This informative annex is not a part of the requirements of this NFPA document but is included for informational purposes only.

Table Page
C.1 — Electrical Metallic Tubing (EMT) 837
C.1(A)* — Electrical Metallic Tubing (EMT) 841
C.2 — Electrical Nonmetallic Tubing (ENT) 843
C.2(A)* — Electrical Nonmetallic Tubing (ENT) 847
C.3 — Flexible Metal Conduit (FMC) 849
C.3(A)* — Flexible Metal Conduit (FMC) 853
C.4 — Intermediate Metal Conduit (IMC) 855
C.4(A)* — Intermediate Metal Conduit (IMC) 859
C.5 — Liquidtight Flexible Nonmetallic Conduit (Type LFNC-A) 861
C.5(A)* — Liquidtight Flexible Nonmetallic Conduit (Type LFNC-A) 865
C.6 — Liquidtight Flexible Nonmetallic Conduit (Type LFNC-B) 867
C.6(A)* — Liquidtight Flexible Nonmetallic Conduit (Type LFNC-B) 871
C.7 — Liquidtight Flexible Nonmetallic Conduit (Type LFNC-C) 873
C.7(A) — Liquidtight Flexible Nonmetallic Conduit (Type LFNC-C) 877
C.8 — Liquidtight Flexible Metal Conduit (LFMC) 879
C.8(A)* — Liquidtight Flexible Metal Conduit (LFMC) 883
C.9 — Rigid Metal Conduit (RMC) 885
C.9(A)* — Rigid Metal Conduit (RMC) 889
C.10 — Rigid PVC Conduit, Schedule 80 891
C.10(A)* — Rigid PVC Conduit, Schedule 80 895
C.11 — Rigid PVC Conduit, Schedule 40 and HDPE Conduit 897
C.11(A)* — Rigid PVC Conduit, Schedule 40 and HDPE Conduit 901
C.12 — Type A, Rigid PVC Conduit 903
C.12(A)* — Type A, Rigid PVC Conduit 907
C.13 — Type EB, PVC Conduit 909
C.13(A)* — Type EB, PVC Conduit 913
*Where this table is used in conjunction with Tables C.1 through C.13, the conductors installed must be of the compact type.

Table C.1 Maximum Number of Conductors or Fixture Wires in Electrical Metallic Tubing (EMT)
(Based on Chapter 9: Table 1, Table 4, and Table 5)

Type Conductor
Size (AWG/kcmil)
Trade Size (Metric Designator)
3/8
(12)
1/2
(16)
3/4
(21)
1
(27)
11/4
(35)
11/2
(41)
2
(53)
21/2
(63)
3
(78)
31/2
(91)
4
(103)
5
(129)
6
(155)
CONDUCTORS
RHH, RHW, RHW-2 14 4 7 11 20 27 46 80 120 157 201
12 3 6 9 17 23 38 66 100 131 167
10 2 5 8 13 18 30 53 81 105 135
8 1 2 4 7 9 16 28 42 55 70
6 1 1 3 5 8 13 22 34 44 56
4 1 1 2 4 6 10 17 26 34 44
3 1 1 1 4 5 9 15 23 30 38
2 1 1 1 3 4 7 13 20 26 33
1 0 1 1 1 3 5 9 13 17 22
1/0 0 1 1 1 2 4 7 11 15 19
2/0 0 1 1 1 2 4 6 10 13 17
3/0 0 0 1 1 1 3 5 8 11 14
4/0 0 0 1 1 1 3 5 7 9 12
250 0 0 0 1 1 1 3 5 7 9
300 0 0 0 1 1 1 3 5 6 8
350 0 0 0 1 1 1 3 4 6 7
400 0 0 0 1 1 1 2 4 5 7
500 0 0 0 0 1 1 2 3 4 6
600 0 0 0 0 1 1 1 3 4 5
700 0 0 0 0 0 1 1 2 3 4
750 0 0 0 0 0 1 1 2 3 4
800 0 0 0 0 0 1 1 2 3 4
900 0 0 0 0 0 1 1 1 3 3
1000 0 0 0 0 0 1 1 1 2 3
1250 0 0 0 0 0 0 1 1 1 2
1500 0 0 0 0 0 0 1 1 1 1
1750 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 1 1 1 1
TW, THHW, THW, THW-2 14 8 15 25 43 58 96 168 254 332 424
12 6 11 19 33 45 74 129 195 255 326
10 5 8 14 24 33 55 96 145 190 243
8 2 5 8 13 18 30 53 81 105 135
RHH*, RHW*, RHW-2* 14 6 10 16 28 39 64 112 169 221 282
12 4 8 13 23 31 51 90 136 177 227
10 3 6 10 18 24 40 70 106 138 177
8 1 4 6 10 14 24 42 63 83 106
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2* 6 1 3 4 8 11 18 32 48 63 81
4 1 1 3 6 8 13 24 36 47 60
3 1 1 3 5 7 12 20 31 40 52
2 1 1 2 4 6 10 17 26 34 44
1 1 1 1 3 4 7 12 18 24 31
1/0 0 1 1 2 3 6 10 16 20 26
2/0 0 1 1 1 3 5 9 13 17 22
3/0 0 1 1 1 2 4 7 11 15 19
4/0 0 0 1 1 1 3 6 9 12 16
250 0 0 1 1 1 3 5 7 10 13
300 0 0 1 1 1 2 4 6 8 11
350 0 0 0 1 1 1 4 6 7 10
400 0 0 0 1 1 1 3 5 7 9
500 0 0 0 1 1 1 3 4 6 7
600 0 0 0 1 1 1 2 3 4 6
700 0 0 0 0 1 1 1 3 4 5
750 0 0 0 0 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 3 5
900 0 0 0 0 0 1 1 2 3 4
1000 0 0 0 0 0 1 1 2 3 4
1250 0 0 0 0 0 1 1 1 2 3
1500 0 0 0 0 0 1 1 1 1 2
1750 0 0 0 0 0 0 1 1 1 2
2000 0 0 0 0 0 0 1 1 1 1
THHN, THWN, THWN-2 14 12 22 35 61 84 138 241 364 476 608
12 9 16 26 45 61 101 176 266 347 443
10 5 10 16 28 38 63 111 167 219 279
8 3 6 9 16 22 36 64 96 126 161
6 2 4 7 12 16 26 46 69 91 116
4 1 2 4 7 10 16 28 43 56 71
3 1 1 3 6 8 13 24 36 47 60
2 1 1 3 5 7 11 20 30 40 51
1 1 1 1 4 5 8 15 22 29 37
1/0 1 1 1 3 4 7 12 19 25 32
2/0 0 1 1 2 3 6 10 16 20 26
3/0 0 1 1 1 3 5 8 13 17 22
4/0 0 1 1 1 2 4 7 11 14 18
250 0 0 1 1 1 3 6 9 11 15
300 0 0 1 1 1 3 5 7 10 13
350 0 0 1 1 1 2 4 6 9 11
400 0 0 0 1 1 1 4 6 8 10
500 0 0 0 1 1 1 3 5 6 8
600 0 0 0 1 1 1 2 4 5 7
700 0 0 0 1 1 1 2 3 4 6
750 0 0 0 0 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 3 3 4
1000 0 0 0 0 1 1 1 2 3 4
FEP, FEPB, PFA, PFAH, TFE 14 12 21 34 60 81 134 234 354 462 590
12 9 15 25 43 59 98 171 258 337 430
10 6 11 18 31 42 70 122 185 241 309
8 3 6 10 18 24 40 70 106 138 177
6 2 4 7 12 17 28 50 75 98 126
4 1 3 5 9 12 20 35 53 69 88
3 1 2 4 7 10 16 29 44 57 73
2 1 1 3 6 8 13 24 36 47 60
PFA, PFAH, TFE 1 1 1 2 4 6 9 16 25 33 42
PFA, PFAH, TFE, Z 1/0 1 1 1 3 5 8 14 21 27 35
2/0 0 1 1 3 4 6 11 17 22 29
3/0 0 1 1 2 3 5 9 14 18 24
4/0 0 1 1 1 2 4 8 11 15 19
Z 14 14 25 41 72 98 161 282 426 556 711
12 10 18 29 51 69 114 200 302 394 504
10 6 11 18 31 42 70 122 185 241 309
8 4 7 11 20 27 44 77 117 153 195
6 3 5 8 14 19 31 54 82 107 137
4 1 3 5 9 13 21 37 56 74 94
3 1 2 4 7 9 15 27 41 54 69
2 1 1 3 6 8 13 22 34 45 57
1 1 1 2 4 6 10 18 28 36 46
XHHW, ZW, XHHW-2, XHH 14 8 15 25 43 58 96 168 254 332 424
12 6 11 19 33 45 74 129 195 255 326
10 5 8 14 24 33 55 96 145 190 243
8 2 5 8 13 18 30 53 81 105 135
6 1 3 6 10 14 22 39 60 78 100
4 1 2 4 7 10 16 28 43 56 72
3 1 1 3 6 8 14 24 36 48 61
2 1 1 3 5 7 11 20 31 40 51
XHHW, XHHW-2, XHH 1 1 1 1 4 5 8 15 23 30 38
1/0 1 1 1 3 4 7 13 19 25 32
2/0 0 1 1 2 3 6 10 16 21 27
3/0 0 1 1 1 3 5 9 13 17 22
4/0 0 1 1 1 2 4 7 11 14 18
250 0 0 1 1 1 3 6 9 12 15
300 0 0 1 1 1 3 5 8 10 13
350 0 0 1 1 1 2 4 7 9 11
400 0 0 0 1 1 1 4 6 8 10
500 0 0 0 1 1 1 3 5 6 8
600 0 0 0 1 1 1 2 4 5 6
700 0 0 0 0 1 1 2 3 4 6
750 0 0 0 0 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 3 3 4
1000 0 0 0 0 0 1 1 2 3 4
1250 0 0 0 0 0 1 1 1 2 3
1500 0 0 0 0 0 1 1 1 1 3
1750 0 0 0 0 0 0 1 1 1 2
2000 0 0 0 0 0 0 1 1 1 1
FIXTURE WIRES
RFH-2, FFH-2, RFHH-2 18 8 14 24 41 56 92 161 244 318 407
16 7 12 20 34 47 78 136 205 268 343
SF-2, SFF-2 18 10 18 30 52 71 116 203 307 401 513
16 8 15 25 43 58 96 168 254 332 424
14 7 12 20 34 47 78 136 205 268 343
SF-1, SFF-1 18 18 33 53 92 125 206 360 544 710 908
RFH-1, TF, TFF, XF, XFF 18 14 24 39 68 92 152 266 402 524 670
16 11 19 31 55 74 123 215 324 423 541
XF, XFF 14 8 15 25 43 58 96 168 254 332 424
TFN, TFFN 18 22 38 63 109 148 244 426 643 839 1073
16 17 29 48 83 113 186 325 491 641 819
PF, PFF, PGF, PGFF, PAF, PTF, PTFF, PAFF 18 21 36 59 103 140 231 404 610 796 1017
16 16 28 46 79 108 179 312 471 615 787
14 12 21 34 60 81 134 234 354 462 590
ZF, ZFF, ZHF 18 27 47 77 133 181 298 520 786 1026 1311
16 20 35 56 98 133 220 384 580 757 967
14 14 25 41 72 98 161 282 426 556 711
KF-2, KFF-2 18 40 71 115 199 271 447 781 1179 1539 1967
16 28 49 80 139 189 312 545 823 1074 1372
14 19 33 54 93 127 209 366 553 721 922
12 13 23 37 65 88 146 254 384 502 641
10 8 15 25 43 58 96 168 254 332 424
KF-1, KFF-1 18 46 82 133 230 313 516 901 1361 1776 2269
16 33 57 93 161 220 363 633 956 1248 1595
14 22 38 63 109 148 244 426 643 839 1073
12 14 25 41 72 98 161 282 426 556 711
10 9 16 27 47 64 105 184 278 363 464
XF, XFF 12 4 8 13 23 31 51 90 136 177 227
10 3 6 10 18 24 40 70 106 138 177
Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.1(A) should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires. Consult manufacturer's conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

Table C.1(A) Maximum Number of Conductors or Fixture Wires in Electrical Metallic Tubing (EMT)
(Based on Chapter 9: Table 1, Table 4, and Table 5A)

Type Conductor Size (AWG/kcmil) Trade Size (Metric Designator)
3/8
(12)
1/2
(16)
3/4
(21)
1
(27)
11/4
(35)
11/2
(41)
2
(53)
21/2
(63)
3
(78)
31/2
(91)
4
(103)
5
(129)
6
(155)
COMPACT CONDUCTORS
THW, THW-2, THHW 8 2 4 6 11 16 26 46 69 90 115
6 1 3 5 9 12 20 35 53 70 89
4 1 2 4 6 9 15 26 40 52 67
2 1 1 3 5 7 11 19 29 38 49
1 1 1 1 3 4 8 13 21 27 34
1/0 1 1 1 3 4 7 12 18 23 30
2/0 0 1 1 2 3 5 10 15 20 25
3/0 0 1 1 1 3 5 8 13 17 21
4/0 0 1 1 1 2 4 7 11 14 18
250 0 0 1 1 1 3 5 8 11 14
300 0 0 1 1 1 3 5 7 9 12
350 0 0 1 1 1 2 4 6 8 11
400 0 0 0 1 1 1 4 6 8 10
500 0 0 0 1 1 1 3 5 6 8
600 0 0 0 1 1 1 2 4 5 7
700 0 0 0 1 1 1 2 3 4 6
750 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 3 4 5
1000 0 0 0 0 1 1 1 2 3 4
THHN, THWN, THWN-2 8
6 2 4 7 13 18 29 52 78 102 130
4 1 3 4 8 11 18 32 48 63 81
2 1 1 3 6 8 13 23 34 45 58
1 1 1 2 4 6 10 17 26 34 43
1/0 1 1 1 3 5 8 14 22 29 37
2/0 1 1 1 3 4 7 12 18 24 30
3/0 0 1 1 2 3 6 10 15 20 25
4/0 0 1 1 1 3 5 8 12 16 21
250 0 1 1 1 1 4 6 10 13 16
300 0 0 1 1 1 3 5 8 11 14
350 0 0 1 1 1 3 5 7 10 12
400 0 0 1 1 1 2 4 6 9 11
500 0 0 0 1 1 1 4 5 7 9
600 0 0 0 1 1 1 3 4 6 7
700 0 0 0 1 1 1 2 4 5 7
750 0 0 0 1 1 1 2 4 5 6
900 0 0 0 0 1 1 1 3 4 5
1000 0 0 0 0 1 1 1 3 3 4
XHHW, XHHW-2 8 3 5 8 15 20 34 59 90 117 149
6 1 4 6 11 15 25 44 66 87 111
4 1 3 4 8 11 18 32 48 63 81
2 1 1 3 6 8 13 23 34 45 58
1 1 1 2 4 6 10 17 26 34 43
1/0 1 1 1 3 5 8 14 22 29 37
2/0 1 1 1 3 4 7 12 18 24 31
3/0 0 1 1 2 3 6 10 15 20 25
4/0 0 1 1 1 3 5 8 13 17 21
250 0 1 1 1 2 4 7 10 13 17
300 0 0 1 1 1 3 6 9 11 14
350 0 0 1 1 1 3 5 8 10 13
400 0 0 1 1 1 2 4 7 9 11
500 0 0 0 1 1 1 4 6 7 9
600 0 0 0 1 1 1 3 4 6 8
700 0 0 0 1 1 1 2 4 5 7
750 0 0 0 1 1 1 2 3 5 6
900 0 0 0 0 1 1 1 3 4 5
1000 0 0 0 0 1 1 1 3 4 5
Definition: Compact stranding is the result of a manufacturing process where the stranded conductor is compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

Table C.2 Maximum Number of Conductors or Fixture Wires in Electrical Nonmetallic Tubing (ENT)
(Based on Chapter 9: Table 1, Table 4, and Table 5)

Type Conductor Size (AWG/kcmil) Trade Size (Metric Designator)
3/8
(12)
1/2
(16)
3/4
(21)
1
(27)
11/4
(35)
11/2
(41)
2
(53)
21/2
(63)
3
(78)
31/2
(91)
4
(103)
5
(129)
6
(155)
CONDUCTORS
RHH, RHW, RHW-2 14 4 7 11 20 27 45
12 3 5 9 16 22 37
10 2 4 7 13 18 30
8 1 2 4 7 9 15
6 1 1 3 5 7 12
4 1 1 2 4 6 10
3 1 1 1 4 5 8
2 1 1 1 3 4 7
1 0 1 1 1 3 5
1/0 0 1 1 1 2 4
2/0 0 0 1 1 1 3
3/0 0 0 1 1 1 3
4/0 0 0 1 1 1 2
250 0 0 0 1 1 1
300 0 0 0 1 1 1
350 0 0 0 1 1 1
400 0 0 0 1 1 1
500 0 0 0 0 1 1
600 0 0 0 0 1 1
700 0 0 0 0 0 1
750 0 0 0 0 0 1
800 0 0 0 0 0 1
900 0 0 0 0 0 1
1000 0 0 0 0 0 1
1250 0 0 0 0 0 0
1500 0 0 0 0 0 0
1750 0 0 0 0 0 0
2000 0 0 0 0 0 0
TW, THHW, THW, THW-2 14 8 14 24 42 57 94
12 6 11 18 32 44 72
10 4 8 13 24 32 54
8 2 4 7 13 18 30
RHH*, RHW*, RHW-2* 14 5 9 16 28 38 63
12 4 8 13 22 30 50
10 3 6 10 17 24 39
8 1 3 6 10 14 23
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2* 6 1 2 4 8 11 18
4 1 1 3 6 8 13
3 1 1 3 5 7 11
2 1 1 2 4 6 10
1 0 1 1 3 4 7
1/0 0 1 1 2 3 6
2/0 0 1 1 1 3 5
3/0 0 1 1 1 2 4
4/0 0 0 1 1 1 3
250 0 0 1 1 1 3
300 0 0 1 1 1 2
350 0 0 0 1 1 1
400 0 0 0 1 1 1
500 0 0 0 1 1 1
600 0 0 0 0 1 1
700 0 0 0 0 1 1
750 0 0 0 0 1 1
800 0 0 0 0 1 1
900 0 0 0 0 0 1
1000 0 0 0 0 0 1
1250 0 0 0 0 0 1
1500 0 0 0 0 0 1
1750 0 0 0 0 0 0
2000 0 0 0 0 0 0
THHN, THWN, THWN-2 14 11 21 34 60 82 135
12 8 15 25 43 59 99
10 5 9 15 27 37 62
8 3 5 9 16 21 36
6 1 4 6 11 15 26
4 1 2 4 7 9 16
3 1 1 3 6 8 13
2 1 1 3 5 7 11
1 1 1 1 3 5 8
1/0 1 1 1 3 4 7
2/0 0 1 1 2 3 6
3/0 0 1 1 1 3 5
4/0 0 1 1 1 2 4
250 0 0 1 1 1 3
300 0 0 1 1 1 3
350 0 0 1 1 1 2
400 0 0 0 1 1 1
500 0 0 0 1 1 1
600 0 0 0 1 1 1
700 0 0 0 0 1 1
750 0 0 0 0 1 1
800 0 0 0 0 1 1
900 0 0 0 0 1 1
1000 0 0 0 0 0 1
FEP, FEPB, PFA, PFAH, TFE 14 11 20 33 58 79 131
12 8 15 24 42 58 96
10 6 10 17 30 41 69
8 3 6 10 17 24 39
6 2 4 7 12 17 28
4 1 3 5 8 12 19
3 1 2 4 7 10 16
2 1 1 3 6 8 13
PFA, PFAH, TFE 1 1 1 2 4 5 9
PFA, PFAH, TFE, Z 1/0 1 1 1 3 4 8
2/0 0 1 1 3 4 6
3/0 0 1 1 2 3 5
4/0 0 1 1 1 2 4
Z 14 13 24 40 70 95 158
12 9 17 28 49 68 112
10 6 10 17 30 41 69
8 3 6 11 19 26 43
6 2 4 7 13 18 30
4 1 3 5 9 12 21
3 1 2 4 6 9 15
2 1 1 3 5 7 12
1 1 1 2 4 6 10
XHHW, ZW, XHHW-2, XHH 14 8 14 24 42 57 94
12 6 11 18 32 44 72
10 4 8 13 24 32 54
8 2 4 7 13 18 30
6 1 3 5 10 13 22
4 1 2 4 7 9 16
3 1 1 3 6 8 13
2 1 1 3 5 7 11
XHHW, XHHW-2, XHH 1 1 1 1 3 5 8
1/0 0 1 1 3 4 7
2/0 0 1 1 2 3 6
3/0 0 1 1 1 3 5
4/0 0 1 1 1 2 4
250 0 0 1 1 1 3
300 0 0 1 1 1 3
350 0 0 1 1 1 2
400 0 0 0 1 1 1
500 0 0 0 1 1 1
600 0 0 0 1 1 1
700 0 0 0 0 1 1
750 0 0 0 0 1 1
800 0 0 0 0 1 1
900 0 0 0 0 1 1
1000 0 0 0 0 0 1
1250 0 0 0 0 0 1
1500 0 0 0 0 0 1
1750 0 0 0 0 0 0
2000 0 0 0 0 0 0
FIXTURE WIRES
RFH-2, FFH-2, RFHH-2 18 8 14 23 40 54 90
16 6 12 19 33 46 76
SF-2, SFF-2 18 10 17 29 50 69 114
16 8 14 24 42 57 94
14 6 12 19 33 46 76
SF-1, SFF-1 18 17 31 51 89 122 202
RFH-1, TF, TFF, XF, XFF 18 13 23 38 66 90 149
16 10 18 30 53 73 120
XF, XFF 14 8 14 24 42 57 94
TFN, TFFN 18 20 37 60 105 144 239
16 16 28 46 80 110 183
PF, PFF, PGF, PGFF, PAF, PTF, PTFF, PAFF 18 19 35 57 100 137 227
16 15 27 44 77 106 175
14 11 20 33 58 79 131
ZF, ZFF, ZHF 18 25 45 74 129 176 292
16 18 33 54 95 130 216
14 13 24 40 70 95 158
KF-2, KFF-2 18 38 67 111 193 265 439
16 26 47 77 135 184 306
14 18 31 52 91 124 205
12 12 22 36 63 86 143
10 8 14 24 42 57 94
KF-1, KFF-1 18 44 78 128 223 305 506
16 31 55 90 157 214 355
14 20 37 60 105 144 239
12 13 24 40 70 95 158
10 9 16 26 45 62 103
XF, XFF 12 4 8 13 22 30 50
10 3 6 10 17 24 39
Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.2(A) should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires.
Consult manufacturer's conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

Table C.2(A) Maximum Number of Conductors or Fixture Wires in Electrical Nonmetallic Tubing (ENT)
(Based on Chapter 9: Table 1, Table 4, and Table 5A)

Type Conductor Size (AWG/kcmil) Trade Size (Metric Designator)
3/8
(12)
1/2
(16)
3/4
(21)
1
(27)
11/4
(35)
11/2
(41)
2
(53)
21/2
(63)
3
(78)
31/2
(91)
4
(103)
5
(129)
6
(155)
COMPACT CONDUCTORS
THW, THW-2, THHW 8 1 4 6 11 15 26
6 1 3 5 9 12 20
4 1 1 3 6 9 15
2 1 1 2 5 6 11
1 1 1 1 3 4 7
1/0 0 1 1 3 4 6
2/0 0 1 1 2 3 5
3/0 0 1 1 1 3 5
4/0 0 1 1 1 2 4
250 0 0 1 1 1 3
300 0 0 1 1 1 2
350 0 0 1 1 1 2
400 0 0 0 1 1 1
500 0 0 0 1 1 1
600 0 0 0 1 1 1
700 0 0 0 0 1 1
750 0 0 0 0 1 1
900 0 0 0 0 1 1
1000 0 0 0 0 1 1
THHN, THWN, THWN-2 8
6 2 4 7 13 17 29
4 1 2 4 8 11 18
2 1 1 3 5 8 13
1 1 1 2 4 6 9
1/0 1 1 1 3 5 8
2/0 0 1 1 3 4 7
3/0 0 1 1 2 3 5
4/0 0 1 1 1 3 4
250 0 0 1 1 1 3
300 0 0 1 1 1 3
350 0 0 1 1 1 3
400 0 0 1 1 1 2
500 0 0 0 1 1 1
600 0 0 0 1 1 1
700 0 0 0 1 1 1
750 0 0 0 1 1 1
900 0 0 0 0 1 1
1000 0 0 0 0 1 1
XHHW, XHHW-2 8 3 5 8 14 20 33
6 1 4 6 11 15 25
4 1 2 4 8 11 18
2 1 1 3 5 8 13
1 1 1 2 4 6 9
1/0 1 1 1 3 5 8
2/0 1 1 1 3 4 7
3/0 0 1 1 2 3 5
4/0 0 1 1 1 3 5
250 0 0 1 1 1 4
300 0 0 1 1 1 3
350 0 0 1 1 1 3
400 0 0 1 1 1 2
500 0 0 0 1 1 1
600 0 0 0 1 1 1
700 0 0 0 1 1 1
750 0 0 0 1 1 1
900 0 0 0 0 1 1
1000 0 0 0 0 1 1
Definition: Compact stranding is the result of a manufacturing process where the stranded conductor is compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

Table C.3 Maximum Number of Conductors or Fixture Wires in Flexible Metal Conduit (FMC)
(Based on Chapter 9: Table 1, Table 4, and Table 5)

Type Conductor Size (AWG/kcmil) Trade Size (Metric Designator)
3/8
(12)
1/2
(16)
3/4
(21)
1
(27)
11/4
(35)
11/2
(41)
2
(53)
21/2
(63)
3
(78)
31/2
(91)
4
(103)
5
(129)
6
(155)
CONDUCTORS
RHH, RHW, RHW-2 14 1 4 7 11 17 25 44 67 96 131 171
12 1 3 6 9 14 21 37 55 80 109 142
10 1 3 5 7 11 17 30 45 64 88 115
8 0 1 2 4 6 9 15 23 34 46 60
6 0 1 1 3 5 7 12 19 27 37 48
4 0 1 1 2 4 5 10 14 21 29 37
3 0 1 1 1 3 5 8 13 18 25 33
2 0 1 1 1 3 4 7 11 16 22 28
1 0 0 1 1 1 2 5 7 10 14 19
1/0 0 0 1 1 1 2 4 6 9 12 16
2/0 0 0 1 1 1 1 3 5 8 11 14
3/0 0 0 0 1 1 1 3 5 7 9 12
4/0 0 0 0 1 1 1 2 4 6 8 10
250 0 0 0 0 1 1 1 3 4 6 8
300 0 0 0 0 1 1 1 2 4 5 7
350 0 0 0 0 1 1 1 2 3 5 6
400 0 0 0 0 0 1 1 1 3 4 6
500 0 0 0 0 0 1 1 1 3 4 5
600 0 0 0 0 0 1 1 1 2 3 4
700 0 0 0 0 0 0 1 1 1 3 3
750 0 0 0 0 0 0 1 1 1 2 3
800 0 0 0 0 0 0 1 1 1 2 3
900 0 0 0 0 0 0 1 1 1 2 3
1000 0 0 0 0 0 0 1 1 1 1 3
1250 0 0 0 0 0 0 0 1 1 1 1
1500 0 0 0 0 0 0 0 1 1 1 1
1750 0 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 0 0 1 1 1
TW, THHW, THW, THW-2 14 3 9 15 23 36 53 94 141 203 277 361
12 2 7 11 18 28 41 72 108 156 212 277
10 1 5 8 13 21 30 54 81 116 158 207
8 1 3 5 7 11 17 30 45 64 88 115
RHH*, RHW*, RHW-2* 14 1 6 10 15 24 35 62 94 135 184 240
12 1 5 8 12 19 28 50 75 108 148 193
10 1 4 6 10 15 22 39 59 85 115 151
8 1 1 4 6 9 13 23 35 51 69 90
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2* 6 1 1 3 4 7 10 18 27 39 53 69
4 0 1 1 3 5 7 13 20 29 39 51
3 0 1 1 3 4 6 11 17 25 34 44
2 0 1 1 2 4 5 10 14 21 29 37
1 0 1 1 1 2 4 7 10 15 20 26
1/0 0 0 1 1 1 3 6 9 12 17 22
2/0 0 0 1 1 1 3 5 7 10 14 19
3/0 0 0 1 1 1 2 4 6 9 12 16
4/0 0 0 0 1 1 1 3 5 7 10 13
250 0 0 0 1 1 1 3 4 6 8 11
300 0 0 0 1 1 1 2 3 5 7 9
350 0 0 0 0 1 1 1 3 4 6 8
400 0 0 0 0 1 1 1 3 4 6 7
500 0 0 0 0 1 1 1 2 3 5 6
600 0 0 0 0 0 1 1 1 3 4 5
700 0 0 0 0 0 1 1 1 2 3 4
750 0 0 0 0 0 1 1 1 2 3 4
800 0 0 0 0 0 1 1 1 1 3 4
900 0 0 0 0 0 0 1 1 1 3 3
1000 0 0 0 0 0 0 1 1 1 2 3
1250 0 0 0 0 0 0 1 1 1 1 2
1500 0 0 0 0 0 0 0 1 1 1 1
1750 0 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 0 1 1 1 1
THHN, THWN, THWN-2 14 4 13 22 33 52 76 135 202 291 396 518
12 3 9 16 24 38 56 98 147 212 289 378
10 1 6 10 15 24 35 62 93 134 182 238
8 1 3 6 9 14 20 35 53 77 105 137
6 1 2 4 6 10 14 25 38 55 76 99
4 0 1 2 4 6 9 16 24 34 46 61
3 0 1 1 3 5 7 13 20 29 39 51
2 0 1 1 3 4 6 11 17 24 33 43
1 0 1 1 1 3 4 8 12 18 24 32
1/0 0 1 1 1 2 4 7 10 15 20 27
2/0 0 0 1 1 1 3 6 9 12 17 22
3/0 0 0 1 1 1 2 5 7 10 14 18
4/0 0 0 1 1 1 1 4 6 8 12 15
250 0 0 0 1 1 1 3 5 7 9 12
300 0 0 0 1 1 1 3 4 6 8 11
350 0 0 0 1 1 1 2 3 5 7 9
400 0 0 0 0 1 1 1 3 5 6 8
500 0 0 0 0 1 1 1 2 4 5 7
600 0 0 0 0 0 1 1 1 3 4 5
700 0 0 0 0 0 1 1 1 3 4 5
750 0 0 0 0 0 1 1 1 2 3 4
800 0 0 0 0 0 1 1 1 2 3 4
900 0 0 0 0 0 0 1 1 1 3 4
1000 0 0 0 0 0 0 1 1 1 3 3
FEP, FEPB, PFA, PFAH, TFE 14 4 12 21 32 51 74 130 196 282 385 502
12 3 9 15 24 37 54 95 143 206 281 367
10 2 6 11 17 26 39 68 103 148 201 263
8 1 4 6 10 15 22 39 59 85 115 151
6 1 2 4 7 11 16 28 42 60 82 107
4 1 1 3 5 7 11 19 29 42 57 75
3 0 1 2 4 6 9 16 24 35 48 62
2 0 1 1 3 5 7 13 20 29 39 51
PFA, PFAH, TFE 1 0 1 1 2 3 5 9 14 20 27 36
PFA, PFAH, TFE, Z 1/0 0 1 1 1 3 4 8 11 17 23 30
2/0 0 1 1 1 2 3 6 9 14 19 24
3/0 0 0 1 1 1 3 5 8 11 15 20
4/0 0 0 1 1 1 2 4 6 9 13 16
Z 14 5 15 25 39 61 89 157 236 340 463 605
12 4 11 18 28 43 63 111 168 241 329 429
10 2 6 11 17 26 39 68 103 148 201 263
8 1 4 7 11 17 24 43 65 93 127 166
6 1 3 5 7 12 17 30 45 65 89 117
4 1 1 3 5 8 12 21 31 45 61 80
3 0 1 2 4 6 8 15 23 33 45 58
2 0 1 1 3 5 7 12 19 27 37 49
1 0 1 1 2 4 6 10 15 22 30 39
XHHW, ZW, XHHW-2, XHH 14 3 9 15 23 36 53 94 141 203 277 361
12 2 7 11 18 28 41 72 108 156 212 277
10 1 5 8 13 21 30 54 81 116 158 207
8 1 3 5 7 11 17 30 45 64 88 115
6 1 1 3 5 8 12 22 33 48 65 85
4 0 1 2 4 6 9 16 24 34 47 61
3 0 1 1 3 5 7 13 20 29 40 52
2 0 1 1 3 4 6 11 17 24 33 44
XHH, XHHW, XHHW-2 1 0 1 1 1 3 5 8 13 18 25 32
1/0 0 1 1 1 2 4 7 10 15 21 27
2/0 0 0 1 1 2 3 6 9 13 17 23
3/0 0 0 1 1 1 3 5 7 10 14 19
4/0 0 0 1 1 1 2 4 6 9 12 15
250 0 0 0 1 1 1 3 5 7 10 13
300 0 0 0 1 1 1 3 4 6 8 11
350 0 0 0 1 1 1 2 4 5 7 9
400 0 0 0 0 1 1 1 3 5 6 8
500 0 0 0 0 1 1 1 3 4 5 7
600 0 0 0 0 0 1 1 1 3 4 5
700 0 0 0 0 0 1 1 1 3 4 5
750 0 0 0 0 0 1 1 1 2 3 4
800 0 0 0 0 0 1 1 1 2 3 4
900 0 0 0 0 0 0 1 1 1 3 4
1000 0 0 0 0 0 0 1 1 1 3 3
1250 0 0 0 0 0 0 1 1 1 1 3
1500 0 0 0 0 0 0 1 1 1 1 2
1750 0 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 0 1 1 1 1
FIXTURE WIRES
RFH-2, FFH-2, RFHH-2 18 3 8 14 22 35 51 90 135 195 265 346
16 2 7 12 19 29 43 76 114 164 223 292
SF-2, SFF-2 18 4 11 18 28 44 64 113 170 246 334 437
16 3 9 15 23 36 53 94 141 203 277 361
14 2 7 12 19 29 43 76 114 164 223 292
SF-1, SFF-1 18 7 19 33 50 78 114 201 302 435 592 773
RFH-1, TF, TFF, XF, XFF 18 5 14 24 37 58 84 148 223 321 437 571
16 4 11 19 30 47 68 120 180 259 353 461
XF, XFF 14 3 9 15 23 36 53 94 141 203 277 361
TFN, TFFN 18 8 23 38 59 93 135 237 357 514 699 914
16 6 17 29 45 71 103 181 272 392 534 698
PF, PFF, PGF, PGFF, PAF, PTF, PTFF, PAFF 18 8 22 36 56 88 128 225 338 487 663 866
16 6 17 28 43 68 99 174 262 377 513 670
14 4 12 21 32 51 74 130 196 282 385 502
ZF, ZFF, ZHF 18 10 28 47 72 113 165 290 436 628 855 1117
16 7 20 35 53 83 122 214 322 463 631 824
14 5 15 25 39 61 89 157 236 340 463 605
KF-2, KFF-2 18 15 42 71 109 170 247 436 654 942 1282 1675
16 10 29 49 76 118 173 304 456 657 895 1169
14 7 20 33 51 80 116 204 307 442 601 785
12 5 13 23 35 55 80 142 213 307 418 546
10 3 9 15 23 36 53 94 141 203 277 361
KF-1, KFF-1 18 18 48 82 125 196 286 503 755 1087 1480 1933
16 12 34 57 88 138 201 353 530 764 1040 1358
14 8 23 38 59 93 135 237 357 514 699 914
12 5 15 25 39 61 89 157 236 340 463 605
10 3 10 16 25 40 58 103 154 222 303 395
XF, XFF 12 1 5 8 12 19 28 50 75 108 148 193
10 1 4 6 10 15 22 39 59 85 115 151
Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.3(A) should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires. Consult manufacturer's conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

Table C.3(A) Maximum Number of Conductors or Fixture Wires in Flexible Metal Conduit (FMC)
(Based on Chapter 9: Table 1, Table 4, and Table 5A)

Type Conductor Size (AWG/kcmil) Trade Size (Metric Designator)
3/8
(12)
1/2
(16)
3/4
(21)
1
(27)
11/4
(35)
11/2
(41)
2
(53)
21/2
(63)
3
(78)
31/2
(91)
4
(103)
5
(129)
6
(155)
COMPACT CONDUCTORS
THW, THW-2, THHW 8 1 2 4 6 10 14 25 38 55 75 98
6 1 1 3 5 7 11 20 29 43 58 76
4 0 1 2 3 5 8 15 22 32 43 57
2 0 1 1 2 4 6 11 16 23 32 42
1 0 1 1 1 3 4 7 11 16 22 29
1/0 0 1 1 1 2 3 6 10 14 19 25
2/0 0 0 1 1 1 3 5 8 12 16 21
3/0 0 0 1 1 1 2 4 7 10 14 18
4/0 0 0 1 1 1 1 4 6 8 11 15
250 0 0 0 1 1 1 3 4 7 9 12
300 0 0 0 1 1 1 2 4 6 8 10
350 0 0 0 1 1 1 2 3 5 7 9
400 0 0 0 0 1 1 1 3 5 6 8
500 0 0 0 0 1 1 1 3 4 5 7
600 0 0 0 0 0 1 1 1 3 4 6
700 0 0 0 0 0 1 1 1 3 4 5
750 0 0 0 0 0 1 1 1 2 3 5
900 0 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 0 0 1 1 1 3 4
THHN, THWN, THWN-2 8
6 1 3 4 7 11 16 29 43 62 85 111
4 1 1 3 4 7 10 18 27 38 52 69
2 0 1 1 3 5 7 13 19 28 38 49
1 0 1 1 2 3 5 9 14 21 28 37
1/0 0 1 1 1 3 4 8 12 17 24 31
2/0 0 1 1 1 2 4 6 10 14 20 26
3/0 0 0 1 1 1 3 5 8 12 17 22
4/0 0 0 1 1 1 2 4 7 10 14 18
250 0 0 1 1 1 1 3 5 8 11 14
300 0 0 0 1 1 1 3 5 7 9 12
350 0 0 0 1 1 1 3 4 6 8 10
400 0 0 0 1 1 1 2 3 5 7 9
500 0 0 0 0 1 1 1 3 4 6 8
600 0 0 0 0 1 1 1 2 3 5 6
700 0 0 0 0 0 1 1 1 3 4 6
750 0 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 0 0 1 1 1 3 4
XHHW, XHHW-2 8 1 3 5 8 13 19 33 50 71 97 127
6 1 2 4 6 9 14 24 37 53 72 95
4 1 1 3 4 7 10 18 27 38 52 69
2 0 1 1 3 5 7 13 19 28 38 49
1 0 1 1 2 3 5 9 14 21 28 37
1/0 0 1 1 1 3 4 8 12 17 24 31
2/0 0 1 1 1 2 4 7 10 15 20 26
3/0 0 0 1 1 1 3 5 8 12 17 22
4/0 0 0 1 1 1 2 4 7 10 14 18
250 0 0 1 1 1 1 4 5 8 11 14
300 0 0 0 1 1 1 3 5 7 9 12
350 0 0 0 1 1 1 3 4 6 8 11
400 0 0 0 1 1 1 2 4 5 7 10
500 0 0 0 0 1 1 1 3 4 6 8
600 0 0 0 0 1 1 1 2 3 5 6
700 0 0 0 0 0 1 1 1 3 4 6
750 0 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 0 1 1 1 2 3 4
Definition: Compact stranding is the result of a manufacturing process where the stranded conductor is compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

TABLE C.4 Maximum Number of Conductors or Fixture Wires in Intermediate Metal Conduit (IMC)(Based on Chapter 9: Table 1, Table 4, and Table 5)

Type Conductor Size (AWG/kcmil) Trade Size (Metric Designator)
3/8
(12)
1/2
(16)
3/4
(21)
1
(27)
11/4
(35)
11/2
(41)
2
(53)
21/2
(63)
3
(78)
31/2
(91)
4
(103)
5
(129)
6
(155)
CONDUCTORS
RHH, RHW, RHW-2 14 4 8 13 22 30 49 70 108 144 186
12 4 6 11 18 25 41 58 89 120 154
10 3 5 8 15 20 33 47 72 97 124
8 1 3 4 8 10 17 24 38 50 65
6 1 1 3 6 8 14 19 30 40 52
4 1 1 3 5 6 11 15 23 31 41
3 1 1 2 4 6 9 13 21 28 36
2 1 1 1 3 5 8 11 18 24 31
1 0 1 1 2 3 5 7 12 16 20
1/0 0 1 1 1 3 4 6 10 14 18
2/0 0 1 1 1 2 4 6 9 12 15
3/0 0 0 1 1 1 3 5 7 10 13
4/0 0 0 1 1 1 3 4 6 9 11
250 0 0 1 1 1 1 3 5 6 8
300 0 0 0 1 1 1 3 4 6 7
350 0 0 0 1 1 1 2 4 5 7
400 0 0 0 1 1 1 2 3 5 6
500 0 0 0 1 1 1 1 3 4 5
600 0 0 0 0 1 1 1 2 3 4
700 0 0 0 0 1 1 1 2 3 4
750 0 0 0 0 1 1 1 1 3 4
800 0 0 0 0 0 1 1 1 3 3
900 0 0 0 0 0 1 1 1 2 3
1000 0 0 0 0 0 1 1 1 2 3
1250 0 0 0 0 0 1 1 1 1 1
1500 0 0 0 0 0 0 1 1 1 1
1750 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 1 1 1 1
TW, THHW, THW, THW-2 14 10 17 27 47 64 104 147 228 304 392
12 7 13 21 36 49 80 113 175 234 301
10 5 9 15 27 36 59 84 130 174 224
8 3 5 8 15 20 33 47 72 97 124
RHH*, RHW*, RHW-2* 14 6 11 18 31 42 69 98 151 202 261
12 5 9 14 25 34 56 79 122 163 209
10 4 7 11 19 26 43 61 95 127 163
8 2 4 7 12 16 26 37 57 76 98
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2* 6 1 3 5 9 12 20 28 43 58 75
4 1 2 4 6 9 15 21 32 43 56
3 1 1 3 6 8 13 18 28 37 48
2 1 1 3 5 6 11 15 23 31 41
1 1 1 1 3 4 7 11 16 22 28
1/0 1 1 1 3 4 6 9 14 19 24
2/0 0 1 1 2 3 5 8 12 16 20
3/0 0 1 1 1 3 4 6 10 13 17
4/0 0 1 1 1 2 4 5 8 11 14
250 0 0 1 1 1 3 4 7 9 12
300 0 0 1 1 1 2 4 6 8 10
350 0 0 1 1 1 2 3 5 7 9
400 0 0 0 1 1 1 3 4 6 8
500 0 0 0 1 1 1 2 4 5 7
600 0 0 0 1 1 1 1 3 4 5
700 0 0 0 0 1 1 1 3 4 5
750 0 0 0 0 1 1 1 2 3 4
800 0 0 0 0 1 1 1 2 3 4
900 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 0 1 1 1 3 3
1250 0 0 0 0 0 1 1 1 1 3
1500 0 0 0 0 0 1 1 1 1 2
1750 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 1 1 1 1
THHN, THWN, THWN-2 14 14 24 39 68 91 149 211 326 436 562
12 10 17 29 49 67 109 154 238 318 410
10 6 11 18 31 42 69 97 150 200 258
8 3 6 10 18 24 39 56 86 115 149
6 2 4 7 13 17 28 40 62 83 107
4 1 3 4 8 11 17 25 38 51 66
3 1 2 4 6 9 15 21 32 43 56
2 1 1 3 5 7 12 17 27 36 47
1 1 1 2 4 5 9 13 20 27 35
1/0 1 1 1 3 4 8 11 17 23 29
2/0 1 1 1 3 4 6 9 14 19 24
3/0 0 1 1 2 3 5 7 12 16 20
4/0 0 1 1 1 2 4 6 9 13 17
250 0 0 1 1 1 3 5 8 10 13
300 0 0 1 1 1 3 4 7 9 12
350 0 0 1 1 1 2 4 6 8 10
400 0 0 1 1 1 2 3 5 7 9
500 0 0 0 1 1 1 3 4 6 7
600 0 0 0 1 1 1 2 3 5 6
700 0 0 0 1 1 1 1 3 4 5
750 0 0 0 1 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 1 1 1 2 3 4
FEP, FEPB, PFA, PFAH, TFE 14 13 23 38 66 89 145 205 317 423 545
12 10 17 28 48 65 106 150 231 309 398
10 7 12 20 34 46 76 107 166 221 285
8 4 7 11 19 26 43 61 95 127 163
6 3 5 8 14 19 31 44 67 90 116
4 1 3 5 10 13 21 30 47 63 81
3 1 3 4 8 11 18 25 39 52 68
2 1 2 4 6 9 15 21 32 43 56
PFA, PFAH, TFE 1 1 1 2 4 6 10 14 22 30 39
PFA, PFAH, TFE, Z 1/0 1 1 1 4 5 8 12 19 25 32
2/0 1 1 1 3 4 7 10 15 21 27
3/0 0 1 1 2 3 6 8 13 17 22
4/0 0 1 1 1 3 5 7 10 14 18
Z 14 16 28 46 79 107 175 247 381 510 657
12 11 20 32 56 76 124 175 271 362 466
10 7 12 20 34 46 76 107 166 221 285
8 4 7 12 22 29 48 68 105 140 180
6 3 5 9 15 20 33 47 73 98 127
4 1 3 6 10 14 23 33 50 67 87
3 1 2 4 7 10 17 24 37 49 63
2 1 1 3 6 8 14 20 30 41 53
1 1 1 3 5 7 11 16 25 33 43
XHHW, ZW, XHHW-2, XHH 14 10 17 27 47 64 104 147 228 304 392
12 7 13 21 36 49 80 113 175 234 301
10 5 9 15 27 36 59 84 130 174 224
8 3 5 8 15 20 33 47 72 97 124
6 1 4 6 11 15 24 35 53 71 92
4 1 3 4 8 11 18 25 39 52 67
3 1 2 4 7 9 15 21 33 44 56
2 1 1 3 5 7 12 18 27 37 47
XHHW, XHHW-2, XHH 1 1 1 2 4 6 9 13 20 27 35
1/0 1 1 1 3 5 8 11 17 23 30
2/0 1 1 1 3 4 6 9 14 19 25
3/0 0 1 1 2 3 5 7 12 16 20
4/0 0 1 1 1 2 4 6 10 13 17
250 0 0 1 1 1 3 5 8 11 14
300 0 0 1 1 1 3 4 7 9 12
350 0 0 1 1 1 3 4 6 8 10
400 0 0 1 1 1 2 3 5 7 9
500 0 0 0 1 1 1 3 4 6 8
600 0 0 0 1 1 1 2 3 5 6
700 0 0 0 1 1 1 1 3 4 5
750 0 0 0 1 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 1 1 1 2 3 4
1250 0 0 0 0 0 1 1 1 2 3
1500 0 0 0 0 0 1 1 1 1 2
1750 0 0 0 0 0 1 1 1 1 2
2000 0 0 0 0 0 0 1 1 1 1
FIXTURE WIRES
RFH-2, FFH-2, RFHH-2 18 9 16 26 45 61 100 141 218 292 376
16 8 13 22 38 51 84 119 184 246 317
SF-2, SFF-2 18 12 20 33 57 77 126 178 275 368 474
16 10 17 27 47 64 104 147 228 304 392
14 8 13 22 38 51 84 119 184 246 317
SF-1, SFF-1 18 21 36 59 101 137 223 316 487 651 839
RFH-1, TF, TFF, XF, XFF 18 15 26 43 75 101 165 233 360 481 619
16 12 21 35 60 81 133 188 290 388 500
XF, XFF 14 10 17 27 47 64 104 147 228 304 392
TFN, TFFN 18 25 42 69 119 162 264 373 576 769 991
16 19 32 53 91 123 201 285 440 588 757
PF, PFF, PGF, PGFF, PAF, PTF, PTFF, PAFF 18 23 40 66 113 153 250 354 546 730 940
16 18 31 51 88 118 193 274 422 564 727
14 13 23 38 66 89 145 205 317 423 545
ZF, ZFF, ZHF 18 30 52 85 146 197 322 456 704 941 1211
16 22 38 63 108 146 238 336 519 694 894
14 16 28 46 79 107 175 247 381 510 657
KF-2, KFF-2 18 45 78 128 219 296 484 684 1056 1411 1817
16 32 54 89 153 207 337 477 737 984 1268
14 21 36 60 103 139 227 321 495 661 852
12 15 25 41 71 96 158 223 344 460 592
10 10 17 27 47 64 104 147 228 304 392
KF-1, KFF-1 18 52 90 147 253 342 558 790 1218 1628 2097
16 37 63 103 178 240 392 555 856 1144 1473
14 25 42 69 119 162 264 373 576 769 991
12 16 28 46 79 107 175 247 381 510 657
10 10 18 30 52 70 114 161 249 333 429
XF, XFF 12 5 9 14 25 34 56 79 122 163 209
10 4 7 11 19 26 43 61 95 127 163
Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.4(A) should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation, which has much larger diameters than other RHH wires. Consult manufacturer's conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

Table C.4(A) Maximum Number of Conductors or Fixture Wires in Intermediate Metal Conduit (IMC)
(Based on Chapter 9: Table 1, Table 4, and Table 5A)

Type Conductor Size (AWG/kcmil) Trade Size (Metric Designator)
3/8
(12)
1/2
(16)
3/4
(21)
1
(27)
11/4
(35)
11/2
(41)
2
(53)
21/2
(63)
3
(78)
31/2
(91)
4
(103)
5
(129)
6
(155)
COMPACT CONDUCTORS
THW, THW-2, THHW 8 2 4 7 13 17 28 40 62 83 107
6 1 3 6 10 13 22 31 48 64 82
4 1 2 4 7 10 16 23 36 48 62
2 1 1 3 5 7 12 17 26 35 45
1 1 1 1 4 5 8 12 18 25 32
1/0 1 1 1 3 4 7 10 16 21 27
2/0 0 1 1 3 4 6 9 13 18 23
3/0 0 1 1 2 3 5 7 11 15 20
4/0 0 1 1 1 2 4 6 9 13 16
250 0 0 1 1 1 3 5 7 10 13
300 0 0 1 1 1 3 4 6 9 11
350 0 0 1 1 1 2 4 6 8 10
400 0 0 1 1 1 2 3 5 7 9
500 0 0 0 1 1 1 3 4 6 8
600 0 0 0 1 1 1 2 3 5 6
700 0 0 0 1 1 1 1 3 4 5
750 0 0 0 1 1 1 1 3 4 5
900 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 1 1 1 2 3