not made, or where the operation of the boiler or pressure vessel is deemed unsafe by the Authority Having Jurisdiction, they shall have the authority to revoke the permit to operate the boiler or pressure vessel. Where the operation of a boiler or pressure vessel is deemed by the Authority Having Jurisdiction to constitute an immediate danger, the pressure on such boiler or pressure vessel shall be permitted to be relieved at the owner's cost and the boiler or pressure vessel shall not thereafter be operated without approval of the Authority Having Jurisdiction.