UpCodes logo
Table of contentsContents
CALIFORNIA FIRE CODE — MATRIX ADOPTION TABLE
APPENDIX C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user.
See Chapter 1 for state agency authority and building applications.)
Adopting AgencyBSCBSC-
CG
SFMHCDDSAOSHPDBSCCDPHAGRDWRCECCASLSLC
T-24T-19*121/ACACSS11R2345
Adopt Entire Chapter
Adopt Entire Chapter as amended (amended sections listed below)X
Adopt only those sections that are listed below
[California Code of Regulations, Title 19, Division 1]
Chapter / Section
C101.1X
* The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Fire Code are a reprint from the current CCR, Title 19, Division 1 text for the code user's convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same.
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance or legislation of the jurisdiction.
User note:
About this appendix: Appendix C focuses on the location and spacing of fire hydrants, which is important to the success of fire-fighting operations. The difficulty with determining the spacing of fire hydrants is that every situation is unique and has unique challenges. Finding one methodology for determining hydrant spacing is difficult. This particular appendix gives one methodology based on the required fire flow that fire departments can work with to set a policy for hydrant distribution around new buildings and facilities in conjunction with Section 507.5.
In addition to the requirements of Section 507.5.1, fire hydrants shall be provided in accordance with this appendix for the protection of buildings, or portions of buildings, hereafter constructed or moved into the jurisdiction.
Exception: [SFM] Group B, S-2 and U occupancies having a floor area not exceeding 1,000 square feet, primarily constructed of noncombustible exterior walls with wood or steel roof framing, having a Class A roof assembly, with uses limited to the following or similar uses:
  1. California State Parks buildings of an accessory nature (restrooms).
  2. Safety roadside rest areas, (SRRA), public restrooms.
  3. Truck inspection facilities, (TIF), California Highway Patrol (CHP) office space and vehicle inspection bays.
  4. Sand/salt storage buildings, storage of sand and salt.
The number of fire hydrants available to a building shall be not less than the minimum specified in Table C102.1.
TABLE C102.1
REQUIRED NUMBER AND SPACING OF FIRE HYDRANTSh
FIRE-FLOW REQUIREMENT
(gpm)
MINIMUM NUMBER
OF HYDRANTS
AVERAGE SPACING
BETWEEN HYDRANTSa, b, c, f, g
(feet)
MAXIMUM DISTANCE FROM ANY
POINT ON STREET OR ROAD
FRONTAGE TO A HYDRANTd, f, g
1,750 or less 1 500 250
1,751—2,250 2 450 225
2,251—2,750 3 450 225
2,751—3,250 3 400 225
3,251—4,000 4 350 210
4,001—5,000 5 300 180
5,001—5,500 6 300 180
5,501—6,000 6 250 150
6,001—7,000 7 250 150
7,001 or more 8 or moree 200 120
For SI: 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
  1. Reduce by 100 feet for dead-end streets or roads.
  2. Where streets are provided with median dividers that cannot be crossed by fire fighters pulling hose lines, or where arterial streets are provided with four or more traffic lanes and have a traffic count of more than 30,000 vehicles per day, hydrant spacing shall average 500 feet on each side of the street and be arranged on an alternating basis.
  3. Where new water mains are extended along streets where hydrants are not needed for protection of structures or similar fire problems, fire hydrants shall be provided at spacing not to exceed 1,000 feet to provide for transportation hazards.
  4. Reduce by 50 feet for dead-end streets or roads.
  5. One hydrant for each 1,000 gallons per minute or fraction thereof.
  6. A 50-percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1 of the California Fire Code.
  7. A 25-percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.2 or 903.3.1.3 of the California Fire Code or Section 313 of the California Residential Code.
  8. The fire code official is authorized to modify the location, number and distribution of fire hydrants based on site-specific constraints and hazards.
Fire apparatus access roads and public streets providing required access to buildings in accordance with Section 503 shall be provided with one or more fire hydrants, as determined by Section C102.1. Where more than one fire hydrant is required, the distance between required fire hydrants shall be in accordance with Sections C103.2 and C103.3.
The average spacing between fire hydrants shall be in accordance with Table C102.1.
Exception: The average spacing shall be permitted to be increased by 10 percent where existing fire hydrants provide all or a portion of the required number of fire hydrants.
The maximum spacing between fire hydrants shall be in accordance with Table C102.1.
Existing fire hydrants on public streets are allowed to be considered as available to meet the requirements of Sections C102 and C103. Existing fire hydrants on adjacent properties are allowed to be considered as available to meet the requirements of Sections C102 and C103 provided that a fire apparatus access road extends between properties and that an easement is established to prevent obstruction of such roads.
See Table C105.1 for standards that are referenced in various sections of this appendix. Standards are listed by the standard identification with the effective date, standard title, and the section or sections of this appendix that reference the standard.
TABLE C105.1
REFERENCED STANDARD
STANDARD
ACRONYM
STANDARD NAME SECTION
HEREIN
REFERENCED
CRC—22 California Residential Code Table C102.1