* | The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Fire Code are a reprint from the current CCR, Title 19, Division 1 text for the code user's convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. |
---|
Plant processing or extraction facilities shall
comply with this chapter and the California Building Code.
The extraction process includes the act of extraction of the
oils and fats by use of a solvent, desolventizing of the raw
material and production of the miscella, distillation of the solvent
from the miscella and solvent recovery. The use, storage,
transfilling, and handling of hazardous materials in these
facilities shall comply with this chapter, other applicable provisions
of this code and the California Building Code.
Existing buildings or
facilities used for the processing of plants or where the
medium of extraction or solvent is changed shall comply with
this chapter.
Processing shall be located in a building
complying with the California Building Code.
Extraction processes utilizing
flammable gasses or flammable cryogenic fluids shall not
be located in any building containing a Group A, E, I or R
occupancy.
The extraction equipment and extraction
process utilizing hydrocarbon solvents shall be located in a
room or area dedicated to extraction.
Postprocessing
and winterization involving the heating or pressurizing
of the miscella to other than normal pressure or temperature
shall be approved and performed in an appliance
listed for such use. Domestic or commercial cooking appliances
shall not be used.
The use of industrial ovens shall
comply with Chapter 30.
The use
of flammable and combustible liquids for liquid extraction
processes where the liquid is boiled, distilled, or evaporated
shall be located within a hazardous exhaust fume hood, rated
for exhausting flammable vapors. Electrical equipment used
within the hazardous exhaust fume hood shall be rated for use
in flammable atmospheres. Heating of flammable or combustible
liquids over an open flame is prohibited.
Exception: The use of a heating element not rated for
flammable atmospheres approved where documentation
from the manufacture or approved testing laboratory indicates
it is rated for heating of flammable liquids.
Liquefied petroleum gases
(LPG) shall not be released to the atmosphere.
Exception: LPG may be released to the atmosphere in
accordance with NFPA 58 Section 7.3.
Systems and equipment used
with the processing and extraction of oils and products from
plants shall comply with Sections 3804.2 through 3804.4,
5003.2, other applicable provisions of this code, the California
Building Code, and the California Mechanical Code.
Systems or equipment used
for the extraction of oils from plant material shall be listed or
approved for the specific use. If the system used for extraction
of oils and products from plant material is not listed, then the
system shall be reviewed by a Registered Design Professional.
The Registered Design Professional shall review and consider any information provided by the system's designer or manufacturer. For systems and equipment not listed for the specific use, a technical report in accordance with Section 3804.3 shall be prepared and submitted to the fire code official for review and approval. The firm or individual preparing the technical report shall be approved by the fire code official prior to performing the analysis.
The Registered Design Professional shall review and consider any information provided by the system's designer or manufacturer. For systems and equipment not listed for the specific use, a technical report in accordance with Section 3804.3 shall be prepared and submitted to the fire code official for review and approval. The firm or individual preparing the technical report shall be approved by the fire code official prior to performing the analysis.
The technical report that has been
reviewed and approved by the fire code official, as required
by Section 3804.2, is required prior to the equipment being
located or installed at the facility. The report shall be prepared
by a Registered Design Professional or other professional
approved by the fire code official.
The technical report shall contain
all of the following:
- Manufacturer information.
- Preparer of record on technical report.
- Date of review and report revision history.
- Signature page shall include all of the following:
- Author of the report.
- Date of report.
- Date and signature of Registered Design Professional of record performing the design or peer review.
- Model number of the item evaluated. If the equipment is provided with a serial number, the serial number shall be included for verification at time of site inspection.
- Methodology of the design or peer review process used to determine minimum safety requirements. Methodology shall consider the basis of design, and shall include a code analysis and code path to demonstrate the reason as to why specific code or standards are applicable or not.
- Equipment description. A list of every component and sub-assembly (fittings, hose, quick disconnects, gauges, site glass, gaskets, valves, pumps, vessels, containers, switches, etc.) of the system or equipment, indicating the manufacturer, model number, material, and solvent compatibility. Manufacturer's data sheets shall be provided.
- A general flow schematic or general process flow diagram of the process. Post-processing or winterization may be included in this diagram. All primary components of the process equipment shall be identified and match the equipment list required in Item 7. Operating temperatures, pressures, and solvent state of matter shall be identified in each primary step or component. A piping and instrumentation diagram (PID or PI&D) shall be provided.
- Analysis of the vessel(s) if pressurized beyond standard atmospheric pressure. Analysis shall include purchased and fabricated components.
- Structural analysis for the frame system supporting the equipment.
- Process safety analysis of the extraction system, from the introduction of raw product to the end of the extraction process.
- Comprehensive process hazard analysis considering failure modes and points of failure throughout the process. The process hazard analysis shall include a review of emergency procedure information provided by the manufacturer of the equipment or process and not that of the facility, building or room.
- Review of the assembly instructions, operational and maintenance manuals provided by the manufacturer.
- List of references used in the analysis.
Prior to operation of the extraction
equipment, where required by the fire code official, the engineer
of record or approved professional, as approved in Section
3805.2, shall inspect the site of the extraction process
once equipment has been installed for compliance with the
technical report and the building analysis. The engineer of
record or approved professional shall provide a report of
findings and observations of the site inspection to the fire
code official prior to the approval of the extraction process.
The field inspection report authored by engineer of record
shall include the serial number of the equipment used in the
process and shall confirm the equipment installed is the same
model and type of equipment identified in the technical report.
For extraction processes utilizing flammable
gases as solvents, a continuous gas detection system
shall be provided. The gas detection threshold shall be no
greater than 25 percent of the lower flammable limit (LFL) of
the materials.
The flammable gas detection system
shall be listed or approved and shall be calibrated to
the types of fuels or gases used for the extraction process.
The gas detection system shall be designed to activate
when the level of flammable gas exceeds 25 percent of the
lower flammable limit (LFL).
Activation of the gas detection system
shall result in all the following:
- Initiation of distinct audible and visual alarm signals in the extraction room.
- Deactivation of all heating systems located in the extraction room.
- Activation of the mechanical ventilation system, where the system is interlocked with gas detection.
Failure of
the gas detection system shall result in the deactivation of
the heating system, activation of the mechanical ventilation
system where the system is interlocked with the gas detection
system and cause a trouble signal to sound in an
approved location.
All electrical components within the
extraction room shall be interlocked with the gas detection
system. Activation of the gas detection system shall disable
all light switches and electrical outlets.