Adopting agency | BSC | BSC-CG | SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||
1 | 2 | 1/AC | AC | SS | SS/CC | 1 | 2 | 3 | 4 | ||||||||||||
Adopt entire chapter | X | ||||||||||||||||||||
Adopt entire chapter as amended (amended sections listed below) | |||||||||||||||||||||
Adopt only those sections that are listed below | |||||||||||||||||||||
Chapter / Section | |||||||||||||||||||||
The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures for applications listed in Sections 1.10.1 [OSHPD 1] regulated by the Office of Statewide Health Planning and Development (OSHPD).
SFM and DSA-AC requirements for existing structures shall be enforced by the Office of Statewide Health Planning and Development (OSHPD).
[DSA-AC] For applications listed in Section 1.9.1 regulated by the Division of the State Architect-Access Compliance for accessibility requirements, see Chapter 11B.
The additions, alterations and repairs shall follow one of the three procedures listed below:
- Provisions in Sections 3403A, 3404A and 3405A; or
- Nonconforming buildings provisions in Section 3411A; or
- Performance based or prescriptive provisions in Section 3412A.
Items 1 through 3 above shall not be applied in combination with each other, except when explicitly permitted.
The services/systems, utilities and means of egress shall satisfy requirements in Sections 3416A and 3417A.
Buildings and structures, and parts thereof, shall be maintained in a safe and sanitary condition. Devices or safeguards which are required by this code shall be maintained in conformance with the code edition under which installed. The owner or the owner's designated agent shall be responsible for the maintenance of buildings and structures. To determine compliance with this subsection, the building official shall have the authority to require a building or structure to be reinspected. The requirements of this chapter shall not provide the basis for removal or abrogation of fire protection and safety systems and devices in existing structures.
Alterations, repairs, additions and changes of occupancy to, or relocation of, existing buildings and structures shall comply with the provisions for alterations, repairs, additions and changes of occupancy or relocation, respectively, in the California Energy Code, California Fire Code, California Mechanical Code, California Plumbing Code and California Electrical Code, California Residential Code and NFPA 70. Where provisions of the other codes conflict with provisions of this chapter, the provisions of this chapter shall take precedence.
Building materials, equipment, and systems shall comply with the requirements of this section.
Materials and equipment already in use in a building in compliance with requirements or approvals in effect at the time of their erection or installation shall be permitted to remain in use unless determined by the building official to be unsafe in accordance with Section 116.
Except as otherwise required or permitted by this code, materials and equipment permitted by the applicable code for new construction shall be used. Like materials shall be permitted for repairs and alterations, provided no hazard to life, health or property is created. Hazardous materials shall not be used where the code for new construction would not permit their use in buildings of similar occupancy, purpose and location.
Where the existing seismic force-resisting system is a type that can be designated ordinary or is a welded steel moment frame constructed under a permit issued prior to October 25, 1994, values of R, Ω0, and Cd for the existing seismic force-resisting system shall be those specified by this code for an ordinary system unless it is demonstrated that the existing system will provide performance equivalent to that of a detailed, intermediate or special system.
The building official shall have the authority to require the elimination of conditions deemed dangerous.
The following words and terms shall, for the purposes of this chapter and as used elsewhere in the code, have the meanings shown herein. Definitions provided in Section 1613A.2, ASCE 7 Section 11.2 and ASCE 41 shall apply when appropriate in addition to terms defined in this section:
CHANGE IN FUNCTION. See Section 1224.3.
EXISTING STRUCTURE. A structure that has a valid certificate of occupancy issued by the building official.
GENERAL ACUTE CARE HOSPITAL. See Section 1224.3.
NONSTRUCTURAL ALTERATION is any alteration which neither affects existing structural elements nor requires new structural elements for vertical or lateral support and which does not increase the lateral shear force in any story by more than 5 percent.
PEER REVIEW refers to procedure contained in Section 3414A.
REPAIR as used in this chapter means all the design and construction work affecting existing or requiring new structural elements undertaken to restore or enhance the structural and nonstructural load resisting system participating in vertical or lateral response of a structure primarily intended to correct the effects of deterioration or impending or actual failure, regardless of cause.
SPC SEISMIC SEPARATION. Means a building separation in accordance with the California Administrative Code, Chapter 6 Section 3.4.
UNREINFORCED MASONRY as used in this chapter means masonry construction where reinforcements in any direction is less than minimum reinforcement specified in TMS 402 Section 7.3.2.6.
UNREINFORCED CONCRETE as used in this chapter means plain concrete as defined in ACI 318 Section 2.3.
VOLUNTARY STRUCTURAL ALTERATION is any alteration of existing structural element or provision of new structural elements which is not necessary for vertical or lateral support of other work and is initiated by the applicant primarily for the purpose of increasing the vertical or lateral load-carrying strength or stiffness of an existing building.
Additions to any building or structure shall comply with the requirements of this code for new construction. Alterations to the existing building or structure shall be made to ensure that the existing building or structure together with the addition are no less conforming with the provisions of this code than the existing building or structure was prior to the addition. An existing building together with its additions shall comply with the height and area provisions of Chapter 5.
For buildings and structures in flood hazard areas established in Section 1612A.3, any addition that constitutes substantial improvement of the existing structure, as defined in Section 202, shall comply with the flood design requirements for new construction, and all aspects of the existing structure shall be brought into compliance with the requirements for new construction for flood design.
For buildings and structures in flood hazard areas established in Section 1612A.3, any additions that do not constitute substantial improvement of the existing structure, as defined in Section 202, are not required to comply with the flood design requirements for new construction.
Any existing gravity load-carrying structural element for which an addition and its related alterations cause an increase in design gravity load of more than 5 percent shall be strengthened, supplemented, replaced or otherwise altered as needed to carry the increased load required by this code for new structures. Any existing gravity load-carrying structural element whose gravity load-carrying capacity is decreased shall be considered an altered element subject to the requirements of Section 3404A.3. Any existing element that will form part of the lateral load path for any part of the addition shall be considered an existing lateral load-carrying structural element subject to the requirements of Section 3403A.4.
Where the addition does not result in increased design live load, existing gravity load-carrying structural elements shall be permitted to be evaluated and designed for live loads approved prior to the addition. If the approved live load is less than that required by Section 1607A, the area designed for the non-conforming live load shall be posted with placards of approved design indicating the approved live load. Where the addition does result in increased design live load, the live load required by Section 1607A shall be used.
Where the addition is structurally independent of the existing structure, existing lateral load-carrying structural elements shall be permitted to remain unaltered. Where the addition is not structurally independent of the existing structure, the existing structure and its addition acting together as a single structure shall be shown to meet the requirements of Sections 1609A and 1613A.
Exceptions. For incidental and minor additions:
- Any existing lateral load-carrying structural element whose demand-capacity ratio with the addition considered is no more than 10 percent greater than its demand-capacity ratio with the addition ignored shall be permitted to remain unaltered. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations with design lateral loads or forces in accordance with Sections 1609A and 1613A. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces and capacities shall account for the cumulative effects of additions and alterations since original construction.
- Drift limits based on original design code shall be permitted to be used in lieu of the drift limits required by ASCE 7.
Where an addition is made to a building or structure of a Group R or I-1 occupancy, the existing building shall be provided with smoke alarms in accordance with Section 1103A.8 of the California Fire Code.
Except as provided by this section, alterations to any building or structure shall comply with the requirements of the code for new construction. Alterations shall be such that the existing building or structure is no less complying with the provisions of this code than the existing building or structure was prior to the alteration.
Exceptions:
- An existing stairway shall not be required to comply with the requirements of Section 1009 where the existing space and construction does not allow a reduction in pitch or slope.
- Handrails otherwise required to comply with Section 1009.15 shall not be required to comply with the requirements of Section 1012.6 regarding full extension of the handrails where such extensions would be hazardous due to plan configuration.
For buildings and structures in flood hazard areas established in Section 1612A.3, any alteration that constitutes substantial improvement of the existing structure, as defined in Section 202, shall comply with the flood design requirements for new construction, and all aspects of the existing structure shall be brought into compliance with the requirements for new construction for flood design.
For buildings and structures in flood hazard areas established in Section 1612A.3, any alterations that do not constitute substantial improvement of the existing structure, as defined in Section 202, are not required to comply with the flood design requirements for new construction.
Any existing gravity load-carrying structural element for which an alteration causes an increase in design gravity load of more than 5 percent shall be strengthened, supplemented, replaced or otherwise altered as needed to carry the increased gravity load required by this code for new structures. Any existing gravity load-carrying structural element whose gravity load-carrying capacity is decreased as part of the alteration shall be shown to have the capacity to resist the applicable design gravity loads required by this code for new structures.
Where the alteration does not result in increased design live load, existing gravity load-carrying structural elements shall be permitted to be evaluated and designed for live loads approved prior to the alteration. If the approved live load is less than that required by Section 1607A, the area designed for the non-conforming live load shall be posted with placards of approved design indicating the approved live load. Where the alteration does result in increased design live load, the live load required by Section 1607A shall be used.
Except as permitted by Section 3404A.5, where the alteration increases design lateral loads in accordance with Section 1609A or 1613A, or where the alteration results in a prohibited structural irregularity as defined in this code, or where the alteration decreases the capacity of any existing lateral load-carrying structural element, the structure of the altered building or structure shall be shown to meet the requirements of Sections 1609A and 1613A.
Exceptions. For incidental and minor alterations:
- Any existing lateral load-carrying structural element whose demand-capacity ratio with the alteration considered is no more than 10 percent greater than its demand-capacity ratio with the alteration ignored shall be permitted to remain unaltered. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations with design lateral loads or forces per Sections 1609A and 1613A. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces, and capacities shall account for the cumulative effects of additions and alterations since original construction.
- Drift limits based on original design code shall be permitted to be used in lieu of the drift limits required by ASCE 7.
Alterations to existing structural elements or additions of new structural elements that are not otherwise required by this chapter and are initiated for the purpose of improving the performance of the seismic force-resisting system of an existing structure or the performance of seismic bracing or anchorage of existing nonstructural elements shall be permitted, provided that an engineering analysis is submitted demonstrating the following:
- The altered structure, and the altered structural and nonstructural elements are no less in compliance with the provisions of this code with respect to earthquake design than they were prior to the alteration.
- New structural elements are designed, detailed and connected to the existing structural elements as required by Chapter 16A. Alterations of existing structural elements shall be based on design demand required by Chapter 16A. Demands for new or altered existing structural elements need not exceed the maximum load effect that can be transferred to the elements by the system.
- New, relocated or altered nonstructural elements are designed, detailed and connected to existing or new structural elements as required by Chapter 16A.
- The alterations do not create a structural irregularity as defined in ASCE 7 or make an existing structural irregularity more severe.
Individual sleeping units and individual dwelling units in Group R and I-1 occupancies shall be provided with smoke alarms in accordance with Section 1103A.8 of the California Fire Code.
Buildings and structures, and parts thereof, shall be repaired in compliance with Section 3405A and 3401A.2. Work on nondamaged components that is necessary for the required repair of damaged components shall be considered part of the repair and shall not be subject to the requirements for alterations in this chapter. Routine maintenance required by Section 3401A.2, ordinary repairs exempt from permit in accordance with Section 105.2, and abatement of wear due to normal service conditions shall not be subject to the requirements for repairs in this section.
A building that has sustained substantial structural damage to the vertical elements of its lateral force-resisting system shall be evaluated and repaired in accordance with the applicable provisions of Sections 3405A.2.1 through 3405A.2.3.
The building shall be evaluated by a registered design professional, and the evaluation findings shall be submitted to the building official. The evaluation shall establish whether the damaged building, if repaired to its pre-damage state, would comply with the provisions of this code for wind and earthquake loads.
Wind loads for this evaluation shall be those prescribed in Section 1609A. Earthquake loads for this evaluation, if required, shall be permitted to be 75 percent of those prescribed in Section 1613A.
If the evaluation establishes compliance of the pre-damage building in accordance with Section 3405A.2.1, then repairs shall be permitted that restore the building to its pre-damage state.
If the evaluation does not establish compliance of the predamage building in accordance with Section 3405A.2.1, then the building shall be rehabilitated to comply with applicable provisions of this code for load combinations, including wind or seismic loads. The wind loads for the repair shall be as required by the building code in effect at the time of original construction, unless the damage was caused by wind, in which case the wind loads shall be as required by the code in effect at the time of original construction or as required by this code. Earthquake loads for this rehabilitation design shall be those required for the design of the predamage building, but not less than ninety percent of those prescribed in Section 1613A. New structural members and connections required by this rehabilitation design shall comply with the detailing provisions of this code for new buildings of similar structure, purpose and location.
Gravity load-carrying components that have sustained substantial structural damage shall be rehabilitated to comply with the applicable provisions of this code for dead and live loads. Snow loads shall be considered if the substantial structural damage was caused by or related to snow load effects. Existing gravity load-carrying structural elements shall be permitted to be designed for live loads approved prior to the damage. If the approved live load is less than that required by Section 1607A, the area designed for the nonconforming live load shall be posted with placards of approved design, indicating the approved live load. Nondamaged gravity load-carrying components that receive dead, live or snow loads from rehabilitated components shall also be rehabilitated or shown to have the capacity to carry the design loads of the rehabilitation design. New structural members and connections required by this rehabilitation design shall comply with the detailing provisions of this code for new buildings of similar structure, purpose and location.
Regardless of the level of damage to vertical elements of the lateral force-resisting system, if substantial structural damage to gravity load-carrying components was caused primarily by wind or earthquake effects, then the building shall be evaluated in accordance with Section 3405A.2.1 and, if noncompliant, rehabilitated in accordance with Section 3405A.2.3.
For damage less than substantial structural damage, repairs shall be allowed that restore the building to its pre-damage state. New structural members and connections used for this repair shall comply with the detailing provisions of this code for new buildings of similar structure, purpose and location.
For buildings and structures in flood hazard areas established in Section 1612A.3, any repair that constitutes substantial improvement of the existing structure, as defined in Section 202, shall comply with the flood design requirements for new construction, and all aspects of the existing structure shall be brought into compliance with the requirements for new construction for flood design.
For buildings and structures in flood hazard areas established in Section 1612A.3, any repairs that do not constitute substantial improvement or repair of substantial damage of the existing structure, as defined in Section 202, are not required to comply with the flood design requirements for new construction.
The installation or replacement of glass shall be as required for new installations.
No change shall be made in the use or occupancy of any building that would place the building in a different division of the same group of occupancies or in a different group of occupancies, unless such building is made to comply with the requirements of this code for the use or occupancy. Subject to the approval of the building official, the use or occupancy of existing buildings shall be permitted to be changed and the building is allowed to be occupied for purposes in other groups without conforming to all the requirements of this code for those groups, provided the new or proposed use is less hazardous, based on life and fire risk, than the existing use.
A change in function shall require compliance with all the functional requirements for new construction in this code, including requirements in Sections 1224, 1225, 1226, and 1227.
A certificate of occupancy shall be issued where it has been determined that the requirements for the new occupancy classification have been met.
An existing stairway shall not be required to comply with the requirements of Section 1009 where the existing space and construction does not allow a reduction in pitch or slope.
When a change of occupancy results in a structure being reclassified to a higher risk category, the structure shall conform to the seismic requirements for a new structure of the higher risk category.
Exception: Specific seismic detailing requirements of Section 1613A for a new structure shall not be required to be met where the seismic performance is shown to be equivalent to that of a new structure. A demonstration of equivalence shall consider the regularity, overstrength, redundancy and ductility of the structure.
Structures moved into or within the jurisdiction shall comply with the provisions of this code for new structures.
Provisions of this section shall apply to hospital buildings which were originally designed to pre- 1973 building code and not designated as SPC 3 or higher in accordance with Chapter 6 of the California Administrative Code.
Incidental and minor structural additions shall be permitted provided the additions meet this code for new construction using importance factor, Ie, equal to or greater than 1.0. Alterations or repairs to the existing affected lateral force-resisting systems shall be made to conform to the requirements of Sections 3404A or 3405A respectively using importance factor, Ie, equal to or greater than 1.0.
Component importance factor, Ip, shall be permitted to be 1.0.
Exception: Components required for life-safety purposes after an earthquake, including emergency and standby power systems, mechanical smoke removal systems, fire protection sprinkler systems, fire alarm control panels, and egress stairways shall have a component importance factor (Ip) of 1.5.
Major structural alterations, additions or repairs shall be in accordance with Sections 3412A.1.1.a or 3412A.1.1.c, as applicable.
Except for the modifications as set forth in Sections 3412A and 3413A all additions, alterations, repairs and seismic retrofit to existing structures or portions thereof shall be permitted to be designed in accordance with the provisions of ASCE 41. When load combinations which do not include seismic forces are required, the new building code provisions of this code shall be applicable.
Target building performance level shall be as follows:
For general acute care hospital buildings along with all structures required for their continuous operation or access/egress.
- Immediate Occupancy (IO) Structural Performance Level (S-1) as defined in Section 2.3.1.1 at Basic Safety Earthquake 1N (BSE-1N) Seismic Hazard Level; and
- Life Safety (LS) Structural performance level (S-3) as defined in Section 2.3.1.3 at Basic Safety Earthquake 2N (BSE-2N) Seismic Hazard Level;
The nonstructural components shall satisfy the requirements of this code for new construction.
Exception: Performance objectives for upgrading nonconforming hospital buildings to SPC-4D and for incidental or minor alterations or repairs of SPC-4D buildings shall be in accordance with Section 3412A.2.3.2 of this code.
For incidental and minor additions, alterations or repairs of pre-1973 hospital buildings which will not be used for general acute care services after January 1, 2030:
- Life Safety Structural Performance (S-3) Level as defined in ASCE 41 Section 2.3.1.3 at the Basic Safety Earthquake 1E (BSE-1E) Seismic Hazard Level; and
- Collapse Prevention (CP) building performance level (5-D) in accordance with Section 2.3.3.4 at the Basic Safety Earthquake 2E (BSE-2E) Seismic Hazard Level; and
- The nonstructural components shall satisfy the requirements of Position Retention Nonstructural Performance Level (N-B) in accordance with ASCE 41 Section 2.3.2.2 at BSE-1E Seismic Hazard Level.
All other hospital buildings:
- Operational Building Performance Level of (1-A) as defined in Section 2.3.3.1 at Basic Safety Earthquake 1N (BSE-1N) Seismic Hazard Level;
- Life Safety (LS) building performance level (S-3) as defined in Section 2.3.1.3 at Basic Safety Earthquake 2N (BSE-2N) Seismic Hazard Level.
Use of material properties based on historical information as default values shall not be permitted.
The selection of a particular analysis procedure from ASCE 41 shall be subject to the approval of the enforcement agency.
Prior to implementation of ASCE 41 Nonlinear Dynamic Procedure, the ground motion, analysis and design methods, material assumptions and acceptance criteria proposed by the engineer shall be reviewed by the enforcement agency.
Where analysis/modeling parameters or acceptance criteria for structural elements are not provided in ASCE 41 or are considered to be inadequate, the analysis/modeling parameters or acceptance criteria shall be permitted to be established on the basis of test, using a criteria acceptable to the building official, and ASCE 41 Section 7.6.3.
Construction, testing, inspection and structural observation requirements shall be as required for new construction.
Not withstanding any other requirements of this code, existing general acute care hospitals shall comply with the seismic evaluation requirements specified in Chapter 6, of the California Administrative Code, when applicable. Seismic retrofit to comply with requirements specified in Chapter 6 of the California Administrative Code shall be permitted to be in accordance with this section. When load combinations that do not include seismic forces are required, the new building provisions of this code shall be applicable.
New hospitals (facility) or new building(s), larger than 4000 sq ft, designed and built to the requirements of this code for general acute care hospital buildings shall be considered to satisfy the requirements of SPC 5 and NPC 5.
Structures shall be considered to comply with SPC 5 requirements of Table 2.5.3, Chapter 6 of the California Administrative Code where all of the following are satisfied:
- Immediate Occupancy structural performance level (S-1) in accordance with Section 2.3.1.1 of ASCE 41 at BSE-1N;
- Life Safety performance level S-3 in accordance with Section 2.3.1.3 of ASCE 41 at BSE-2N; and
- Items identified in Chapter 6, Article 10 of the California Administrative Code, satisfying the requirements of Operational Nonstructural performance level (N-A) in accordance with Section 2.3.2.1 of ASCE 41 at BSE-1N.
Nonconforming hospital buildings satisfying the following requirements and one of Sections 3412A.2.3.1, 3412A.2.3.2 or 3412A.2.3.3, but not a combination thereof, shall be considered to satisfy the requirements of SPC-4D.
- Approval of construction documents based on building characterization in accordance with the California Administrative Code (CAC) Chapter 6 Section 2.1.2.1, material properties in accordance with the CAC Chapter 6 Section 2.1.2.2 and Section 3413A.1.3 of this code, and a complete rational structural analysis shall be required.
- Where the SPC-4D upgrade involves construction, a building permit prior to construction shall be required.
- Where multiple building permits are used to upgrade a building to SPC-4D, a complete rational structural analysis to justify compliance with SPC-4D for the building in its final configuration, shall be submitted as part of the construction documents submittal to the Office for the last project.
- Where the SPC-4D upgrade involves construction, buildings shall be assigned to SPC-4D after all projects required for SPC-4D are closed in compliance.
Nonconforming buildings shall satisfy the following requirements:
The California Building Code, 1980 (CBC 1980), as used in this chapter, consists of the Uniform Building Code, 1979 (UBC 1979) along with requirements contained in:
- California Code of Regulations, Title 24-Building Standards, dated February 2, 1980 (Revision record for Register 80, No. 5).
- California Code of Regulations, Title 22 — Social Security, dated October 13, 1979 (Revision Record for Register 79, No 41).
- California Code of Regulations, Title 17 — Public Health, dated October 13, 1979 (Revision Record for Register 79, No 41-B).
- All existing structural elements of Seismic Force Resisting System (SFRS) shall satisfy the detailing requirements in the CBC 1980 or demonstrate that the level of seismic performance is equivalent to that given in the CBC 1980, as determined by the building official.
- A continuous load path or paths with adequate strength and stiffness to transfer all the forces from the point of origin to final point of resistance shall be justified by analysis.
- Site data report in accordance with the CBC 1980 shall establish that seismically induced differential settlement does not exceed 1" in 40'.
- Adjacent buildings shall satisfy the SPC building separation requirements in accordance with the California Administrative Code, Chapter 6 Section 3.4.
The addition of new structural elements or strengthening of existing structural elements for retrofit of nonconforming buildings to SPC-4D shall comply with the following:
- The seismic demand (forces or displacements) shall be in accordance with the CBC 1980;
- Capacity, detailing and connections for new structural elements shall satisfy the requirements in this code (CBC 2016) for new construction; and
- The strengthening of existing structural elements shall use capacities determined in accordance with this code (CBC 2016) for new construction consistent with the detailing and connections used in the strengthened member.
- All construction, quality assurance and quality control shall be in accordance with the new construction provisions of this code (CBC 2016).
- Elements not part of the Seismic Force Resisting System (SFRS), including those identified in the California Administrative Code Chapter 6, Article 10, shall be evaluated using seismic forces and the requirements of the CBC 1980.
Any column or wall that forms part of two or more intersecting SFRS and is subjected to axial load due to seismic forces acting along either principal plan axis equaling or exceeding 20 percent of the axial design strength of the column or wall shall be evaluated for the most critical load effect due to application of seismic force in any direction. The most critical load effect may be deemed to be satisfied if members and their foundations are evaluated for 100 percent of the forces for one direction plus 30 percent of the forces for the perpendicular direction, whereby the combination produces the maximum effect.
Exceptions: The following buildings (with structural irregularities or unusual configuration/system) shall not be eligible for the SPC-4D upgrade using the prescriptive provisions in this section:
- Buildings with prohibited irregularities in accordance with Section 1616A.1.10 of this code.
- Buildings taller than 5-stories or 65' height above the base having horizontal or vertical irregularities in accordance with ASCE 7 Tables 12.3-1 Items # 1a, 1b and 3 or 12.3-2 Items #1a, 1b, 5a and 5b.
- Buildings with unusual configuration or structural system, as determined by the building official.
Structures shall be deemed to comply with the SPC-4D requirements of Table 2.5.3, Chapter 6 of the California Administrative Code, when all of the following are satisfied:
- Damage control structural performance level (S-2) in accordance with Section 2.3.1.2.1 of ASCE 41 at BSE-1E; and
- Collapse Prevention Structural Performance Level (S-5) in accordance with Section 2.3.1.5 of ASCE 41 at BSE-2E; and
- Items identified in Chapter 6, Article 10 of the California Administrative Code satisfy the requirements of Position Retention nonstructural performance level (N-B) in accordance with Section 2.3.2.2 at BSE-1E.
Structures satisfying the requirements of this code for new general acute care hospital buildings design shall be deemed to satisfy the SPC-4D requirements of Table 2.5.3, Chapter 6 of the California Administrative Code.
All existing structural elements of Seismic Force Resisting System (SFRS) shall satisfy the detailing requirements of this code for new construction or demonstrate that the level of seismic performance is equivalent, as determined by the building official. A demonstration of equivalence shall consider the regularity, overstrength, redundancy, and ductility of the structure.
Elements not part of the Seismic Force Resisting System (SFRS), including those identified in the California Administrative Code Chapter 6, Article 10, shall be evaluated using seismic forces and the requirements of this code for new general acute care hospital buildings.
Structures shall be considered to comply with SPC 2 requirements of Table 2.5.3, Chapter 6 of the California Administrative Code, when all of the following are satisfied:
- Life Safety structural performance level (S-3) in accordance with Section 2.3.1.3 of ASCE 41 at BSE-1E; and
- Items identified in Chapter 6, Article 10 of the California Administrative Code satisfying the requirements of Position Retention nonstructural performance level (N-B) in accordance with Section 2.3.2.2 at BSE-1E.
Nonstructural components for Operational Nonstructural performance level (N-A) in Section 2.3.2.1 or NPC-4 shall satisfy the requirements of this code for new construction. Nonstructural components for NPC-5 shall satisfy Operational performance level N-A/NPC-4 and Section 1616A.1.40 Items 1 & 2 of this code.
Operational Nonstructural performance level (N-A) and Position Retention nonstructural performance level (N-B) of ASCE 41 at BSE-1N shall be considered equivalent to NPC 3/NPC 2 and NPC 3R requirements respectively of Table 11.1, Chapter 6, of the California Administrative Code. For NPC 3/NPC 3R/NPC 2, only components listed in Table 11.1, Chapter 6, of the California Administrative Code for NPC 3/NPC 3R/NPC 2 need to satisfy the requirements specified above.
Exceptions:
- Evaluation procedure of Article 11, Chapter 6, of the California Administrative Code shall be used for seismic evaluation of NPC 2, NPC 3/NPC 3R, NPC 4 and NPC 5, where specific procedure is not outlined in ASCE 41. Administrative and permitting provisions outlined in Article 11, Chapter 6, of the California Administrative Code shall apply.
- Supports and attachments of nonstructural components, except those listed in Item 4 below, in buildings in seismic performance categories SPC 1 and SPC 2 with a performance level of NPC 3R shall be permitted to comply with the provisions of Section 1630A of the 1995 California Building Code using an importance factor Ip =1.0. The capacity of welds, anchors and fasteners shall be determined in accordance with requirements of this code.
- Supports and attachments of nonstructural components, except those listed in Item 4 below, in buildings in seismic performance categories SPC 1 or SPC 2 with a performance level of NPC 3 or higher, and SPC 3, SPC 4 or SPC-4D, shall be permitted to comply with the provisions of Section 1630B of the 1998 California Building Code using an importance factor Ip =1.5. The capacity of welds, anchors and fasteners shall be determined in accordance with requirements of this code.
- Supports and attachments for systems listed under NPC-2 and NPC-5 (excluding those specifically listed for NPC-3/NPC-3R and NPC-4) in the California Administrative Code, Chapter 6, Table 11.1 shall satisfy the requirements of this code for new construction and Items 2 and 3 above shall not be applicable.
For NPC 3R, the adequacy of load path for nonstructural elements need only be verified when the total reaction at the point of support (including the application of Fp) exceeds the following limits:
- 250 pounds for components or equipment attached to light frame walls. For the purposes of this requirement, the sum of the absolute value of all reactions due to component loads on a single stud shall not exceed 250 pounds.
- 1,000 pounds for components or equipment attached to roofs, or walls of reinforced concrete or masonry construction.
2,000 pounds for components or equipment attached to floors or slabs-on-grade.
Exception: If the anchorage or bracing is configured in a manner that results in significant torsion on a supporting structural element, the effects of the nonstructural reaction force on the structural element shall be considered in the anchorage design.
The text of ASCE 41 shall be modified as indicated in Sections 3413A.1.1 through 3413A.1.14.
Modify ASCE 41 Section 1.1 with the following:
Seismic evaluations shall be performed for performance objective specified in Section 3412A of this code (CBC) using procedure of this standard (ASCE 41) as follows:
- Structural components shall be evaluated in accordance with Tier 3 systematic evaluations procedure in Chapter 6.
- Nonstructural components shall be evaluated in accordance with Chapter 13.
Exception: For general acute care hospitals, seismic evaluation shall be permitted to be in accordance with Chapter 6 of the California Administrative Code (CAC) when required by provisions of that chapter.
Modify ASCE 41 Section 2.4 by the following:
Response spectra and acceleration time histories shall be constructed in accordance with Sections 1613A, 1616A, and 1803A.6.
Modify ASCE 41 Section 6.2 with the following:
Data Collection Requirements. The extent of data collection shall be at Comprehensive level for all structures, including structures upgraded to SPC-4D. A testing program for materials properties shall be approved by the enforcement agent prior to commencement of material testing work. Previously approved material test results shall be permitted to be used to satisfy part of the comprehensive data collection requirements.
Exception: Data collection at Usual level shall be permitted for structures with SPC-2 or lower target performance objective.
Tension testing of reinforcing bars shall be in accordance with ASTM A370 Annex A9. All test specimens shall be the full section of the bar as rolled (8-in. gage length) and shall not be reduced.
At test sample locations, structural members, slabs and walls shall be repaired to a state that is equivalent to their original condition.
For buildings built under an OSHPD permit based on the 1976 or later edition of the CBC, where materials properties are shown on design drawings and original materials test data are available, no materials testing shall be required when approved by the enforcement agent.
Modify ASCE 41 Section 7.3.2.1 with the following:
Nonlinear Static Procedure. If higher mode effects are significant and building is taller than 75 feet above the base, the Nonlinear Dynamic Procedure shall be used.
Modify ASCE 41 Section 7.5.1 with the following:
Acceptance Criteria — Drift Limitations. The interstory drift ratio shall not exceed the drift limits for Risk Category IV buildings in ASCE 7 Table 12.12-1 due to forces corresponding to BSE-1E or BSE-1N, as applicable.
Exception: Larger interstory drift ratios shall be permitted where justified by rational analysis that both structural and nonstructural elements can tolerate such drift and approved by the enforcement agent.
Modify ASCE 41 Section 7.5.1.4 by the following:
Material Properties. Expected material properties are not permitted to be determined by multiplying lower bound values by the assumed factors specified in Chapters 8 through 12 and shall be based exclusively on materials tests.
Modify ASCE 41 Section 8.4 with the following:
Foundation Strength and Stiffness. Foundation and soil strength shall be used to evaluate potential overturning, uplift and sliding for fixed base assumptions, and stiffness for flexible base assumptions, including deformations associated with those actions.
Replace ASCE 41 Section 8.4.1.1 as follows:
Prescriptive Expected Capacities. Not permitted by OSHPD.
Modify ASCE 41 Section 8.5 with the following:
The product of RRSbsa x RRSe, shall not be less than 0.7.
The combined effect of kinematic interaction and foundation damping shall meet the following:
- The site specific response spectrum modified for soil-structure interaction effects shall not be taken as less than 80 percent of the spectral acceleration as determined from a site-specific response spectrum in accordance with ASCE 7 Section 21.3, or
The site specific response spectrum modified for soil-structure interaction effects shall not be taken as less than 70 percent of the spectral acceleration as determined from the design response spectrum and MCER response spectrum in accordance and with ASCE 7 Sections 11.4.5 and 11.4.6 respectively.
Exception: For the seismic retrofit of existing nonconforming buildings, design ground motion shall be consistent with performance objectives in Section 3412A.
Modify ASCE 41 Section 8.6 with the following:
Seismic Earth Pressure. Where the grade difference from one side of the building to another exceeds one-half story height, the seismic increment of earth pressure shall be added to the gravity lateral earth pressure to evaluate the building overturning and sliding stability and the lateral force resisting system below grade in combination with the building seismic forces.
Modify ASCE 41 Section 10.7.1.1 with the following:
Monolithic Reinforced Concrete Shear Walls and Wall Segments. For nonlinear procedures, shear walls or wall segments with axial loads greater than 0.35 Po shall be included in the model as primary elements with appropriate strength and stiffness degrading properties assigned to those components subject to the approval of the enforcement agent. For linear procedures, the effects of deformation compatibility shall be investigated using moment-curvature section analyses and cyclic testing results of similar components to determine whether strengthening is necessary to maintain the gravity load carrying capacity of that component.
Horizontal wall segments or spandrels reinforced similar to vertical wall segments or piers shall be classified as wall segments, not shear wall coupling beams, in Tables 10-19 through 10-22.
Modify ASCE 41 Section 11.1 by the following:
Scope: Unreinforced Masonry walls (including unreinforced infill walls) and partitions are not permitted for General Acute Care (GAC) hospital buildings.
Modify ASCE 41 Section 14.1 by the following:
Scope: For buildings located in Seismic Design Category F, verification of the interstory lateral displacements, the strength adequacy of the seismic force resisting system and anchorage to the foundation shall be accomplished using the Nonlinear Dynamic Procedure.
Not permitted by OSHPD.
Independent peer review is an objective technical review by knowledgeable reviewer(s) experienced in structural design, analysis and performance issues involved. The reviewer(s) shall examine the available information on the condition of building, basic engineering concept employed and recommendations for action.
The independent reviewer (s) shall be selected prior to initiation of substantial portion of the design and analysis work that is to be reviewed, and review shall start as soon as practical and sufficient information defining the project is available.
The reviewer shall be independent from the design and construction team.
The reviewer(s) shall have no other involvement in the project before, during or after the review, except in a review capacity.
The reviewer shall be selected and paid by owner and shall have technical expertise similar to the being reviewed, as determined by enforcement agent.
The reviewer (in case of review team, the chair) shall be a California-licensed structural engineer who is familiar with technical issues and regulations governing the work to be reviewed.
The reviewer shall serve through completion of the project and shall not be terminated except for failure to perform the duties specified herein. Such termination shall be in writing with copies to enforcement agent, owner, and the engineer of record. When a reviewer is terminated or resigns, a qualified replacement shall be appointed within 10 working days or a timeframe mutually agreed to by the Owner, Registered Design Professional (RDP) and the Office.
Review activities shall include, where appropriate, available construction documents, design criteria, observation of the condition of structure, all new and original inspection reports, including methods of sampling, analyses prepared by the engineer of record and consultants, and the retrofit or repair design. Review shall include consideration of the proposed design approach, method, materials and details.
The reviewer(s) shall prepare a written report to the owner and responsible enforcement agent that covers all aspect of the review performed including conclusions reached by the reviewer. Report shall be issued after the schematic phase, during design development, and at the completion of construction documents, but prior to their issuance of permit. Such report shall include, at the minimum, statement of the following.
- Scope of engineering design peer review with limitations defined.
- The status of the project documents at each review stage.
- Ability of selected materials and framing systems to meet the performance criteria with given loads and configuration.
- Degree of structural system redundancy and the deformation compatibility among structural and nonstructural elements.
- Basic constructability of the retrofit or repair system.
- Other recommendation that will be appropriate for the specific project.
- Presentation of the conclusions of the reviewer identifying any areas that need further review, investigation and/or clarification.
- Recommendations.
The engineer of record shall review the report from the reviewer(s) and shall develop corrective actions and other responses as appropriate. Changes observed during construction that affect the seismic-resisting system shall be reported to the reviewer in writing for review and recommendations. All reports, responses and corrective actions prepared pursuant to this section shall be submitted to the responsible enforcement agent and the owner along with other plans, specifications and calculations required. If the reviewer resigns or is terminated by the owner prior to completion of the project, then the reviewer shall submit copies of all reports, notes, and the correspondence to the responsible enforcement agent, the owner, and the engineer of record within 10 working days of such termination.
All owners of existing structures, selected by the enforcement agency for the installation of earthquake-recording instruments, shall provide space for the installation and access to such instruments. Location of said instruments shall be determined by the enforcement agency. The enforcement agency shall make arrangements to provide, maintain, and service the instruments. Data shall be the property of the enforcement agency, but copies of individual records shall be made available to the public on request and the payment of an appropriate fee.
The provisions of this section are intended to maintain or increase the current degree of public safety, health and general welfare in existing buildings while permitting repair, alteration, addition and change of occupancy without requiring full compliance with Chapters 2 through 33, or Sections 3401A.3, and 3403A through 3408A, except where compliance with other provisions of this code is specifically required in this section.
Services/systems and utilities that originate in and pass through or under buildings and are necessary to the operation of the hospital buildings shall meet the structural requirements of this section. Examples of services/systems and utilities include but are not limited to normal power; emergency power; nurse call; fire alarm; communication and data systems; space-heating systems; process load systems; cooling systems; domestic hot and cold water systems; means of egress systems; fire-suppression systems; building drain and sewer systems; and medical gas systems that support basic and supplemental services.
After January 1, 2030, services/systems and utilities for acute care hospital buildings shall not originate in or pass through or under a nonhospital or Hospital building unless it has approved performance categories of SPC-3 or higher and NPC-5.
Services/systems and utilities that are necessary to the operation of the hospital buildings shall meet the structural requirements of this section, based upon the approved Structural Performance Category (SPC) of the building receiving the services/systems and utilities.
Services from a conforming building shall be permitted to serve a nonconforming building with prior approval of the Office. The services/systems and utilities in the nonconforming building shall be equipped with fail safe valves, switches or other equivalent devices that allow the nonconforming building to be isolated from the conforming buildings.
Exception: Remodel projects that use available existing services/systems and utilities are exempted from the requirements of this section. The enforcing agency shall be permitted to exempt minor addition, minor alteration, and minor remodel projects and projects to upgrade existing services/systems and utilities from the requirements of this section.
Services/systems and utilities for new hospital buildings and additions, and alterations or remodels to existing conforming buildings shall originate in hospital buildings that are conforming or have approved performance categories of SPC-3 or higher and NPC-4 or higher. The services/systems and utilities shall not pass through or under buildings that do not have approved performance categories of SPC-2 or higher and NPC-4 or higher.
Exception: Services/systems and utilities shall be permitted to pass through or under buildings that have approved nonstructural performance categories of NPC-3 or higher or NPC-2, provided that the building has an approved extension to the NPC-3 deadline. The services/systems and utilities feeding the new building addition, alteration, or remodel shall conform to the new building provisions of this code and shall be deemed by OSHPD to be free of adverse seismic interactions that could be caused by potential failure of overhead or adjacent components.
Services/systems and utilities for additions, alterations, or remodels of SPC-2 hospital buildings shall be permitted to originate in and pass through or under SPC-2 or higher buildings that have an approved nonstructural performance category of NPC-3 or higher.
Exception: Services/systems and utilities shall be permitted to pass through or under buildings that have approved nonstructural performance categories of NPC-2, provided that the building has an approved extension to the NPC-3 deadline. Services/systems and utilities feeding the addition, alteration or remodel shall conform to the nonstructural bracing requirements for new buildings.
Services/systems and utilities for alterations or remodels of SPC-1 hospital buildings shall be permitted to originate in and pass through or under SPC-1 or higher buildings that have an approved nonstructural performance category of NPC-2 or higher.
When services/systems and utilities for new buildings, additions, alterations, or remodels pass through or under hospital buildings which would not otherwise require evaluation for an SPC rating, such buildings shall be evaluated in accordance with the requirements of Section 1.3, Chapter 6, California Administrative Code, to determine the appropriate ratings, or shall be shown to meet the structural requirements of these regulations for new hospital buildings. The services/systems and utilities feeding the new building addition, alteration, or remodel shall conform with new building provisions of this code and shall be deemed by OSHPD to be free of adverse seismic interactions that could be caused by potential failure of overhead or adjacent components.
Services/systems and utilities for conforming acute care hospital buildings shall be permitted to pass through or under a building that has been removed from acute care hospital service until January 1, 2030 if the building removed from service meets the performance requirements of Section 3416A.1.1.1.1. Services/systems and utilities for nonconforming acute care hospital buildings shall be permitted to pass through or under a building that has been removed from acute care hospital service only if the building removed from service and meets the performance requirements of Section 3416A.1.1.1.2.
Services/systems and utilities shall originate in and only pass through or under buildings that are under the jurisdiction of the Office of Statewide Health Planning and Development (OSHPD).
Means of egress through existing buildings shall be in accordance with Chapter 10 except as modified in this section.
Means of egress shall comply with the requirements of Sections 3417A.1.1.1 and 3417A.1.1.2.
Exception: The enforcing agency shall be permitted to exempt minor additions, minor alterations and minor remodel projects from these requirements.
Means of egress for hospital buildings shall comply with the requirements of Sections 3417A.1.1.1.1 through 3417A.1.1.1.6.
Means of egress for new hospital buildings and additions to existing conforming hospital buildings shall only pass through buildings that are conforming or comply with the requirements of SPC-3 or higher and NPC-4 or higher.
Exception: Existing means of egress that pass through hospital buildings that have approved nonstructural performance categories NPC-3, or NPC-2, if the building has an approved extension to the NPC-3 deadline, shall be permitted to remain for the duration of extension. The nonstructural components in the path of egress shall be braced in accordance with the new building provisions of this code.
Means of egress for additions to existing SPC-2 hospital buildings shall only pass through hospital buildings that have OSHPD-approved performance categories of SPC-2 or higher and NPC-4 or higher.
Exception: The means of egress shall be permitted to pass through hospital buildings that have approved nonstructural performance categories of NPC-3, or NPC-2 if the building has an approved extension to the NPC-3 deadline. Nonstructural components in the path of egress shall be braced in accordance with the new building provisions of this code.
Means of egress for remodels of existing SPC-3 or higher hospital buildings shall only pass through hospital buildings that have approved performance categories of SPC-2 or higher and NPC-4 or higher.
Exception: The means of egress shall be permitted to pass through hospital buildings that have approved nonstructural performance categories of NPC-3, or NPC-2 if the building has an approved extension to the NPC-3 deadline. Nonstructural components in the path of egress shall be braced in accordance with the new building provisions of this code.
Means of egress for remodels of existing SPC-1 hospital buildings shall only pass through hospital buildings that have approved performance categories of SPC-1 or higher and NPC-2 or higher.
Exception: Means of egress for acute care service spaces for hospitals licensed pursuant to subdivision (a) of Section 1250 of the Health and Safety Code shall comply with the requirements of Section 3417A.1.1.1.2.
Hospital buildings that would not otherwise require evaluation for an SPC rating, which are used as a part of the means of egress for hospital buildings, shall be evaluated in accordance with the requirements of Section 1.3, Chapter 6, of the California Administrative Code to determine the appropriate rating, or shall meet the structural requirements of these regulations for conforming hospital buildings. Means of egress shall be in accordance with the requirements of Sections 3417A.1.1.1.1 through 3417A.1.1.1.4.
The means of egress for acute care hospitals shall be permitted to pass through buildings that are removed from hospital service only if the buildings remain under the jurisdiction of OSHPD, and only until January 1, 2030, subject to the following:
- Egress for conforming hospital buildings shall be permitted to pass through buildings that have been removed from acute care hospital service that comply with the requirements of Section 3417A.1.1.1.1 or 3417A.1.1.1.3.
- Egress for nonconforming hospital buildings shall be permitted to pass through buildings that have been removed from acute care hospital service that comply with the requirements of Section 3417A.1.1.1.2 or 3417A.1.1.1.4.
After January 1, 2030, the means of egress for acute care hospital buildings shall only pass through hospital buildings that have approved performance categories of SPC-3 or higher and NPC-5.
Means of egress shall only pass through buildings that are under the jurisdiction of the Office of Statewide Health Planning and Development (OSHPD).
The requirements of this section shall apply when general acute care services are completely removed from SPC buildings or when buildings are removed from OSHPD jurisdiction. All buildings that remain under the OSHPD jurisdiction, after one or more SPC buildings are removed, shall satisfy the requirements of the California Building Standards Code. Approval of construction documents and a building permit are required for removal of SPC Buildings from general acute care services or removal of buildings from OSHPD jurisdiction.
A SPC 1 hospital building without an approved delay in compliance requirements in accordance with the California Administrative Code (CAC) Chapter 6 Section 1.5.2 or past the extension date granted in accordance with the CAC Chapter 6 Section 1.5.2 shall not be issued a building permit until a project to remove the subject SPC 1 building from general acute care services has been approved, permitted, and closed in compliance by the Office.
Exception: Building permits for seismic compliance, maintenance and repair shall be permitted to be issued.
The following words and terms are applicable to this section only:
BUILDING. The area included within surrounding exterior walls or any combination of exterior walls and fire walls (as described in Sections 202 and 706) exclusive of vent shafts and courts. Areas of the building not provided with surrounding walls shall be included in the building area if such areas are included within the horizontal projection of the roof or floor above. A building may consist of one or more adjacent SPC buildings.
GENERAL ACUTE CARE SERVICE. Means basic and supplemental services, as defined in Section 1224.3, provided in a general acute care building, as defined in Section 202 and the California Administrative Code, Chapter 6, Section 1.2.
STRUCTURAL SEPARATION.Means a building separation in accordance with this code.
In order to establish that one or more SPC buildings are eligible for removal from general acute care service, the hospital owner shall submit construction documents showing that after the SPC Buildings are removed from general acute care service:
All basic acute care services or supplemental services on the hospital's license are provided in SPC buildings satisfying the requirements for SPC-2, SPC-3, SPC-4, SPC-4D, or SPC-5.
Exception: If the hospital includes SPC-1 buildings that are not being removed from general acute care service, and these SPC-1 buildings have an approved extension to the SPC-2 deadline, basic acute care services or supplemental services on the hospital's license are permitted to remain in these SPC buildings for the duration of their extension or until these SPC-1 buildings are removed from general acute care service, whichever comes first.
All basic acute care services or supplemental services on the hospital's license are provided in SPC buildings satisfying the requirements for NPC-3, NPC-4 or NPC-5.
Exception: Services shall be permitted to be located in SPC buildings satisfying the requirements of NPC-2 if the SPC buildings has approved extension to NPC-3 deadline.
The hospital complies with all egress requirements, including occupant load, number of required exits and travel distance to exits, and provides evidence that no egress from any acute care hospital building passes through the SPC buildings removed from general acute care service, SPC-1 buildings, or through buildings not under OSHPD jurisdiction.
Exceptions:
- If the SPC building has an approved extension to the SPC-2 deadline, existing egress through the SPC-1 building shall be permitted for the duration of the extension or until the SPC-1 building is removed from general acute care service, whichever comes first.
- When permitted by Section 3417A.1.1.1.6.
- No SPC building removed from general acute care service is used as a smoke compartment for any acute care hospital building. Buildings not under OSHPD jurisdiction shall not be used as a smoke compartment for any acute care hospital building.
Structural separation, fire barriers and fire walls shall satisfy the requirements of the California Building Standards Code.
Exception: An SPC seismic separation in accordance with the California Administrative Code Chapter 6 Section 3.4 shall be deemed to satisfy the building structural/seismic separation requirement in this section for SPC buildings that will remain under OSHPD jurisdiction.
If the SPC building removed from general acute care service shares a common fire alarm system with the acute care hospital, the main fire alarm control panel shall be located in an acute care hospital building. The SPC building removed from general acute care service shall be in a separate zone monitored by the main fire alarm control panel. Flexible connections shall be provided for conduits/conductors crossing structural or SPC seismic separation joints. If the intent is to place the SPC building under local jurisdiction, the building shall satisfy Section 3418A.5.1
Exception: Flexible connections for fire alarm conduits/conductors crossing seismic separation joints between an SPC building removed from general acute care service and adjacent SPC-1 or SPC-2 buildings may be omitted, provided the fire alarm in the adjacent SPC-1 and SPC-2 buildings have no connection to any SPC-3, SPC-4, SPC-4D, and SPC-5 buildings providing general acute care service.
If the SPC building removed from general acute care service shares the fire sprinkler system with the acute care hospital, an isolation valve with a tamper switch shall be provided to isolate the portion of the system serving the SPC building removed from acute care service. Flexible connections shall be provided in piping that crosses structural or SPC seismic separation joints. The fire sprinkler system shall not originate in the SPC building removed from general acute care service. If the intent is to place the building under local jurisdiction, the building shall satisfy Section 3418A.5.1.
Exception: Flexible connections for seismic separation joints and fail safe shut-off valves, and disconnects for utilities between an SPC building removed from general acute care service and adjacent SPC-1 or SPC-2 buildings may be omitted, provided utilities in the adjacent SPC-1 and SPC-2 buildings have no connection to any SPC-3, SPC-4, SPC-4D, and SPC-5 buildings providing general acute care service.
- Patient access as required by Section 1224.4.7.5 does not pass through an SPC building removed from general acute care service or through buildings that are not under the jurisdiction of OSHPD.
- The primary accessible entrance to the hospital is not through an SPC building removed from general acute care service or through buildings that are not under the jurisdiction of OSHPD.
- No utilities servicing acute care hospital buildings originate in or pass through, over or under, an SPC building removed from general acute care service, except as permitted by Section 3416A.1.1.1.5, or a building not under OSHPD jurisdiction.
If utilities originating in an acute care hospital building feed an SPC building removed from general acute care hospital service, fail safe shut-off valves and/or disconnects shall be provided that permit isolation of the SPC building removed from general acute care service from the hospital utilities. Flexible connections shall be provided for all utilities crossing structural or SPC seismic separation joints.
Exception: Flexible connections for seismic separation joints and fail safe shut-off valves, and disconnects for utilities between an SPC building removed from general acute care service and adjacent SPC-1 or SPC-2 buildings may be omitted, provided utilities in the adjacent SPC-1 and SPC-2 buildings have no connection to any SPC-3, SPC-4, SPC-4D, and SPC-5 buildings providing general acute care service.
In order for a freestanding building to remain under OSHPD jurisdiction that is removed from general acute care service, it shall contain one or more qualifying services. Qualifying services include:
Services considered "Outpatient Clinical Services" as defined in H&SC §129730 (a):
- Administrative space
- Central sterile supply
- Storage
- Morgue and autopsy facilities
- Employee dressing rooms and lockers
- Janitorial and housekeeping facilities
- Laundry
Outpatient portions of the following services (with no more than 25 percent in-patient use), including but not limited to:
- Surgical
- Chronic dialysis
- Psychiatry
- Rehabilitation, occupational therapy or physical therapy
- Maternity
- Dentistry
- Chemical dependency
- Services that duplicate Basic Services, as defined in H&SC§1250, or services that are provided as part of a Basic Service, but are not required for facility licensure (with no more than 25 percent in-patient use).
All hospital support services listed in Section 3418A.4.1 Item a that are located in an SPC building at the time general acute care services are removed may remain, provided the California Department of Public Health certifies to the Office that it has received and approved a plan that demonstrates how the health facility will continue to provide all basic services in the event of any emergency when the SPC building may no longer remain functional. This certification shall be submitted by hospital to the Office prior to approval of the application to remove the SPC building from general acute care service.
Existing approved nonacute care occupancies, or services, existing in the SPC building at the time it is removed from general acute care service shall be permitted to remain, and removal of the SPC building from general acute care service is not considered a change in occupancy. The enforcement agency shall be permitted to require evidence that the existing occupancies and services were in compliance at the time they were located in the SPC building. Any hospital support services located in the building removed from general acute care service, including administrative services, central sterile supply, storage, morgue and autopsy, employee dressing rooms and lockers, janitorial and housekeeping service, and laundry, shall be in excess of the minimum requirements for licensure and operation. Prior approval by the California Department of Public Health shall be obtained by hospital to maintain these services in the SPC building removed from acute care service.
A change of service or function for all, or a portion, of the SPC building removed from general acute care service requires compliance with the current requirements for that service, including accessibility requirements in accordance with Chapter 11B.
When general acute care services are removed from an SPC building which is intended to be used for skilled nursing or acute psychiatric services, and the new services will be licensed under the existing license of the general acute care hospital these new services shall comply with Section 3416A.1.1.1.5 for a nonconforming hospital building.
When general acute care services are removed from an SPC building that is intended to be used for outpatient clinical services under the existing acute care hospital license, the building is required to comply with the current OSHPD 3 code requirements for the new service.
When general acute care services are removed from an SPC building, and new services provided in the SPC building are issued an initial license, as determined by the California Department of Public Health, as a skilled nursing facility or acute psychiatric hospital, the SPC building shall comply with the new building code requirements or equivalent provisions of the California Building Standards code at the time of application.
When an SPC building is removed from general acute care service with or without change of license, the new occupancy group and division of the building, and/or new service or function, shall be established. A new certificate of occupancy shall be required for the building removed from general acute care service.
Except as provided by Section 3418A.5.3, at the hospital's discretion, a building removed from general acute care service shall be permitted to be placed under the jurisdiction of the local enforcement agency. To be eligible for a change in jurisdiction, the building removed from general acute care service shall satisfy the requirements of Section 3418A.5.1.
For a building removed from general acute care service to be eligible for a change in jurisdiction to the local enforcing agency, all the following criteria shall be satisfied:
- The building removed from general acute care service shall be freestanding, as defined in the California Administrative Code, Section 7-111.
- Any hospital support services located in the building removed from general acute care service, including administrative services, central sterile supply, storage, morgue and autopsy, employee dressing rooms and lockers, janitorial and housekeeping service, and laundry, shall be in excess of the minimum requirements for licensure and operation. Prior approval by the California Department of Public Health shall be obtained by hospital to locate these services in the building removed from general acute care service.
- Services/systems and utilities (e.g., power, emergency power, communication/data/nurse-call systems, space-heating systems, fire alarm system, fire-sprinkler system, medical gas and plumbing systems) shall be separate and independent from those serving any buildings under OSHPD jurisdiction.
- If the building being transferred to the jurisdiction of the local enforcing agency is adjacent to a building under OSHPD jurisdiction and fire resistive construction separations are required, they shall be located in the building under OSHPD jurisdiction.
The owner of the building shall be responsible for bringing the building into compliance with all requirements of the new authority having jurisdiction. If a building requires modification to become eligible for removal from OSHPD jurisdiction, the construction project shall be closed with compliance by OSHPD prior to the change in jurisdiction. All occupancy separation, setback, and allowable area requirements shall be enforced.
The following freestanding buildings shall remain under OSHPD jurisdiction:
- Any building in which basic and/or supplementary services are provided for a general acute care hospital, acute psychiatric hospital and general acute care hospital providing only acute medical rehabilitation center services.
- Any building that provides required patient access, egress, or smoke compartment for a building under OSHPD's jurisdiction.
- Any building in which services under OSHPD jurisdiction are provided, including skilled nursing services, intermediate care services, acute psychiatric services, and distinct part skilled nursing or intermediate care services.
- Any building providing central plant or utility services to a building under OSHPD jurisdiction.
- Any building through which utilities pass through, over or under, to serve a building under OSHPD jurisdiction.
With the removal of general acute care services, the vacated space must be reclassified with an intended occupancy as required under Section 302. If the hospital determines that the building or space in the SPC building removed from general acute care service will be vacant, the hospital shall demonstrate that unsafe conditions as described in Section 116.1 are not created.
Demolition of SPC buildings to be removed from general acute care services shall be permitted when buildings remaining under OSHPD's jurisdiction, after demolition, satisfy the requirements of the California Building Standards Code and demolition activity does not impair the operation and/or safety of any buildings that remain under OSHPD's jurisdiction. Demolition shall be in accordance with Section 3303.
The requirements of this section and Section 3418A shall apply to buildings removed from general acute care services that remain under OSHPD jurisdiction.
Non-GAC buildings shall conform to the requirements of Section 1.10.1.
Application and enforcement of freestanding buildings removed from general acute care services but remaining under OSHPD jurisdiction shall be in accordance with Section 1.10.
Freestanding hospital-owned clinics shall be permitted to be under the jurisdiction of OSHPD in accordance with California Administrative Code Sections 7-2104, 7-2105, and 7-2106.