Adopting agency | BSC | BSC-CG | SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||
1 | 2 | 1/AC | AC | SS | SS/CC | 1 | 2 | 3 | 4 | ||||||||||||
Adopt entire chapter | X | ||||||||||||||||||||
Adopt entire chapter as amended (amended sections listed below) | X | X | X | X | X | ||||||||||||||||
Adopt only those sections that are listed below | X | X | X | ||||||||||||||||||
Chapter / Section | |||||||||||||||||||||
1601.1.1 | X | ||||||||||||||||||||
1601.1.2 | X | ||||||||||||||||||||
1601.1.3 | X | ||||||||||||||||||||
1601.1.4 | X | ||||||||||||||||||||
1601.2 | X | X | |||||||||||||||||||
1603.1 | X | ||||||||||||||||||||
1607.1, Table 1607.1 | X | ||||||||||||||||||||
Table 1607.1 | X | X | X | ||||||||||||||||||
1607.8 | X | ||||||||||||||||||||
1607.8.2 | X | X | |||||||||||||||||||
1612.3, Exception | X | ||||||||||||||||||||
1613.1 | X | ||||||||||||||||||||
1613.1.1 | X | ||||||||||||||||||||
1613.1.2 | X | ||||||||||||||||||||
1613.1.3 | X | ||||||||||||||||||||
1613.3.1, Exception | X | ||||||||||||||||||||
1613.3.5, Exception | X | ||||||||||||||||||||
1613.3.5.1, Exception | X | ||||||||||||||||||||
1613.3.5.2, Exception | X | ||||||||||||||||||||
1613.5 | X | X | |||||||||||||||||||
1613.5.1, Exception | X | ||||||||||||||||||||
1616 | X | ||||||||||||||||||||
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
[DSA-SS/CC] The scope of application of Chapter 16 is as follows:
Community college buildings regulated by the Division of the State Architect-Structural Safety/Community Colleges (DSA-SS/CC), as listed in Section 1.9.2.2.
[DSA-SS/CC] Division of the State Architect-Structural Safety/Community Colleges (DSA-SS/CC) amendments appear in this chapter preceded with the appropriate acronym, as follows:
Division of the State Architect - Structural Safety/Community Colleges: [DSA-SS/CC] - For community college buildings listed in Section 1.9.2.2
[DSA-SS/CC] See Section 1616 for additional requirements.
[DSA-SS/CC, OSHPD 2] In addition to requirements of the California Administrative Code and the California Building Code, any aspect of project design, construction, quality assurance or quality control programs for which this code requires approval by the Registered Design Professional (RDP), are also subject to approval by the enforcement agency.
The following terms are defined in Chapter 2:
LIVE LOAD (ROOF).
LOAD AND RESISTANCE FACTOR DESIGN (LRFD). LOAD EFFECTS.
PANEL (PART OF A STRUCTURE).
D = Dead load.
Di = Weight of ice in accordance with Chapter 10 of ASCE 7.
E = Combined effect of horizontal and vertical earthquake induced forces as defined in Section 12.4.2 of ASCE 7.
F = Load due to fluids with well-defined pressures and maximum heights.
Fa = Flood load in accordance with Chapter 5 of ASCE 7.
H = Load due to lateral earth pressures, ground water pressure or pressure of bulk materials.
L = Roof live load greater than 20 psf (0.96 kN/m2) and floor live load.
Lr = Roof live load of 20 psf (0.96 kN/m2) or less.
R = Rain load.
S = Snow load.
T = Self-straining load.
Vasd = Nominal design wind speed (3-second gust), miles per hour (mph) (km/hr) where applicable.
Vult = Ultimate design wind speeds (3-second gust), miles per hour (mph) (km/hr) determined from Figures 1609.3(1), 1609.3(2), 1609.3(3) or ASCE 7.
W = Load due to wind pressure.
Wi = Wind-on-ice in accordance with Chapter 10 of ASCE 7.
Construction documents shall show the size, section and relative locations of structural members with floor levels, column centers and offsets dimensioned. The design loads and other information pertinent to the structural design required by Sections 1603.1.1 through 1603.1.8 shall be indicated on the construction documents.
Exception: Construction documents for buildings constructed in accordance with the conventional light-frame construction provisions of Section 2308 shall indicate the following structural design information:
- Floor and roof live loads.
- Ground snow load, Pg.
- Ultimate design wind speed, Vult, (3-second gust), miles per hour (mph) (km/hr) and nominal design wind speed, Vasd, as determined in accordance with Section 1609.3.1 and wind exposure.
- Seismic design category and site class.
- Flood design data, if located in flood hazard areas established in Section 1612.3.
- Design load-bearing values of soils.
[OSHPD 2] Additional requirements are included in Sections 7-115 and 7-125 of the California Administrative Code (Part 1, Title 24, C.C.R).
The ground snow load, Pg, shall be indicated. In areas where the ground snow load, Pg, exceeds 10 pounds per square foot (psf) (0.479 kN/m2), the following additional information shall also be provided, regardless of whether snow loads govern the design of the roof:
- Flat-roof snow load, Pf.
- Snow exposure factor, Ce.
- Snow load importance factor, Is.
- Thermal factor, Ct.
- Drift surcharge load(s), Pd, where the sum of Pd and Pf exceeds 20 psf (0.96 kN/m2).
- Width of snow drift(s), w.
The following information related to wind loads shall be shown, regardless of whether wind loads govern the design of the lateral force-resisting system of the structure:
- Ultimate design wind speed, Vult, (3-second gust), miles per hour (km/hr) and nominal design wind speed, Vasd, as determined in accordance with Section 1609.3.1.
- Risk category.
- Wind exposure. Applicable wind direction if more than one wind exposure is utilized.
- Applicable internal pressure coefficient.
- Design wind pressures to be used for exterior component and cladding materials not specifically designed by the registered design professional responsible for the design of the structure, psf (kN/m2).
The following information related to seismic loads shall be shown, regardless of whether seismic loads govern the design of the lateral force-resisting system of the structure:
- Risk category.
- Seismic importance factor, Ie.
- Mapped spectral response acceleration parameters, SS and S1.
- Site class.
- Design spectral response acceleration parameters, SDS and SD1.
- Seismic design category.
- Basic seismic force-resisting system(s).
- Design base shear(s).
- Seismic response coefficient(s), CS.
- Response modification coefficient(s), R.
- Analysis procedure used.
For buildings located in whole or in part in flood hazard areas as established in Section 1612.3, the documentation pertaining to design, if required in Section 1612.5, shall be included and the following information, referenced to the datum on the community's Flood Insurance Rate Map (FIRM), shall be shown, regardless of whether flood loads govern the design of the building:
- Flood design class assigned according to ASCE 24.
- In flood hazard areas other than coastal high hazard areas or coastal A zones, the elevation of the proposed lowest floor, including the basement.
- In flood hazard areas other than coastal high hazard areas or coastal A zones, the elevation to which any nonresidential building will be dry floodproofed.
- In coastal high hazard areas and coastal A zones, the proposed elevation of the bottom of the lowest horizontal structural member of the lowest floor, including the basement.
Buildings and other structures, and parts thereof, shall be designed and constructed to support safely the factored loads in load combinations defined in this code without exceeding the appropriate strength limit states for the materials of construction. Alternatively, buildings and other structures, and parts thereof, shall be designed and constructed to support safely the nominal loads in load combinations defined in this code without exceeding the appropriate specified allowable stresses for the materials of construction.
Loads and forces for occupancies or uses not covered in this chapter shall be subject to the approval of the building official.
Structural systems and members thereof shall be designed to have adequate stiffness to limit deflections and lateral drift. See Section 12.12.1 of ASCE 7 for drift limits applicable to earthquake loading.
DEFLECTION LIMITSa, b, c, h, i
CONSTRUCTION | L | E, S or Wf | D + Ld, g |
Roof members:e | |||
Supporting plaster or stucco ceiling | l/360 | l/360 | l/240 |
Supporting nonplaster ceiling | l/240 | l/240 | l/180 |
Not supporting ceiling | l/180 | l/180 | l/120 |
Floor members | l/360 | — | l/240 |
Exterior walls: | |||
With plaster or stucco finishes | — | l/360 | — |
With other brittle finishes | — | l/240 | — |
With flexible finishes | — | l/120 | — |
Interior partitions:b | |||
With plaster or stucco finishes | l/360 | — | — |
With other brittle finishes | l/240 | — | — |
With flexible finishes | l/120 | — | — |
Farm buildings | — | — | l/180 |
Greenhouses | — | — | l/120 |
For SI: 1 foot = 304.8 mm.
- For structural roofing and siding made of formed metal sheets, the total load deflection shall not exceed 1/60. For secondary roof structural members supporting formed metal roofing, the live load deflection shall not exceed 1/150. For secondary wall members supporting formed metal siding, the design wind load deflection shall not exceed 1/90. For roofs, this exception only applies when the metal sheets have no roof covering.
- Flexible, folding and portable partitions are not governed by the provisions of this section. The deflection criterion for interior partitions is based on the horizontal load defined in Section 1607.14.
- See Section 2403 for glass supports.
- The deflection limit for the D+L load combination only applies to the deflection due to the creep component of long-term dead load deflection plus the short-term live load deflection. For wood structural members that are dry at time of installation and used under dry conditions in accordance with the AWC NDS, the creep component of the long-term deflection shall be permitted to be estimated as the immediate dead load deflection resulting from 0.5D. For wood structural members at all other moisture conditions, the creep component of the long-term deflection is permitted to be estimated as the immediate dead load deflection resulting from D. The value of 0.5D shall not be used in combination with AWC NDS provisions for long-term loading.
- The above deflections do not ensure against ponding. Roofs that do not have sufficient slope or camber to ensure adequate drainage shall be investigated for ponding. See Section 1611 for rain and ponding requirements and Section 1503.4 for roof drainage requirements.
- The wind load is permitted to be taken as 0.42 times the "component and cladding" loads for the purpose of determining deflection limits herein. Where members support glass in accordance with Section 2403 using the deflection limit therein, the wind load shall be no less than 0.6 times the "component and cladding" loads for the purpose of determining deflection.
- For steel structural members, the dead load shall be taken as zero.
- For aluminum structural members or aluminum panels used in skylights and sloped glazing framing, roofs or walls of sunroom additions or patio covers not supporting edge of glass or aluminum sandwich panels, the total load deflection shall not exceed 1/60. For continuous aluminum structural members supporting edge of glass, the total load deflection shall not exceed 1/175 for each glass lite or 1/60 for the entire length of the member, whichever is more stringent. For aluminum sandwich panels used in roofs or walls of sunroom additions or patio covers, the total load deflection shall not exceed 1/120.
- For cantilever members, 1 shall be taken as twice the length of the cantilever.
Load effects on structural members and their connections shall be determined by methods of structural analysis that take into account equilibrium, general stability, geometric compatibility and both short- and long-term material properties.
Members that tend to accumulate residual deformations under repeated service loads shall have included in their analysis the added eccentricities expected to occur during their service life.
Any system or method of construction to be used shall be based on a rational analysis in accordance with well-established principles of mechanics. Such analysis shall result in a system that provides a complete load path capable of transferring loads from their point of origin to the load-resisting elements.
The total lateral force shall be distributed to the various vertical elements of the lateral force-resisting system in proportion to their rigidities, considering the rigidity of the horizontal bracing system or diaphragm. Rigid elements assumed not to be a part of the lateral force-resisting system are permitted to be incorporated into buildings provided their effect on the action of the system is considered and provided for in the design. A diaphragm is rigid for the purpose of distribution of story shear and torsional moment when the lateral deformation of the diaphragm is less than or equal to two times the average story drift. Where required by ASCE 7, provisions shall be made for the increased forces induced on resisting elements of the structural system resulting from torsion due to eccentricity between the center of application of the lateral forces and the center of rigidity of the lateral force-resisting system.
Every structure shall be designed to resist the overturning effects caused by the lateral forces specified in this chapter. See Section 1609 for wind loads, Section 1610 for lateral soil loads and Section 1613 for earthquake loads.
Each building and structure shall be assigned a risk category in accordance with Table 1604.5. Where a referenced standard specifies an occupancy category, the risk category shall not be taken as lower than the occupancy category specified therein. Where a referenced standard specifies that the assignment of a risk category be in accordance with ASCE 7, Table 1.5-1, Table 1604.5 shall be used in lieu of ASCE 7, Table 1.5-1.
RISK CATEGORY OF BUILDINGS AND OTHER STRUCTURES
RISK CATEGORY | NATURE OF OCCUPANCY |
I | Buildings and other structures that represent a low hazard to human life in the event of failure, including but not limited to: • Agricultural facilities. • Certain temporary facilities.• Minor storage facilities. |
II | Buildings and other structures except those listed in Risk Categories I, III and IV. |
III | Buildings and other structures that represent a substantial hazard to human life in the event of failure, including but not limited to: • Buildings and other structures whose primary occupancy is public assembly with an occupant load greater than 300. • Buildings and other structures containing Group E occupancies with an occupant load greater than 250. • Buildings and other structures containing educational occupancies for students above the 12th grade with an occupant load greater than 500. • Group I-2 occupancies with an occupant load of 50 or more resident care recipients but not having surgery or emergency treatment facilities. • Group I-3 occupancies. • Any other occupancy with an occupant load greater than 5,000.a • Power-generating stations, water treatment facilities for potable water, wastewater treatment facilities and other public utility facilities not included in Risk Category IV. • Buildings and other structures not included in Risk Category IV containing quantities of toxic or explosive materials that: Exceed maximum allowable quantities per control area as given in Table 307.1(1) or 307.1(2) or per outdoor control area in accordance with the California Fire Code; and Are sufficient to pose a threat to the public if released.b |
IV | Buildings and other structures designated as essential facilities, including but not limited to: • Group I-2 occupancies having surgery or emergency treatment facilities. • Fire, rescue, ambulance and police stations and emergency vehicle garages. • Designated earthquake, hurricane or other emergency shelters. • Designated emergency preparedness, communications and operations centers and other facilities required for emergency response. • Power-generating stations and other public utility facilities required as emergency backup facilities for Risk Category IV structures. • Buildings and other structures containing quantities of highly toxic materials that: Exceed maximum allowable quantities per control area as given in Table 307.1(2) or per outdoor control area in accordance with the California Fire Code; and Are sufficient to pose a threat to the public if released.b• Aviation control towers, air traffic control centers and emergency aircraft hangars. • Buildings and other structures having critical national defense functions. • Water storage facilities and pump structures required to maintain water pressure for fire suppression. |
- For purposes of occupant load calculation, occupancies required by Table 1004.1.2 to use gross floor area calculations shall be permitted to use net floor areas to determine the total occupant load.
- Where approved by the building official, the classification of buildings and other structures as Risk Category III or IV based on their quantities of toxic, highly toxic or explosive materials is permitted to be reduced to Risk Category II, provided it can be demonstrated by a hazard assessment in accordance with Section 1.5.3 of ASCE 7 that a release of the toxic, highly toxic or explosive materials is not sufficient to pose a threat to the public.
Where supported by attachment to an exterior wall, decks shall be positively anchored to the primary structure and designed for both vertical and lateral loads as applicable. Such attachment shall not be accomplished by the use of toenails or nails subject to withdrawal. Where positive connection to the primary building structure cannot be verified during inspection, decks shall be self-supporting. Connections of decks with cantilevered framing members to exterior walls or other framing members shall be designed for both of the following:
- The reactions resulting from the dead load and live load specified in Table 1607.1, or the snow load specified in Section 1608, in accordance with Section 1605, acting on all portions of the deck.
- The reactions resulting from the dead load and live load specified in Table 1607.1, or the snow load specified in Section 1608, in accordance with Section 1605, acting on the cantilevered portion of the deck, and no live load or snow load on the remaining portion of the deck.
Buildings and other structures and portions thereof shall be designed to resist:
- The load combinations specified in Section 1605.2, 1605.3.1 or 1605.3.2;
- The load combinations specified in Chapters 18 through 23; and
- The seismic load effects including overstrength factor in accordance with Section 12.4.3 of ASCE 7 where required by Section 12.2.5.2, 12.3.3.3 or 12.10.2.1 of ASCE 7. With the simplified procedure of ASCE 7 Section 12.14, the seismic load effects including over-strength factor in accordance with Section 12.14.3.2 of ASCE 7 shall be used.
Applicable loads shall be considered, including both earthquake and wind, in accordance with the specified load combinations. Each load combination shall also be investigated with one or more of the variable loads set to zero.
Where the load combinations with overstrength factor in Section 12.4.3.2 of ASCE 7 apply, they shall be used as follows:
- The basic combinations for strength design with over-strength factor in lieu of Equations 16-5 and 16-7 in Section 1605.2.
- The basic combinations for allowable stress design with overstrength factor in lieu of Equations 16-12, 16-14 and 16-16 in Section 1605.3.1.
- The basic combinations for allowable stress design with overstrength factor in lieu of Equations 16-21 and 16-22 in Section 1605.3.2.
Where strength design or load and resistance factor design is used, buildings and other structures, and portions thereof, shall be designed to resist the most critical effects resulting from the following combinations of factored loads:
(Equation 16-1)
(Equation 16-2)
(Equation 16-3)
(Equation 16-4)
(Equation 16-5)
(Equation 16-6)
(Equation 16-7)
where:
f1 = 1 for places of public assembly live loads in excess of 100 pounds per square foot (4.79 kN/m2), and parking garages; and 0.5 for other live loads.
f2 = 0.7 for roof configurations (such as saw tooth) that do not shed snow off the structure, and 0.2 for other roof configurations.
Exceptions:
- Where other factored load combinations are specifically required by other provisions of this code, such combinations shall take precedence.
- Where the effect of H resists the primary variable load effect, a load factor of 0.9 shall be included with H where H is permanent and H shall be set to zero for all other conditions.
Where allowable stress design (working stress design), as permitted by this code, is used, structures and portions thereof shall resist the most critical effects resulting from the following combinations of loads:
(Equation 16-8)
(Equation 16-9)
(Equation 16-10)
(Equation 16-11)
(Equation 16-12)
(Equation 16-13)
(Equation 16-14)
(Equation 16-15)
(Equation 16-16)
Exceptions:
- Crane hook loads need not be combined with roof live load or with more than three-fourths of the snow load or one-half of the wind load.
- Flat roof snow loads of 30 psf (1.44 kN/m2) or less and roof live loads of 30 psf (1.44 kN/m2) or less need not be combined with seismic loads. Where flat roof snow loads exceed 30 psf (1.44 kN/m2), 20 percent shall be combined with seismic loads.
- Where the effect of H resists the primary variable load effect, a load factor of 0.6 shall be included with H where H is permanent and H shall be set to zero for all other conditions.
- In Equation 16-15, the wind load, W, is permitted to be reduced in accordance with Exception 2 of Section 2.4.1 of ASCE 7.
- In Equation 16-16, 0.6 D is permitted to be increased to 0.9 D for the design of special reinforced masonry shear walls complying with Chapter 21.
In lieu of the basic load combinations specified in Section 1605.3.1, structures and portions thereof shall be permitted to be designed for the most critical effects resulting from the following combinations. When using these alternative basic load combinations that include wind or seismic loads, allowable stresses are permitted to be increased or load combinations reduced where permitted by the material chapter of this code or the referenced standards. For load combinations that include the counteracting effects of dead and wind loads, only two-thirds of the minimum dead load likely to be in place during a design wind event shall be used. When using allowable stresses that have been increased or load combinations that have been reduced as permitted by the material chapter of this code or the referenced standards, where wind loads are calculated in accordance with Chapters 26 through 31 of ASCE 7, the coefficient (ω) in the following equations shall be taken as 1.3. For other wind loads, (ω) shall be taken as 1. When allowable stresses have not been increased or load combinations have not been reduced as permitted by the material chapter of this code or the referenced standards, (ω) shall be taken as 1. When using these alternative load combinations to evaluate sliding, overturning and soil bearing at the soil-structure interface, the reduction of foundation overturning from Section 12.13.4 in ASCE 7 shall not be used. When using these alternative basic load combinations for proportioning foundations for loadings, which include seismic loads, the vertical seismic load effect, Ev, in Equation 12.4-4 of ASCE 7 is permitted to be taken equal to zero.
(Equation 16-17)
(Equation 16-18)
(Equation 16-19)
(Equation 16-20)
(Equation 16-21)
(Equation 16-22)
Exceptions:
- Crane hook loads need not be combined with roof live loads or with more than three-fourths of the snow load or one-half of the wind load.
- Flat roof snow loads of 30 psf (1.44 kN/m2) or less and roof live loads of 30 psf (1.44 kN/m2) or less need not be combined with seismic loads. Where flat roof snow loads exceed 30 psf (1.44 kN/m2), 20 percent shall be combined with seismic loads.
Live loads are those loads defined in Section 1602.1.
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS, Lo, AND MINIMUM CONCENTRATED LIVE LOADSg
OCCUPANCY OR USE | UNIFORM (psf) | CONCENTRATED (lbs.) |
1. Apartments (see residential) | — | — |
2. Access floor systems | ||
Office use | 50 | 2,000 |
Computer use | 100 | 2,000 |
3. Armories and drill rooms | 150m | — |
4. Assembly areas | ||
Fixed seats (fastened to floor) | 60m | |
Follow spot, projections and control rooms | 50 | |
100m | — | |
Movable seats | 100m | |
Stage floors | 150m | |
Platforms (assembly) | 100m | |
Other assembly areas | 100m | |
5. Balconies and decksh | [BSC, HCD 1, HCD 2] 1.5 times the live load for the area served. Not required to exceed 100 psf. | — |
6. Catwalks | 40 | 300 |
7. Cornices | 60 | — |
8. Corridors | ||
First floor | 100 | |
Other floors | Same as occupancy served except as indicated | — |
9. Dining rooms and restaurants | 100m | — |
10. Dwellings (see residential) | — | — |
11. Elevator machine room and control room grating (on area of 2 inches by 2 inches) | — | 300 |
12. Finish light floor plate construction (on area of 1 inch by 1 inch) | — | 200 |
13. Fire escapes | 100 | — |
On single-family dwellings only | 40 | |
14. Garages (passenger vehicles only) | 40m | Note a |
Trucks and buses | See Section 1607.7 | |
15. Handrails, guards and grab bars | See Section 1607.8 | |
16. Helipads | See Section 1607.6 | |
17. Hospitals | ||
Corridors above first floor | 80 | 1,000 |
60 | 1,000 | |
40 | 1,000 | |
18. Hotels (see residential) | — | — |
19. Libraries | ||
Corridors above first floor | 80 | 1,000 |
Reading rooms | 60 | 1,000 |
Stack rooms | 150b, m | 1,000 |
20. Manufacturing | ||
Heavy | 250m | 3,000 |
Light | 125m | 2,000 |
21. Marquees, except one- and two-family dwellings | 75 | — |
22. Office buildings | ||
Corridors above first floor | 80 | 2,000 |
100 | 2,000 | |
Offices | 50 | 2,000 |
23. Penal institutions | ||
Cell blocks | 40 | — |
100 | ||
24. Recreational uses: | ||
Bowling alleys, poolrooms and similar uses | 75m | |
Dance halls and ballrooms | 100m | |
Gymnasiums | 100m | |
Ice skating rink | 250m | — |
Reviewing stands, grandstands and bleachers | 100c, m | |
Roller skating rink | 100m | |
Stadiums and arenas with fixed seats (fastened to floor) | 60c, m | |
25. Residential | ||
One- and two-family dwellings | ||
Uninhabitable attics without storagei | 10 | |
Uninhabitable attics with storagei, j, k | 20 | |
Habitable attics and sleeping areask | 30 | |
20 | — | |
All other areas | 40 | |
Hotels and multifamily dwellings | ||
40 | ||
100 | ||
26. Roofs | ||
All roof surfaces subject to maintenance workers | 300 | |
Awnings and canopies: | ||
Fabric construction supported by a skeleton structure | 5 Nonreducible | |
All other construction, except one- and two-family dwellings | 20 | |
Ordinary flat, pitched, and curved roofs (that are not occupiable) | 20 | |
Primary roof members exposed to a work floor: | ||
2,000 | ||
All other primary roof members | 300 | |
Occupiable roofs: | ||
Roof gardens | 100 | |
100m | ||
All other similar areas | Note 1 | Note 1 |
27. Schools | ||
Classrooms | 40 | 1,000 |
Corridors above first floor | 80 | 1,000 |
First-floor corridors | 100 | 1,000 |
28. Scuttles, skylight ribs and accessible ceilings | — | 200 |
29. Sidewalks, vehicular driveways and yards, subject to trucking | 250d, m | 8,000e |
30. Stairs and exits | ||
One- and two-family dwellings | 40 | 300f |
All other | 100 | 300f |
31. Storage warehouses (shall be designed for heavier loads if required for anticipated storage) | ||
Heavy | 250m | |
Light | 125m | |
32. Stores | ||
Retail | ||
First floor | 100 | 1,000 |
Upper floors | 75 | 1,000 |
Wholesale, all floors | 125m | 1,000 |
33. Vehicle barriers | See Section 1607.8.3 | |
34. Walkways and elevated platforms (other than exitways) | 60 | — |
35. Yards and terraces, pedestrians | 100m | — |
36. [OSHPD 2] Storage racks and wall-hung cabinets. | Total loadsn | — |
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm2, 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kN/m2, 1 pound = 0.004448 kN, 1 pound per cubic foot = 16 kg/m3.
- Floors in garages or portions of buildings used for the storage of motor vehicles shall be designed for the uniformly distributed live loads of this Table or the following concentrated loads: (1) for garages restricted to passenger vehicles accommodating not more than nine passengers, 3,000 pounds acting on an area of 41/2 inches by 41/2 inches; (2) for mechanical parking structures without slab or deck that are used for storing passenger vehicles only, 2,250 pounds per wheel.
The loading applies to stack room floors that support nonmobile, double- faced library book stacks, subject to the following limitations:
- Design in accordance with ICC 300.
- Other uniform loads in accordance with an approved method containing provisions for truck loadings shall be considered where appropriate.
- The concentrated wheel load shall be applied on an area of 4.5 inches by 4.5 inches.
- The minimum concentrated load on stair treads shall be applied on an area of 2 inches by 2 inches. This load need not be assumed to act concurrently with the uniform load.
- Where snow loads occur that are in excess of the design conditions, the structure shall be designed to support the loads due to the increased loads caused by drift buildup or a greater snow design determined by the building official (see Section 1608).
- See Section 1604.8.3 for decks attached to exterior walls.
- Uninhabitable attics without storage are those where the maximum clear height between the joists and rafters is less than 42 inches, or where there are not two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. This live load need not be assumed to act concurrently with any other live load requirements.
Uninhabitable attics with storage are those where the maximum clear height between the joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.
The live load need only be applied to those portions of the joists or truss bottom chords where both of the following conditions are met:
- The attic area is accessible from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is a minimum of 30 inches; and
- The slopes of the joists or truss bottom chords are no greater than two units vertical in 12 units horizontal.
The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
- Attic spaces served by stairways other than the pull-down type shall be designed to support the minimum live load specified for habitable attics and sleeping rooms.
- Areas of occupiable roofs, other than roof gardens and assembly areas, shall be designed for appropriate loads as approved by the building official. Unoccupied landscaped areas of roofs shall be designed in accordance with Section 1607.12.3.
- Live load reduction is not permitted unless specific exceptions of Section 1607.10 apply.
[OSHPD 2] The minimum vertical design live load shall be as follows:
Paper media: 12-inch-deep (305 mm) shelf 33 pounds per lineal foot (482 N/m) 15-inch-deep (381 mm) shelf 41 pounds per lineal foot (598 N/m), or 33 pounds per cubic foot (5183 N/m3) per total volume of the rack or cabinet, whichever is less. Film media: 18-inch-deep (457 mm) shelf 100 pounds per lineal foot (1459 N/m), or 50 pounds per cubic foot (7853 N/m3) per total volume of the rack or cabinet, whichever is less. Other media: 20 pounds per cubic foot (311 N/m3) or 20 pounds per square foot (958 Pa), whichever is less, but not less than actual loads.
Helipads shall be designed for the following live loads:
A uniform live load, L, as specified below. This load shall not be reduced.
- 1.1. 40 psf (1.92 kN/m2) where the design basis helicopter has a maximum take-off weight of 3,000 pounds (13.35 kN) or less.
- 1.2. 60 psf (2.87 kN/m2) where the design basis helicopter has a maximum take-off weight greater than 3,000 pounds (13.35 kN).
- A single concentrated live load, L, of 3,000 pounds (13.35 kN) applied over an area of 4.5 inches by 4.5 inches (114 mm by 114 mm) and located so as to produce the maximum load effects on the structural elements under consideration. The concentrated load is not required to act concurrently with other uniform or concentrated live loads.
- Two single concentrated live loads, L, 8 feet (2438 mm) apart applied on the landing pad (representing the helicopter's two main landing gear, whether skid type or wheeled type), each having a magnitude of 0.75 times the maximum take-off weight of the helicopter, and located so as to produce the maximum load effects on the structural elements under consideration. The concentrated loads shall be applied over an area of 8 inches by 8 inches (203 mm by 203 mm) and are not required to act concurrently with other uniform or concentrated live loads.
Landing areas designed for a design basis helicopter with maximum take-off weight of 3,000-pounds (13.35 kN) shall be identified with a 3,000 pound (13.34 kN) weight limitation. The landing area weight limitation shall be indicated by the numeral "3" (kips) located in the bottom right corner of the landing area as viewed from the primary approach path. The indication for the landing area weight limitation shall be a minimum 5 feet (1524 mm) in height.
Where a structure or portions of a structure are accessed and loaded by fire department access vehicles and other similar emergency vehicles, the structure shall be designed for the greater of the following loads:
- The actual operational loads, including outrigger reactions and contact areas of the vehicles as stipulated and approved by the building official; or
- The live loading specified in Section 1607.7.1.
Garages designed to accommodate vehicles that exceed a 10,000-pound (4536 kg) gross vehicle weight rating, shall be designed using the live loading specified by Section 1607.7.1. For garages the design for impact and fatigue is not required.
Exception: The vehicular live loads and load placement are allowed to be determined using the actual vehicle weights for the vehicles allowed onto the garage floors, provided such loads and placement are based on rational engineering principles and are approved by the building official, but shall not be less than 50 psf (2.9 kN/m2). This live load shall not be reduced.
Handrails and guards shall be designed to resist a linear load of 50 pounds per linear foot (plf) (0.73 kN/m) in accordance with Section 4.5.1 of ASCE 7. Glass handrail assemblies and guards shall also comply with Section 2407.
Exceptions:
- For one- and two-family dwellings, only the single concentrated load required by Section 1607.8.1.1 shall be applied.
- In Group I-3, F, H and S occupancies, for areas that are not accessible to the general public and that have an occupant load less than 50, the minimum load shall be 20 pounds per foot (0.29 kN/m).
Subject to the limitations of Sections 1607.10.1.1 through 1607.10.1.3 and Table 1607.1, members for which a value of KLLAT is 400 square feet (37.16 m2) or more are permitted to be designed for a reduced uniformly distributed live load, L, in accordance with the following equation:
(Equation 16-23)
For SI:
where:
L | = | Reduced design live load per square foot (m2) of area supported by the member. |
Lo | = | Unreduced design live load per square foot (m2) of area supported by the member (see Table 1607.1). |
KLL | = | Live load element factor (see Table 1607.10.1). |
AT | = | Tributary area, in square feet (m2). |
L shall not be less than 0.50Lo for members supporting one floor and L shall not be less than 0.40Lo for members supporting two or more floors.
ELEMENT | KLL |
Interior columns | 4 |
Exterior columns without cantilever slabs | 4 |
Edge columns with cantilever slabs | 3 |
Corner columns with cantilever slabs | 2 |
Edge beams without cantilever slabs | 2 |
Interior beams | 2 |
All other members not identified above including: | |
Edge beams with cantilever slabs | |
Cantilever beams | |
One-way slabs | 1 |
Two-way slabs | |
Members without provisions for continuous shear transfer normal to their span |
Live loads that exceed 100 psf (4.79 kN/m2) shall not be reduced.
Exceptions:
- The live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent, but the live load shall not be less than L as calculated in Section 1607.10.1.
- For uses other than storage, where approved, additional live load reductions shall be permitted where shown by the registered design professional that a rational approach has been used and that such reductions are warranted.
The live loads shall not be reduced in passenger vehicle garages.
Exception: The live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent, but the live load shall not be less than L as calculated in Section 1607.10.1.
As an alternative to Section 1607.10.1 and subject to the limitations of Table 1607.1, uniformly distributed live loads are permitted to be reduced in accordance with the following provisions. Such reductions shall apply to slab systems, beams, girders, columns, piers, walls and foundations.
A reduction shall not be permitted where the live load exceeds 100 psf (4.79 kN/m2) except that the design live load for members supporting two or more floors is permitted to be reduced by a maximum of 20 percent.
Exception: For uses other than storage, where approved, additional live load reductions shall be permitted where shown by the registered design professional that a rational approach has been used and that such reductions are warranted.
- A reduction shall not be permitted in passenger vehicle parking garages except that the live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent.
- For live loads not exceeding 100 psf (4.79 kN/m2), the design live load for any structural member supporting 150 square feet (13.94 m2) or more is permitted to be reduced in accordance with Equation 16-24.
- For one-way slabs, the area, A, for use in Equation 16-24 shall not exceed the product of the slab span and a width normal to the span of 0.5 times the slab span.
(Equation 16-24)
For SI: R = 0.861(A — 13.94)
Such reduction shall not exceed the smallest of:
- 40 percent for members supporting one floor.
- 60 percent for members supporting two or more floors.
- R as determined by the following equation:
(Equation 16-25)
where:
A = Area of floor supported by the member, square feet (m2).
D = Dead load per square foot (m2) of area supported.
Lo = Unreduced live load per square foot (m2) of area supported.
R = Reduction in percent.
Ordinary flat, pitched and curved roofs, and awnings and canopies other than of fabric construction supported by a skeleton structure, are permitted to be designed for a reduced uniformly distributed roof live load, Lr, as specified in the following equations or other controlling combinations of loads as specified in Section 1605, whichever produces the greater load effect.
In structures such as greenhouses, where special scaffolding is used as a work surface for workers and materials during maintenance and repair operations, a lower roof load than specified in the following equations shall not be used unless approved by the building official. Such structures shall be designed for a minimum roof live load of 12 psf (0.58 kN/m2).
(Equation 16-26)
where: 12 ≤ Lr ≤ 20
For SI: Lr = Lo R1R2
where: 0.58 ≤ Lr ≤ 0.96
Lo = Unreduced roof live load per square foot (m2) of horizontal projection supported by the member (see Table 1607.1).
Lr = Reduced roof live load per square foot (m2) of horizontal projection supported by the member.
The reduction factors R1 and R2 shall be determined as follows:
(Equation 16-27)
(Equation 16-28)
For SI: 1.2 — 0.011At for 18.58 square meters < At < 55.74 square meters
(Equation 16-29)
where:
At = Tributary area (span length multiplied by effective width) in square feet (m2) supported by the member, and
(Equation 16-30)
(Equation 16-31)
(Equation 16-32)
where:
F = For a sloped roof, the number of inches of rise per foot (for SI: F = 0.12 × slope, with slope expressed as a percentage), or for an arch or dome, the rise-to-span ratio multiplied by 32.
Solar photovoltaic panels or modules that are independent structures and do not have accessible/occupied space underneath are not required to accommodate a roof photovoltaic live load, provided the area under the structure is restricted to keep the public away. All other loads and combinations in accordance with Section 1605 shall be accommodated.
Solar photovoltaic panels or modules that are designed to be the roof, span to structural supports and have accessible/occupied space underneath shall have the panels or modules and all supporting structures designed to support a roof photovoltaic live load, as defined in Section 1607.12.5.1 in combination with other applicable loads. Solar photovoltaic panels or modules in this application are not permitted to be classified as "not accessible" in accordance with Section 1607.12.5.1.
The maximum wheel loads of the crane shall be increased by the percentages shown below to determine the induced vertical impact or vibration force:
Monorail cranes (powered) | 25 percent |
Cab-operated or remotely operated bridge cranes (powered) | 25 percent |
Pendant-operated bridge cranes (powered) | 10 percent |
Bridge cranes or monorail cranes with hand-geared bridge, trolley and hoist | 0 percent |
Fabric partitions that exceed 6 feet (1829 mm) in height, including their finish materials, shall have adequate strength and stiffness to resist the following load conditions:
- The horizontal distributed load need only be applied to the partition framing. The total area used to determine the distributed load shall be the area of the fabric face between the framing members to which the fabric is attached. The total distributed load shall be uniformly applied to such framing members in proportion to the length of each member.
- A concentrated load of 40 pounds (0.176 kN) applied to an 8-inch-diameter (203 mm) area [50.3 square inches (32 452 mm2)] of the fabric face at a height of 54 inches (1372 mm) above the floor.
The ground snow loads to be used in determining the design snow loads for roofs shall be determined in accordance with ASCE 7 or Figure 1608.2 for the contiguous United States and Table 1608.2 for Alaska. Site-specific case studies shall be made in areas designated "CS" in Figure 1608.2. Ground snow loads for sites at elevations above the limits indicated in Figure 1608.2 and for all sites within the CS areas shall be approved. Ground snow load determination for such sites shall be based on an extreme value statistical analysis of data available in the vicinity of the site using a value with a 2-percent annual probability of being exceeded (50-year mean recurrence interval). Snow loads are zero for Hawaii, except in mountainous regions as approved by the building official.
GROUND SNOW LOADS, pg, FOR ALASKAN LOCATIONS
LOCATION | POUNDS PER SQUARE FOOT |
Adak | 30 |
Anchorage | 50 |
Angoon | 70 |
Barrow | 25 |
Barter Island | 35 |
Bethel | 40 |
Big Delta | 50 |
Cold Bay | 25 |
Cordova | 100 |
Fairbanks | 60 |
Fort Yukon | 60 |
Galena | 60 |
Gulkana | 70 |
Homer | 40 |
Juneau | 60 |
Kenai | 70 |
Kodiak | 30 |
Kotzebue | 60 |
McGrath | 70 |
Nenana | 80 |
Nome | 70 |
Palmer | 50 |
Petersburg | 150 |
St. Paul Islands | 40 |
Seward | 50 |
Shemya | 25 |
Sitka | 50 |
Talkeetna | 120 |
Unalakleet | 50 |
Valdez | 160 |
Whittier | 300 |
Wrangell | 60 |
Yakutat | 150 |
For SI: 1 pound per square foot = 0.0479 kN/m2.
GROUND SNOW LOADS, pg, FOR THE UNITED STATES (psf)
GROUND SNOW LOADS, pg, FOR THE UNITED STATES (psf)
Wind loads on every building or structure shall be determined in accordance with Chapters 26 to 30 of ASCE 7 or provisions of the alternate all-heights method in Section 1609.6. The type of opening protection required, the ultimate design wind speed, Vult, and the exposure category for a site is permitted to be determined in accordance with Section 1609 or ASCE 7. Wind shall be assumed to come from any horizontal direction and wind pressures shall be assumed to act normal to the surface considered.
Exceptions:
- Subject to the limitations of Section 1609.1.1.1, the provisions of ICC 600 shall be permitted for applicable Group R-2 and R-3 buildings.
- Subject to the limitations of Section 1609.1.1.1, residential structures using the provisions of AWC WFCM.
- Subject to the limitations of Section 1609.1.1.1, residential structures using the provisions of AISI S230.
- Designs using NAAMM FP 1001.
- Designs using TIA-222 for antenna-supporting structures and antennas, provided the horizontal extent of Topographic Category 2 escarpments in Section 2.6.6.2 of TIA-222 shall be 16 times the height of the escarpment.
- Wind tunnel tests in accordance with ASCE 49 and Sections 31.4 and 31.5 of ASCE 7.
The wind speeds in Figures 1609.3(1), 1609.3(2) and 1609.3(3) are ultimate design wind speeds, Vult, and shall be converted in accordance with Section 1609.3.1 to nominal design wind speeds, Vasd, when the provisions of the standards referenced in Exceptions 4 and 5 are used.
The provisions of ICC 600 are applicable only to buildings located within Exposure B or C as defined in Section 1609.4. The provisions of ICC 600, AWC WFCM and AISI S230 shall not apply to buildings sited on the upper half of an isolated hill, ridge or escarpment meeting the following conditions:
- The hill, ridge or escarpment is 60 feet (18 288 mm) or higher if located in Exposure B or 30 feet (9144 mm) or higher if located in Exposure C;
- The maximum average slope of the hill exceeds 10 percent; and
- The hill, ridge or escarpment is unobstructed upwind by other such topographic features for a distance from the high point of 50 times the height of the hill or 1 mile (1.61 km), whichever is greater.
In wind-borne debris regions, glazing in buildings shall be impact resistant or protected with an impact-resistant covering meeting the requirements of an approved impact-resistant standard or ASTM E1996 and ASTM E1886 referenced herein as follows:
- Glazed openings located within 30 feet (9144 mm) of grade shall meet the requirements of the large missile test of ASTM E1996.
- Glazed openings located more than 30 feet (9144 mm) above grade shall meet the provisions of the small missile test of ASTM E1996.
Exceptions:
- Wood structural panels with a minimum thickness of 7/16 inch (11.1 mm) and maximum panel span of 8 feet (2438 mm) shall be permitted for opening protection in buildings with a mean roof height of 33 feet (10 058 mm) or less that are classified as a Group R-3 or R-4 occupancy. Panels shall be precut so that they shall be attached to the framing surrounding the opening containing the product with the glazed opening. Panels shall be predrilled as required for the anchorage method and shall be secured with the attachment hardware provided. Attachments shall be designed to resist the components and cladding loads determined in accordance with the provisions of ASCE 7, with corrosion-resistant attachment hardware provided and anchors permanently installed on the building. Attachment in accordance with Table 1609.1.2 with corrosion-resistant attachment hardware provided and anchors permanently installed on the building is permitted for buildings with a mean roof height of 45 feet (13 716 mm) or less where Vasd determined in accordance with Section 1609.3.1 does not exceed 140 mph (63 m/s).
- Glazing in Risk Category I buildings, including greenhouses that are occupied for growing plants on a production or research basis, without public access shall be permitted to be unprotected.
- Glazing in Risk Category II, III or IV buildings located over 60 feet (18 288 mm) above the ground and over 30 feet (9144 mm) above aggregate surface roofs located within 1,500 feet (458 m) of the building shall be permitted to be unprotected.
WIND-BORNE DEBRIS PROTECTION FASTENING SCHEDULE FOR WOOD STRUCTURAL PANELSa, b, c, d
FASTENER TYPE | FASTENER SPACING (inches) | ||
Panel Span ≤ 4 feet | 4 feet < Panel Span ≤ 6 feet | 6 feet < Panel Span ≤ 8 feet | |
No. 8 wood-screw-based anchor with 2-inch embedment length | 16 | 10 | 8 |
No. 10 wood-screw-based anchor with 2-inch embedment length | 16 | 12 | 9 |
1/4-inch diameter lag-screw-based anchor with 2-inch embedment length | 16 | 16 | 16 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N,
1 mile per hour = 0.447 m/s.
- This table is based on 140 mph wind speeds and a 45-foot mean roof height.
- Fasteners shall be installed at opposing ends of the wood structural panel. Fasteners shall be located a minimum of 1 inch from the edge of the panel.
- Anchors shall penetrate through the exterior wall covering with an embedment length of 2 inches minimum into the building frame. Fasteners shall be located a minimum of 21/2 inches from the edge of concrete block or concrete.
- Where panels are attached to masonry or masonry/stucco, they shall be attached using vibration-resistant anchors having a minimum ultimate withdrawal capacity of 1,500 pounds.
The text of Section 6.2.2 of ASTM E1996 shall be substituted as follows:
6.2.2 Unless otherwise specified, select the wind zone based on the strength design wind speed, Vult, as follows:
6.2.2.1 Wind Zone 1—130 mph ≤ ultimate design wind speed, Vult < 140 mph.
6.2.2.2 Wind Zone 2—140 mph ≤ ultimate design wind speed, Vult < 150 mph at greater than one mile (1.6 km) from the coastline. The coastline shall be measured from the mean high water mark.
6.2.2.3 Wind Zone 3—150 mph (58 m/s) ≤ ultimate design wind speed, Vult ≤ 160 mph (63 m/s), or 140 mph (54 m/s) ≤ ultimate design wind speed, Vult ≤ 160 mph (63 m/s) and within one mile (1.6 km) of the coastline. The coastline shall be measured from the mean high water mark.
6.2.2.4 Wind Zone 4— ultimate design wind speed, Vult > 160 mph (63 m/s).
For the purposes of Section 1609 and as used elsewhere in this code, the following terms are defined in Chapter 2.
WIND SPEED, Vult.
WIND SPEED, Vasd.
The ultimate design wind speed, Vult, in mph, for the determination of the wind loads shall be determined by Figures 1609.3(1), 1609.3(2) and 1609.3(3). The ultimate design wind speed, Vult, for use in the design of Risk Category II buildings and structures shall be obtained from Figure 1609.3(1). The ultimate design wind speed, Vult, for use in the design of Risk Category III and IV buildings and structures shall be obtained from Figure 1609.3(2). The ultimate design wind speed, Vult, for use in the design of Risk Category I buildings and structures shall be obtained from Figure 1609.3(3). The ultimate design wind speed, Vult, for the special wind regions indicated near mountainous terrain and near gorges shall be in accordance with local jurisdiction requirements. The ultimate design wind speeds, Vult, determined by the local jurisdiction shall be in accordance with Section 26.5.1 of ASCE 7.
In nonhurricane-prone regions, when the ultimate design wind speed, Vult, is estimated from regional climatic data, the ultimate design wind speed, Vult, shall be determined in accordance with Section 26.5.3 of ASCE 7.
Notes:
- Values are nominal design 3-second gust wind speeds in miles per hour (m/s) at 33 ft (10m) above ground for Exposure C category.
- Linear interpolation between contours is permitted.
- Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area.
- Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions.
- Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (Annual Exceedance Probability = 0.00143, MRI = 700 Years).
ULTIMATE DESIGN WIND SPEEDS, VULT, FOR RISK CATEGORY II BUILDINGS AND OTHER STRUCTURES
Notes:
- Values are nominal design 3-second gust wind speeds in miles per hour (m/s) at 33 ft (10m) above ground for Exposure C category.
- Linear interpolation between contours is permitted.
- Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area.
- Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions.
- Wind speeds correspond to approximately a 3% probability of exceedance in 50 years (Annual Exceedance Probability = 0.000588, MRI = 1700 Years).
ULTIMATE DESIGN WIND SPEEDS, VULT, FOR RISK CATEGORY III AND IV BUILDINGS AND OTHER STRUCTURES
Notes:
- Values are nominal design 3-second gust wind speeds in miles per hour (m/s) at 33 ft (10m) above ground for Exposure C category.
- Linear interpolation between contours is permitted.
- Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area.
- Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions.
- Wind speeds correspond to approximately a 15% probability of exceedance in 50 years (Annual Exceedance Probability = 0.00333, MRI = 300 Years).
ULTIMATE DESIGN WIND SPEEDS, VULT, FOR RISK CATEGORY I BUILDINGS AND OTHER STRUCTURES
When required, the ultimate design wind speeds of Figures 1609.3(1), 1609.3(2) and 1609.3(3) shall be converted to nominal design wind speeds, Vasd, using Table 1609.3.1 or Equation 16-33.
(Equation 16-33)
where:
Vasd = Nominal design wind speed applicable to methods specified in Exceptions 4 and 5 of Section 1609.1.1.
Vult = Ultimate design wind speeds determined from Figures 1609.3(1), 1609.3(2) or 1609.3(3).
WIND SPEED CONVERSIONSa, b, c
Vult | 100 | 110 | 120 | 130 | 140 | 150 | 160 | 170 | 180 | 190 | 200 |
Vasd | 78 | 85 | 93 | 101 | 108 | 116 | 124 | 132 | 139 | 147 | 155 |
For SI: 1 mile per hour = 0.44 m/s.
- Linear interpolation is permitted.
- Vasd = nominal design wind speed applicable to methods specified in Exceptions 1 through 5 of Section 1609.1.1.
- Vult = ultimate design wind speeds determined from Figure 1609.3(1), 1609.3(2) or 1609.3(3).
A ground surface roughness within each 45-degree (0.79 rad) sector shall be determined for a distance upwind of the site as defined in Section 1609.4.3 from the categories defined below, for the purpose of assigning an exposure category as defined in Section 1609.4.3.
Surface Roughness B. Urban and suburban areas, wooded areas or other terrain with numerous closely spaced obstructions having the size of single-family dwellings or larger.
Surface Roughness C. Open terrain with scattered obstructions having heights generally less than 30 feet (9144 mm). This category includes flat open country, and grasslands.
Surface Roughness D. Flat, unobstructed areas and water surfaces. This category includes smooth mud flats, salt flats and unbroken ice.
An exposure category shall be determined in accordance with the following:
Exposure B. For buildings with a mean roof height of less than or equal to 30 feet (9144 mm), Exposure B shall apply where the ground surface roughness, as defined by Surface Roughness B, prevails in the upwind direction for a distance of at least 1,500 feet (457 m). For buildings with a mean roof height greater than 30 feet (9144 mm), Exposure B shall apply where Surface Roughness B prevails in the upwind direction for a distance of at least 2,600 feet (792 m) or 20 times the height of the building, whichever is greater.
Exposure C. Exposure C shall apply for all cases where Exposure B or D does not apply.
Exposure D. Exposure D shall apply where the ground surface roughness, as defined by Surface Roughness D, prevails in the upwind direction for a distance of at least 5,000 feet (1524 m) or 20 times the height of the building, whichever is greater. Exposure D shall also apply where the ground surface roughness immediately upwind of the site is B or C, and the site is within a distance of 600 feet (183 m) or 20 times the building height, whichever is greater, from an Exposure D condition as defined in the previous sentence.
Roof coverings shall comply with Section 1609.5.1.
Exception: Rigid tile roof coverings that are air permeable and installed over a roof deck complying with Section 1609.5.1 are permitted to be designed in accordance with Section 1609.5.3.
Asphalt shingles installed over a roof deck complying with Section 1609.5.1 shall comply with the wind-resistance requirements of Section 1504.1.1.
Wind loads on rigid tile roof coverings shall be determined in accordance with the following equation:
(Equation 16-34)
For SI:
where:
b = Exposed width, feet (mm) of the roof tile.
CL = Lift coefficient. The lift coefficient for concrete and clay tile shall be 0.2 or shall be determined by test in accordance with Section 1711.2.
GCp = Roof pressure coefficient for each applicable roof zone determined from Chapter 30 of ASCE 7. Roof coefficients shall not be adjusted for internal pressure.
L = Length, feet (mm) of the roof tile.
La = Moment arm, feet (mm) from the axis of rotation to the point of uplift on the roof tile. The point of uplift shall be taken at 0.76L from the head of the tile and the middle of the exposed width. For roof tiles with nails or screws (with or without a tail clip), the axis of rotation shall be taken as the head of the tile for direct deck application or as the top edge of the batten for battened applications. For roof tiles fastened only by a nail or screw along the side of the tile, the axis of rotation shall be determined by testing. For roof tiles installed with battens and fastened only by a clip near the tail of the tile, the moment arm shall be determined about the top edge of the batten with consideration given for the point of rotation of the tiles based on straight bond or broken bond and the tile profile.
Ma = Aerodynamic uplift moment, feet-pounds (N-mm) acting to raise the tail of the tile.
qh = Wind velocity pressure, psf (kN/m2) determined from Section 27.3.2 of ASCE 7.
Concrete and clay roof tiles complying with the following limitations shall be designed to withstand the aerodynamic uplift moment as determined by this section.
- The roof tiles shall be either loose laid on battens, mechanically fastened, mortar set or adhesive set.
- The roof tiles shall be installed on solid sheathing which has been designed as components and cladding.
- An underlayment shall be installed in accordance with Chapter 15.
- The tile shall be single lapped interlocking with a minimum head lap of not less than 2 inches (51 mm).
- The length of the tile shall be between 1.0 and 1.75 feet (305 mm and 533 mm).
- The exposed width of the tile shall be between 0.67 and 1.25 feet (204 mm and 381 mm).
- The maximum thickness of the tail of the tile shall not exceed 1.3 inches (33 mm).
- Roof tiles using mortar set or adhesive set systems shall have at least two-thirds of the tile's area free of mortar or adhesive contact.
As an alternative to ASCE 7 Chapters 27 and 30, the following provisions are permitted to be used to determine the wind effects on regularly shaped buildings, or other structures that are regularly shaped, that meet all of the following conditions:
- The building or other structure is less than or equal to 75 feet (22 860 mm) in height with a height-to-least-width ratio of 4 or less, or the building or other structure has a fundamental frequency greater than or equal to 1 hertz.
- The building or other structure is not sensitive to dynamic effects.
- The building or other structure is not located on a site for which channeling effects or buffeting in the wake of upwind obstructions warrant special consideration.
- The building shall meet the requirements of a simple diaphragm building as defined in ASCE 7 Section 26.2, where wind loads are only transmitted to the main windforce-resisting system (MWFRS) at the diaphragms.
- For open buildings, multispan gable roofs, stepped roofs, sawtooth roofs, domed roofs, roofs with slopes greater than 45 degrees (0.79 rad), solid free-standing walls and solid signs, and rooftop equipment, apply ASCE 7 provisions.
Coefficients and variables used in the alternative all-heights method equations are as follows:
Cnet | = | Net-pressure coefficient based on Kd [(G) (Cp) - (GCpi)], in accordance with Table 1609.6.2. |
G | = | Gust effect factor for rigid structures in accordance with ASCE 7 Section 26.9.1. |
Kd | = | Wind directionality factor in accordance with ASCE 7 Table 26-6. |
Pnet | = | Design wind pressure to be used in determination of wind loads on buildings or other structures or their components and cladding, in psf (kN/m2). |
NET PRESSURE COEFFICIENTS, Cneta, b
STRUCTURE OR PART THEREOF | DESCRIPTION | Cnet FACTOR | ||||
1. Main windforce-resisting frames and systems | Walls: | Enclosed | Partially enclosed | |||
+ Internal pressure | - Internal pressure | + Internal pressure | - Internal pressure | |||
Windward wall | 0.43 | 0.73 | 0.11 | 1.05 | ||
Leeward wall | -0.51 | -0.21 | -0.83 | 0.11 | ||
Sidewall | -0.66 | -0.35 | -0.97 | -0.04 | ||
Parapet wall | Windward | 1.28 | 1.28 | |||
Leeward | -0.85 | -0.85 | ||||
Roofs: | Enclosed | Partially enclosed | ||||
Wind perpendicular to ridge | + Internal pressure | - Internal pressure | + Internal pressure | - Internal pressure | ||
Leeward roof or flat roof | -0.66 | -0.35 | -0.97 | -0.04 | ||
Windward roof slopes: | ||||||
Slope < 2:12 (10°) | Condition 1 | -1.09 | -0.79 | -1.41 | -0.47 | |
Condition 2 | -0.28 | 0.02 | -0.60 | 0.34 | ||
Slope = 4:12 (18°) | Condition 1 | -0.73 | -0.42 | -1.04 | -0.11 | |
Condition 2 | -0.05 | 0.25 | -0.37 | 0.57 | ||
Slope = 5:12 (23°) | Condition 1 | -0.58 | -0.28 | -0.90 | 0.04 | |
Condition 2 | 0.03 | 0.34 | -0.29 | 0.65 | ||
Slope = 6:12 (27°) | Condition 1 | -0.47 | -0.16 | -0.78 | 0.15 | |
Condition 2 | 0.06 | 0.37 | -0.25 | 0.68 | ||
Slope = 7:12 (30°) | Condition 1 | -0.37 | -0.06 | -0.68 | 0.25 | |
Condition 2 | 0.07 | 0.37 | -0.25 | 0.69 | ||
Slope = 9:12 (37°) | Condition 1 | -0.27 | 0.04 | -0.58 | 0.35 | |
Condition 2 | 0.14 | 0.44 | -0.18 | 0.76 | ||
Slope = 12:12 (45°) | 0.14 | 0.44 | -0.18 | 0.76 | ||
Wind parallel to ridge and flat roofs | -1.09 | -0.79 | -1.41 | -0.47 | ||
Nonbuilding Structures: Chimneys, Tanks and Similar Structures: | ||||||
h/D | ||||||
1 | 7 | 25 | ||||
Square (Wind normal to face) | 0.99 | 1.07 | 1.53 | |||
Square (Wind on diagonal) | 0.77 | 0.84 | 1.15 | |||
Hexagonal or Octagonal | 0.81 | 0.97 | 1.13 | |||
Round | 0.65 | 0.81 | 0.97 | |||
Open signs and lattice frameworks | Ratio of solid to gross area | |||||
< 0.1 | 0.1 to 0.29 | 0.3 to 0.7 | ||||
Flat | 1.45 | 1.30 | 1.16 | |||
Round | 0.87 | 0.94 | 1.08 |
STRUCTURE OR PART THEREOF | DESCRIPTION | Cnet FACTOR | ||||
2. Components and cladding not in areas of discontinuity—roofs and overhangs | Roof elements and slopes | Enclosed | Partially enclosed | |||
Gable of hipped configurations (Zone 1) | ||||||
Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2B Zone 1 | ||||||
Positive | 10 square feet or less | 0.58 | 0.89 | |||
100 square feet or more | 0.41 | 0.72 | ||||
Negative | 10 square feet or less | -1.00 | -1.32 | |||
100 square feet or more | -0.92 | -1.23 | ||||
Overhang: Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2A Zone 1 | ||||||
Negative | 10 square feet or less | -1.45 | ||||
100 square feet or more | -1.36 | |||||
500 square feet or more | -0.94 | |||||
6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 30.4-2C Zone 1 | ||||||
Positive | 10 square feet or less | 0.92 | 1.23 | |||
100 square feet or more | 0.83 | 1.15 | ||||
Negative | 10 square feet or less | -1.00 | -1.32 | |||
100 square feet or more | -0.83 | -1.15 | ||||
Monosloped configurations (Zone 1) | Enclosed | Partially enclosed | ||||
Flat < Slope < 7:12 (30°) See ASCE 7 Figure 30.4-5B Zone 1 | ||||||
Positive | 10 square feet or less | 0.49 | 0.81 | |||
100 square feet or more | 0.41 | 0.72 | ||||
Negative | 10 square feet or less | -1.26 | -1.57 | |||
100 square feet or more | -1.09 | -1.40 | ||||
Tall flat-topped roofs h > 60 feet | Enclosed | Partially enclosed | ||||
Flat < Slope < 2:12 (10°) (Zone 1) See ASCE 7 Figure 30.8-1 Zone 1 | ||||||
Negative | 10 square feet or less | -1.34 | -1.66 | |||
500 square feet or more | -0.92 | -1.23 | ||||
3. Components and cladding in areas of discontinuities— roofs and overhangs | Gable or hipped configurations at ridges, eaves and rakes (Zone 2) | |||||
Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2B Zone 2 | ||||||
Positive | 10 square feet or less | 0.58 | 0.89 | |||
100 square feet or more | 0.41 | 10.72 | ||||
Negative | 10 square feet or less | -1.68 | -2.00 | |||
100 square feet or more | -1.17 | -1.49 | ||||
Overhang for Slope Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2B Zone 2 | ||||||
Negative | 10 square feet or less | -1.87 | ||||
100 square feet or more | -1.87 | |||||
6:12 (27°) < Slope < 12:12 (45°) Figure 30.4-2C | Enclosed | Partially enclosed | ||||
Positive | 10 square feet or less | 0.92 | 1.23 | |||
100 square feet or more | 0.83 | 1.15 | ||||
Negative | 10 square feet or less | -1.17 | -1.49 | |||
100 square feet or more | -1.00 | -1.32 | ||||
Overhang for 6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 30.4-2C Zone 2 | ||||||
Negative | 10 square feet or less | -1.70 | ||||
500 square feet or more | -1.53 | |||||
Monosloped configurations at ridges, eaves and rakes (Zone 2) | ||||||
Flat < Slope < 7:12 (30°) See ASCE 7 Figure 30.4-5B Zone 2 | ||||||
Positive | 10 square feet or less | 0.49 | 0.81 | |||
100 square feet or more | 0.41 | 0.72 | ||||
Negative | 10 square feet or less | -1.51 | -1.83 | |||
100 square feet or more | -1.43 | -1.74 | ||||
Tall flat topped roofs h > 60 feet | Enclosed | Partially enclosed | ||||
Flat < Slope < 2:12 (10°) (Zone 2) See ASCE 7 Figure 30.8-1 Zone 2 | ||||||
Negative | 10 square feet or less | -2.11 | -2.42 | |||
500 square feet or more | -1.51 | -1.83 | ||||
Gable or hipped configurations at corners (Zone 3) See ASCE 7 Figure 30.4-2B Zone 3 | ||||||
Flat < Slope < 6:12 (27°) | Enclosed | Partially enclosed | ||||
Positive | 10 square feet or less | 0.58 | 0.89 | |||
100 square feet or more | 0.41 | 0.72 | ||||
Negative | 10 square feet or less | -2.53 | -2.85 | |||
100 square feet or more | -1.85 | -2.17 | ||||
Overhang for Slope Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2B Zone 3 | ||||||
Negative | 10 square feet or less | -3.15 | ||||
100 square feet or more | -2.13 | |||||
6:12 (27°) < 12:12 (45°) See ASCE 7 Figure 30.4-2C Zone 3 | ||||||
Positive | 10 square feet or less | 0.92 | 1.23 | |||
100 square feet or more | 0.83 | 1.15 | ||||
Negative | 10 square feet or less | -1.17 | -1.49 | |||
100 square feet or more | -1.00 | -1.32 | ||||
Overhang for 6:12 (27°) < Slope < 12:12 (45°) | Enclosed | Partially enclosed | ||||
Negative | 10 square feet or less | -1.70 | ||||
100 square feet or more | -1.53 | |||||
Monosloped Configurations at corners (Zone 3) See ASCE 7 Figure 30.4-5B Zone 3 | ||||||
Flat < Slope < 7:12 (30°) | ||||||
Positive | 10 square feet or less | 0.49 | 0.81 | |||
100 square feet or more | 0.41 | 0.72 | ||||
Negative | 10 square feet or less | -2.62 | -2.93 | |||
100 square feet or more | -1.85 | -2.17 | ||||
Tall flat topped roofs h > 60 feet | Enclosed | Partially enclosed | ||||
Flat < Slope < 2:12 (10°) (Zone 3) See ASCE 7 Figure 30.8-1 Zone 3 | ||||||
Negative | 10 square feet or less | -2.87 | -3.19 | |||
500 square feet or more | -2.11 | -2.42 | ||||
4. Components and cladding not in areas of discontinuity—walls and parapets | Wall Elements: h ≤ 60 feet (Zone 4) Figure 30.4-1 | Enclosed | Partially enclosed | |||
Positive | 10 square feet or less | 1.00 | 1.32 | |||
500 square feet or more | 0.75 | 1.06 | ||||
Negative | 10 square feet or less | -1.09 | -1.40 | |||
500 square feet or more | -0.83 | -1.15 | ||||
Wall Elements: h > 60 feet (Zone 4) See ASCE 7 Figure 30.8-1 Zone 4 | ||||||
Positive | 20 square feet or less | 0.92 | 1.23 | |||
500 square feet or more | 0.66 | 0.98 | ||||
Negative | 20 square feet or less | -0.92 | -1.23 | |||
500 square feet or more | -0.75 | -1.06 | ||||
Parapet Walls | ||||||
Positive | 2.87 | 3.19 | ||||
Negative | -1.68 | -2.00 | ||||
5. Components and cladding in areas of discontinuity—walls and parapets | Wall elements: h ≤ 60 feet (Zone 5) Figure 30.4-1 | Enclosed | Partially enclosed | |||
Positive | 10 square feet or less | 1.00 | 1.32 | |||
500 square feet or more | 0.75 | 1.06 | ||||
Negative | 10 square feet or less | -1.34 | -1.66 | |||
500 square feet or more | -0.83 | -1.15 | ||||
Wall elements: h > 60 feet (Zone 5) See ASCE 7 Figure 30.8-1 Zone 4 | ||||||
Positive | 20 square feet or less | 0.92 | 1.23 | |||
500 square feet or more | 0.66 | 0.98 | ||||
Negative | 20 square feet or less | -1.68 | -2.00 | |||
500 square feet or more | -1.00 | -1.32 | ||||
Parapet walls | ||||||
Positive | 3.64 | 3.95 | ||||
Negative | -2.45 | -2.76 |
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929m2, 1 degree = 0.0175 rad.
- Linear interpolation between values in the table is permitted.
- Some Cnet values have been grouped together. Less conservative results may be obtained by applying ASCE 7 provisions.
When using the alternative all-heights method, the MWFRS, and components and cladding of every structure shall be designed to resist the effects of wind pressures on the building envelope in accordance with Equation 16-35.
(Equation 16-35)
Design wind forces for the MWFRS shall be not less than 16 psf (0.77 kN/m2) multiplied by the area of the structure projected on a plane normal to the assumed wind direction (see ASCE 7 Section 27.4.7 for criteria). Design net wind pressure for components and cladding shall be not less than 16 psf (0.77 kN/m2) acting in either direction normal to the surface.
Velocity pressure exposure coefficient, Kz, shall be determined in accordance with ASCE 7 Section 27.3.1 and the topographic factor, Kzt, shall be determined in accordance with ASCE 7 Section 26.8.
- For the windward side of a structure, Kzt and Kz shall be based on height z.
- For leeward and sidewalls, and for windward and leeward roofs, Kzt and Kz shall be based on mean roof height h.
For the design of the MWFRS and for components and cladding, the sum of the internal and external net pressure shall be based on the net pressure coefficient, Cnet.
- The pressure coefficient, Cnet, for walls and roofs shall be determined from Table 1609.6.2.
- Where Cnet has more than one value, the more severe wind load condition shall be used for design.
Wind pressure for each component or cladding element is applied as follows using Cnet values based on the effective wind area, A, contained within the zones in areas of discontinuity of width and/or length "a," "2a" or "4a" at: corners of roofs and walls; edge strips for ridges, rakes and eaves; or field areas on walls or roofs as indicated in figures in tables in ASCE 7 as referenced in Table 1609.6.2 in accordance with the following:
- Calculated pressures at local discontinuities acting over specific edge strips or corner boundary areas.
- Include "field" (Zone 1, 2 or 4, as applicable) pressures applied to areas beyond the boundaries of the areas of discontinuity.
- Where applicable, the calculated pressures at discontinuities (Zone 2 or 3) shall be combined with design pressures that apply specifically on rakes or eave overhangs.
Foundation walls and retaining walls shall be designed to resist lateral soil loads. Soil loads specified in Table 1610.1 shall be used as the minimum design lateral soil loads unless determined otherwise by a geotechnical investigation in accordance with Section 1803. Foundation walls and other walls in which horizontal movement is restricted at the top shall be designed for at-rest pressure. Retaining walls free to move and rotate at the top shall be permitted to be designed for active pressure. Design lateral pressure from surcharge loads shall be added to the lateral earth pressure load. Design lateral pressure shall be increased if soils at the site are expansive. Foundation walls shall be designed to support the weight of the full hydrostatic pressure of undrained backfill unless a drainage system is installed in accordance with Sections 1805.4.2 and 1805.4.3.
Exception: Foundation walls extending not more than 8 feet (2438 mm) below grade and laterally supported at the top by flexible diaphragms shall be permitted to be designed for active pressure.
LATERAL SOIL LOAD
DESCRIPTION OF BACKFILL MATERIALc | UNIFIED SOIL CLASSIFICATION | DESIGN LATERAL SOIL LOADa (pound per square foot per foot of depth) | |
Active pressure | At-rest pressure | ||
Well-graded, clean gravels; gravel-sand mixes | GW | 30 | 60 |
Poorly graded clean gravels; gravel-sand mixes | GP | 30 | 60 |
Silty gravels, poorly graded gravel-sand mixes | GM | 40 | 60 |
Clayey gravels, poorly graded gravel-and-clay mixes | GC | 45 | 60 |
Well-graded, clean sands; gravelly sand mixes | SW | 30 | 60 |
Poorly graded clean sands; sand-gravel mixes | SP | 30 | 60 |
Silty sands, poorly graded sand-silt mixes | SM | 45 | 60 |
Sand-silt clay mix with plastic fines | SM-SC | 45 | 100 |
Clayey sands, poorly graded sand-clay mixes | SC | 60 | 100 |
Inorganic silts and clayey silts | ML | 45 | 100 |
Mixture of inorganic silt and clay | ML-CL | 60 | 100 |
Inorganic clays of low to medium plasticity | CL | 60 | 100 |
Organic silts and silt clays, low plasticity | OL | Note b | Note b |
Inorganic clayey silts, elastic silts | MH | Note b | Note b |
Inorganic clays of high plasticity | CH | Note b | Note b |
Organic clays and silty clays | OH | Note b | Note b |
For SI: 1 pound per square foot per foot of depth = 0.157 kPa/m, 1 foot = 304.8 mm.
- Design lateral soil loads are given for moist conditions for the specified soils at their optimum densities. Actual field conditions shall govern. Submerged or saturated soil pressures shall include the weight of the buoyant soil plus the hydrostatic loads.
- Unsuitable as backfill material.
- The definition and classification of soil materials shall be in accordance with ASTM D2487.
Each portion of a roof shall be designed to sustain the load of rainwater that will accumulate on it if the primary drainage system for that portion is blocked plus the uniform load caused by water that rises above the inlet of the secondary drainage system at its design flow. The design rainfall shall be based on the 100-year hourly rainfall rate indicated in Figure 1611.1 or on other rainfall rates determined from approved local weather data.
(Equation 16-36)
For SI: R = 0.0098(ds + dh)
where:
dh = Additional depth of water on the undeflected roof above the inlet of secondary drainage system at its design flow (i.e., the hydraulic head), in inches (mm).
ds = Depth of water on the undeflected roof up to the inlet of secondary drainage system when the primary drainage system is blocked (i.e., the static head), in inches (mm).
R = Rain load on the undeflected roof, in psf (kN/m2). When the phrase "undeflected roof" is used, deflections from loads (including dead loads) shall not be considered when determining the amount of rain on the roof.
[P] FIGURE 1611.1
100-YEAR, 1-HOUR RAINFALL (INCHES) WESTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
[P] FIGURE 1611.1
100-YEAR, 1-HOUR RAINFALL (INCHES) CENTRAL UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
[P] FIGURE 1611.1
100-YEAR, 1-HOUR RAINFALL (INCHES) EASTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
[P] FIGURE 1611.1
100-YEAR, 1-HOUR RAINFALL (INCHES) ALASKA
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
[P] FIGURE 1611.1
100-YEAR, 1-HOUR RAINFALL (INCHES) HAWAII
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
The following terms are defined in Chapter 2:
FLOOD DAMAGE-RESISTANT MATERIALS.
FLOOD INSURANCE RATE MAP (FIRM).
To establish flood hazard areas, the applicable governing authority shall adopt a flood hazard map and supporting data. The flood hazard map shall include, at a minimum, areas of special flood hazard as identified by the Federal Emergency Management Agency in an engineering report entitled "The Flood Insurance Study for [INSERT NAME OF JURISDICTION]," dated [INSERT DATE OF ISSUANCE], as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and related supporting data along with any revisions thereto. The adopted flood hazard map and supporting data are hereby adopted by reference and declared to be part of this section.
Exception: [OSHPD 2] The flood hazard map shall include, at a minimum, areas of special flood hazard as identified by the Federal Emergency Management Agency's Flood Insurance Study (FIS) adopted by the local authority having jurisdiction where the project is located.
Where design flood elevations are not included in the flood hazard areas established in Section 1612.3, or where floodways are not designated, the building official is authorized to require the applicant to:
- Obtain and reasonably utilize any design flood elevation and floodway data available from a federal, state or other source; or
- Determine the design flood elevation and/or floodway in accordance with accepted hydrologic and hydraulic engineering practices used to define special flood hazard areas. Determinations shall be undertaken by a registered design professional who shall document that the technical methods used reflect currently accepted engineering practice.
The following documentation shall be prepared and sealed by a registered design professional and submitted to the building official:
For construction in flood hazard areas other than coastal high hazard areas or coastal A zones:
- 1.1. The elevation of the lowest floor, including the basement, as required by the lowest floor elevation inspection in Section 110.3.3 and for the final inspection in Section 110.3.10.1.
- 1.2. For fully enclosed areas below the design flood elevation where provisions to allow for the automatic entry and exit of floodwaters do not meet the minimum requirements in Section 2.6.2.1 of ASCE 24, construction documents shall include a statement that the design will provide for equalization of hydrostatic flood forces in accordance with Section 2.6.2.2 of ASCE 24.
- 1.3. For dry floodproofed nonresidential buildings, construction documents shall include a statement that the dry floodproofing is designed in accordance with ASCE 24.
For construction in coastal high hazard areas and coastal A zones:
- 2.1. The elevation of the bottom of the lowest horizontal structural member as required by the lowest floor elevation inspection in Section 110.3.3 and for the final inspection in Section 110.3.10.1.
- 2.2. Construction documents shall include a statement that the building is designed in accordance with ASCE 24, including that the pile or column foundation and building or structure to be attached thereto is designed to be anchored to resist flotation, collapse and lateral movement due to the effects of wind and flood loads acting simultaneously on all building components, and other load requirements of Chapter 16.
- 2.3. For breakaway walls designed to have a resistance of more than 20 psf (0.96 kN/m2) determined using allowable stress design, construction documents shall include a statement that the breakaway wall is designed in accordance with ASCE 24.
Every structure, and portion thereof, including nonstructural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with ASCE 7, excluding Chapter 14 and Appendix 11A. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7.
Exceptions:
- Detached one- and two-family dwellings, assigned to Seismic Design Category A, B or C, or located where the mapped short-period spectral response acceleration, SS, is less than 0.4 g.
- The seismic force-resisting system of wood-frame buildings that conform to the provisions of Section 2308 are not required to be analyzed as specified in this section. [OSHPD 2] Not permitted by OSHPD, see Section 2308.
- Agricultural storage structures intended only for incidental human occupancy.
- Structures that require special consideration of their response characteristics and environment that are not addressed by this code or ASCE 7 and for which other regulations provide seismic criteria, such as vehicular bridges, electrical transmission towers, hydraulic structures, buried utility lines and their appurtenances and nuclear reactors.
- [OSHPD 2] Seismic Design Category shall be in accordance with exception to Section 1613.3.5.
[SL] For applications listed in Section 1.12 regulated by the State Librarian, only the provisions of ASCE 7 Tables 13.5-1 and 1607.1, as amended, of this code shall apply.
[BSC] State-owned buildings, including those of the University of California, CSU and Judicial Council, shall not be constructed where any portion of the foundation would be within a mapped area of earthquake-induced liquefaction or landsliding or within 50 feet of a mapped fault rupture hazard as established by Section 1803.7.
[BSC] Additions, alterations, repairs or change of occupancy category of existing buildings shall be in accordance with the California Existing Building Code, Part 10.
The following terms are defined in Chapter 2:
- DESIGN EARTHQUAKE GROUND MOTION.
- MECHANICAL SYSTEMS.
- ORTHOGONAL.
- RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATION.
- SEISMIC DESIGN CATEGORY.
- SEISMIC FORCE-RESISTING SYSTEM.
- SITE CLASS.
- SITE COEFFICIENTS.
The parameters SS and S1 shall be determined from the 0.2 and 1-second spectral response accelerations shown on Figures 1613.3.1(1) through 1613.3.1(6). Where S1 is less than or equal to 0.04 and SS is less than or equal to 0.15, the structure is permitted to be assigned Seismic Design Category A.
Exception: [OSHPD 2] Seismic Design Category shall be in accordance with exception to Section 1613.3.5.
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS FOR THE CONTERMINOUS UNITED STATES OF 0.2-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS FOR THE CONTERMINOUS UNITED STATES OF 0.2-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS FOR THE CONTERMINOUS UNITED STATES OF 1-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS FOR THE CONTERMINOUS UNITED STATES OF 1-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS FOR HAWAII OF 0.2- AND 1-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS FOR ALASKA OF 0.2-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS FOR ALASKA OF 1.0-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS FOR PUERTO RICO AND THE UNITED STATES VIRGIN ISLANDS OF 0.2- AND 1-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
Based on the site soil properties, the site shall be classified as Site Class A, B, C, D, E or F in accordance with Chapter 20 of ASCE 7.
Where the soil properties are not known in sufficient detail to determine the site class, Site Class D shall be used unless the building official or geotechnical data determines Site Class E or F soils are present at the site.
The maximum considered earthquake spectral response acceleration for short periods, SMS, and at 1-second period, SM1, adjusted for site class effects shall be determined by Equations 16-37 and 16-38, respectively:
(Equation 16-37)
(Equation 16-38)
where:
Fa = Site coefficient defined in Table 1613.3.3(1).
Fv = Site coefficient defined in Table 1613.3.3(2).
SS = The mapped spectral accelerations for short periods as determined in Section 1613.3.1.
S1 = The mapped spectral accelerations for a 1-second period as determined in Section 1613.3.1.
VALUES OF SITE COEFFICIENT Fa a
SITE CLASS | MAPPED SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD | ||||
Ss ≤ 0.25 | Ss = 0.50 | Ss = 0.75 | Ss = 1.00 | Ss ≥ 1.25 | |
A | 0.8 | 0.8 | 0.8 | 0.8 | 0.8 |
B | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
C | 1.2 | 1.2 | 1.1 | 1.0 | 1.0 |
D | 1.6 | 1.4 | 1.2 | 1.1 | 1.0 |
E | 2.5 | 1.7 | 1.2 | 0.9 | 0.9 |
F | Note b | Note b | Note b | Note b | Note b |
- Use straight-line interpolation for intermediate values of mapped spectral response acceleration at short period, Ss.
- Values shall be determined in accordance with Section 11.4.7 of ASCE 7.
VALUES OF SITE COEFFICIENT Fva
SITE CLASS | MAPPED SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD | ||||
S1 ≤ 0.1 | S1 = 0.2 | S1 = 0.3 | S1 = 0.4 | S1 ≥ 0.5 | |
A | 0.8 | 0.8 | 0.8 | 0.8 | 0.8 |
B | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
C | 1.7 | 1.6 | 1.5 | 1.4 | 1.3 |
D | 2.4 | 2.0 | 1.8 | 1.6 | 1.5 |
E | 3.5 | 3.2 | 2.8 | 2.4 | 2.4 |
F | Note b | Note b | Note b | Note b | Note b |
- Use straight-line interpolation for intermediate values of mapped spectral response acceleration at 1-second period, S1.
- Values shall be determined in accordance with Section 11.4.7 of ASCE 7.
Five-percent damped design spectral response acceleration at short periods, SDS, and at 1-second period, SDS, shall be determined from Equations 16-39 and 16-40, respectively:
(Equation 16-39)
(Equation 16-40)
where:
SMS = The maximum considered earthquake spectral response accelerations for short period as determined in Section 1613.3.3.
SM1 = The maximum considered earthquake spectral response accelerations for 1-second period as determined in Section 1613.3.3.
Structures classified as Risk Category I, II or III that are located where the mapped spectral response acceleration parameter at 1-second period, S1, is greater than or equal to 0.75 shall be assigned to Seismic Design Category E. Structures classified as Risk Category IV that are located where the mapped spectral response acceleration parameter at 1-second period, S1, is greater than or equal to 0.75 shall be assigned to Seismic Design Category F. All other structures shall be assigned to a seismic design category based on their risk category and the design spectral response acceleration parameters, SDS and SD1, determined in accordance with Section 1613.3.4 or the site-specific procedures of ASCE 7. Each building and structure shall be assigned to the more severe seismic design category in accordance with Table 1613.3.5(1) or 1613.3.5(2), irrespective of the fundamental period of vibration of the structure, T.
Exception: [OSHPD 2] Structures not assigned to Seismic Design Category E or F above shall be assigned to Seismic Design Category D.
SEISMIC DESIGN CATEGORY BASED ON SHORT-PERIOD (0.2 second) RESPONSE ACCELERATIONS
VALUE OF SDS | RISK CATEGORY | ||
I or II | III | IV | |
SDS < 0.167g | A | A | A |
0.167g ≤ SDS < 0.33g | B | B | C |
0.33g ≤ SDS < 0.50g | C | C | D |
0.50g ≤ SDS | D | D | D |
SEISMIC DESIGN CATEGORY BASED ON 1-SECOND PERIOD RESPONSE ACCELERATION
VALUE OF SD1 | RISK CATEGORY | ||
I or II | III | IV | |
SD1 < 0.067g | A | A | A |
0.067g ≤ SD1 < 0.133g | B | B | C |
0.133g ≤ SD1< 0.20g | C | C | D |
0.20g ≤ SD1 | D | D | D |
Where S1 is less than 0.75, the seismic design category is permitted to be determined from Table 1613.3.5(1) alone when all of the following apply:
- In each of the two orthogonal directions, the approximate fundamental period of the structure, Ta, in each of the two orthogonal directions determined in accordance with Section 12.8.2.1 of ASCE 7, is less than 0.8 Ts determined in accordance with Section 11.4.5 of ASCE 7.
- In each of the two orthogonal directions, the fundamental period of the structure used to calculate the story drift is less than Ts.
- Equation 12.8-2 of ASCE 7 is used to determine the seismic response coefficient, Cs.
- The diaphragms are rigid or are permitted to be idealized as rigid in accordance with Section 12.3.1 of ASCE 7 or, for diaphragms permitted to be idealized as flexible in accordance with Section 12.3.1 of ASCE 7, the distances between vertical elements of the seismic force-resisting system do not exceed 40 feet (12 192 mm).
Exception: [OSHPD 2] Seismic design category shall be determined in accordance with exception to Section 1613.3.5.
Where the alternate simplified design procedure of ASCE 7 is used, the seismic design category shall be determined in accordance with ASCE 7.
Exception: [OSHPD 2] Seismic design category shall be determined in accordance with exception to Section 1613.3.5.
Add the following exception to the end of Section 17.5.4.2 of ASCE 7:
Exception: For isolated structures designed in accordance with this standard, the structural system limitations including structural height limits, in Table 12.2-1 for ordinary steel concentrically braced frames (OCBFs) as defined in Chapter 11 and ordinary moment frames (OMFs) as defined in Chapter 11 are permitted to be taken as 160 feet (48 768 mm) for structures assigned to Seismic Design Category D, E or F, provided that the following conditions are satisfied:
- The value of RI as defined in Chapter 17 is taken as 1.
- For OMFs and OCBFs, design is in accordance with AISC 341.
Modify ASCE 7 Section 12.11.2.2.1 as follows:
12.11.2.2.1 Transfer of anchorage forces into diaphragm. Diaphragms shall be provided with continuous ties or struts between diaphragm chords to distribute these anchorage forces into the diaphragms. Diaphragm connections shall be positive, mechanical or welded. Added chords are permitted to be used to form subdiaphragms to transmit the anchorage forces to the main continuous cross-ties. The maximum length-to-width ratio of a wood, wood structural panel or untopped steel deck sheathed structural subdiaphragm that serves as part of the continuous tie system shall be 2.5 to 1. Connections and anchorages capable of resisting the prescribed forces shall be provided between the diaphragm and the attached components. Connections shall extend into the diaphragm a sufficient distance to develop the force transferred into the diaphragm.
Exception: [OSHPD 2] Seismic design category shall be determined in accordance with exception to Section 1613.3.5.
Frame structures constructed primarily of reinforced or prestressed concrete, either cast-in-place or precast, or a combination of these, shall conform to the requirements of Section 4.10 of ACI 318. Where ACI 318 requires that nonprestressed reinforcing or prestressing steel pass through the region bounded by the longitudinal column reinforcement, that reinforcing or prestressing steel shall have a minimum nominal tensile strength equal to two-thirds of the required one-way vertical strength of the connection of the floor or roof system to the column in each direction of beam or slab reinforcement passing through the column.
Exception: Where concrete slabs with continuous reinforcement having an area not less than 0.0015 times the concrete area in each of two orthogonal directions are present and are either monolithic with or equivalently bonded to beams, girders or columns, the longitudinal reinforcing or prestressing steel passing through the column reinforcement shall have a nominal tensile strength of one-third of the required one-way vertical strength of the connection of the floor or roof system to the column in each direction of beam or slab reinforcement passing through the column.
End connections of all beams and girders shall have a minimum nominal axial tensile strength equal to the required vertical shear strength for allowable stress design (ASD) or two-thirds of the required shear strength for load and resistance factor design (LRFD) but not less than 10 kips (45 kN). For the purpose of this section, the shear force and the axial tensile force need not be considered to act simultaneously.
Exception: Where beams, girders, open web joist and joist girders support a concrete slab or concrete slab on metal deck that is attached to the beam or girder with not less than 3/8-inch-diameter (9.5 mm) headed shear studs, at a spacing of not more than 12 inches (305 mm) on center, averaged over the length of the member, or other attachment having equivalent shear strength, and the slab contains continuous distributed reinforcement in each of two orthogonal directions with an area not less than 0.0015 times the concrete area, the nominal axial tension strength of the end connection shall be permitted to be taken as half the required vertical shear strength for ASD or one-third of the required shear strength for LRFD, but not less than 10 kips (45 kN).
Bearing wall structures shall have vertical ties in all load-bearing walls and longitudinal ties, transverse ties and perimeter ties at each floor level in accordance with this section and as shown in Figure 1615.4.
LONGITUDINAL, PERIMETER, TRANSVERSE AND VERTICAL TIES
Longitudinal ties shall consist of continuous reinforcement in slabs; continuous or spliced decks or sheathing; continuous or spliced members framing to, within or across walls; or connections of continuous framing members to walls. Longitudinal ties shall extend across interior load-bearing walls and shall connect to exterior load-bearing walls and shall be spaced at not greater than 10 feet (3038 mm) on center. Ties shall have a minimum nominal tensile strength, TT, given by Equation 16-41. For ASD the minimum nominal tensile strength shall be permitted to be taken as 1.5 times the allowable tensile stress times the area of the tie.
(Equation 16-41)
where:
L = The span of the horizontal element in the direction of the tie, between bearing walls, feet (m).
w = The weight per unit area of the floor or roof in the span being tied to or across the wall, psf (N/m2).
S = The spacing between ties, feet (m).
αT = A coefficient with a value of 1,500 pounds per foot (2.25 kN/m) for masonry bearing wall structures and a value of 375 pounds per foot (0.6 kN/m) for structures with bearing walls of cold-formed steel light-frame construction.
Perimeter ties shall consist of continuous reinforcement in slabs; continuous or spliced decks or sheathing; continuous or spliced members framing to, within or across walls; or connections of continuous framing members to walls. Ties around the perimeter of each floor and roof shall be located within 4 feet (1219 mm) of the edge and shall provide a nominal strength in tension not less than Tp, given by Equation 16-42. For ASD the minimum nominal tensile strength shall be permitted to be taken as 1.5 times the allowable tensile stress times the area of the tie.
(Equation 16-42)
For SI:Tp = 90.7w ≤ βT
where:
w = As defined in Section 1615.4.2.1.
βT = A coefficient with a value of 16,000 pounds (7200 kN) for structures with masonry bearing walls and a value of 4,000 pounds (1300 kN) for structures with bearing walls of cold-formed steel light-frame construction.
Additional requirements for construction documents are included in Sections 4-210 and 4-317 of the California Administrative Code (Part 1, Title 24, C.C.R).
Connections that resist design seismic forces shall be designed and detailed on the design drawings.
Where unusual erection or construction procedures are considered essential by the project structural engineer or architect in order to accomplish the intent of the design or influence the construction, such procedure shall be indicated on the plans or in the specifications.
The maximum span-depth ratio for any roof or floor diaphragm consisting of steel and composite steel slab decking or concrete shall be based on test data and design calculations acceptable to the enforcement agency.
Risk Category IV includes structures as defined in the California Administrative Code, Section 4-207 and all structures required for their continuous operation or access/egress.
For anchorage of concrete or masonry walls to roof and floor diaphragms, the out-of-plane strength design force shall not be less than 280 lb/linear ft (4.09 kN/m) of wall.
When checking stability under the provisions of Section 1605.1.1 using allowable stress design, the factor of safety for soil bearing values shall not be less than the overstrength factor of the structures supported.
The text of ICC 300 shall be modified as indicated in Section 1616.3.2.1 through 1616.3.2.3.
The design dead load shall provide for the weight of at least one additional roof covering in addition to other applicable loadings if the new roof covering is permitted to be applied over the original roofing without its removal, in accordance with Section 1511.
The following minimum loads for stage accessories apply:
- Gridirons and fly galleries: 75 pounds per square foot uniform live load.
- Loft block wells: 250 pounds per lineal foot vertical load and lateral load.
- Head block wells and sheave beams: 250 pounds per lineal foot vertical load and lateral load. Head block wells and sheave beams shall be designed for all tributary loft block well loads. Sheave blocks shall be designed with a safety factor of five.
- Scenery beams where there is no gridiron: 300 pounds per lineal foot vertical load and lateral load.
- Ceiling framing over stages shall be designed for a uniform live load of 20 pounds per square foot. For members supporting a tributary area of 200 square feet or more, this additional load may be reduced to 15 pounds per square foot (0.72 kN/m2).
The minimum uniform live load for a press box floor or accessible roof with railing is 100 psf.
The minimum vertical design live load shall be as follows:
Paper media:
12-inch-deep (305 mm) shelf - 33 pounds per lineal foot (482 N/m)
15-inch-deep (381 mm) shelf - 41 pounds per lineal foot (598 N/m), or 33 pounds per cubic foot (5183 N/m3) per total volume of the rack or cabinet, whichever is less.
Film media:
18-inch-deep (457 mm) shelf - 100 pounds per lineal foot (1459 N/m), or
50 pounds per cubic foot (7853 N/m3) per total volume of the rack or cabinet, whichever is less.
Other media:
20 pounds per cubic foot (311 N/m3) or 20 pounds per square foot (958 Pa), whichever is less, but not less than actual loads.
Uncovered open-frame roof structures shall be designed for a vertical live load of not less than 10 pounds per square foot (0.48 kN/m2) of the total area encompassed by the framework.
The ground snow load or the design snow load for roofs shall conform with the adopted ordinance of the city, county, or city and county in which the project site is located, and shall be approved by DSA.
The calculated story drift due to wind pressures with ultimate design wind speed, Vult, shall not exceed 0.008 times the story height for buildings less than 65 feet (19,812 mm) in height or 0.007 times the story height for buildings 65 feet (19,812 mm) or greater in height.
Exception: This story drift limit need not be applied for single-story open buildings in Risk Category I and II.
Flood hazard maps shall include, at a minimum, areas of special flood hazard as identified by the Federal Emergency Management Agency's Flood Insurance Study (FIS) adopted by the local authority having jurisdiction where the project is located, as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and related supporting data along with any revisions thereto.
The seismic design category for a structure shall be determined in accordance with Section 1613.
In addition to the definitions in Section 1613.2, the following words and terms shall, for the purposes of this section, have the meanings shown herein.
ACTIVE EARTHQUAKE FAULT. A fault that has been the source of earthquakes or is recognized as a potential source of earthquakes, including those that have exhibited surface displacement within Holocene time (about 11,000 years) as determined by California Geological Survey (CGS) under the Alquist-Priolo Earthquake Fault Zoning Act, those included as type A or type B faults for the U.S. Geological Survey (USGS) National Seismic Hazard Maps, and faults considered to have been active in Holocene time by an authoritative source, federal, state or local governmental agency.
DISTANCE FROM AN ACTIVE EARTHQUAKE FAULT. Distance measured from the nearest point of the building to the closest edge of an Alquist-Priolo Earthquake fault zone for an active fault, if such a map exists, or to the closest mapped splay of the fault.
IRREGULAR STRUCTURE. A structure designed as having one or more plan or vertical irregularities per ASCE 7 Section 12.3.
Seismic Design Category shall be determined in accordance with Section 1613.3.5.
Structures not assigned to Seismic Design Category E or F, in accordance with Section 1613.3, shall be assigned to Seismic Design Category D.
The alternative Seismic Design Category determination procedure of Section 1613.3.5.1 is not permitted by DSA-SS/CC.
The simplified design procedure of Section 1613.3.5.2 is not permitted by DSA-SS/CC.
The text of ASCE 7 shall be modified as indicated in Sections 1616.10.1 through 1616.10.24.
Modify ASCE 7 Section 1.3 by adding Section 1.3.6 as follows:
1.3.6 Structural design criteria. Where design is based on ASCE 7 Chapters 16, 17, 18, or 31, the ground motion, wind tunnel design recommendations, analysis, and design methods, material assumptions, testing requirements, and acceptance criteria proposed by the engineer shall be submitted to the enforcement agency in the form of structural design criteria for approval.
Peer review requirements in Section 322 of the California Existing Buildings Code shall apply to design reviews required by ASCE 7 Chapters 17 and 18.
Modify ASCE 7 Section 11.4.7 by adding the following:
For buildings assigned to Seismic Design Category E and F, or when required by the building official, a ground motion hazard analysis shall be performed in accordance with ASCE 7 Chapter 21, as modified by Section 1803A.6 of this code.
Modify ASCE 7 Table 12.2-1 as follows:
BEARING WALL SYSTEMS
- Light-framed walls with shear panels of all other materials - Not permitted by DSA-SS/CC.
BUILDING FRAME SYSTEMS
- Light-framed walls with shear panels of all other materials - Not permitted by DSA-SS/CC.
MOMENT RESISTING FRAME SYSTEMS
Cold-formed steel — special bolted moment frame - Not permitted by DSA-SS/CC.
Exception:
- Systems listed in this section can be used as an alternative system when pre-approved by the enforcement agency.
- Rooftop or other supported structures not exceeding two stories in height and 10 percent of the total structure weight can use the systems in this section when designed as components per ASCE 7 Chapter 13.
- Systems listed in this section can be used for seismically isolated buildings when permitted by Section 1613.4.1.
Replace ASCE 7 Section 12.2.3.1, Items 1 and 2 by the following:
The value of the response modification coefficient, R, used for design at any story shall not exceed the lowest value of R that is used in the same direction at any story above that story. Likewise, the deflection amplification factor, Cd, and the system over strength factor, Ωo, used for the design at any story shall not be less than the largest value of these factors that are used in the same direction at any story above that story.
Modify ASCE 7 Section 12.2.3.2 by adding the following additional requirements for a two stage equivalent lateral force procedure or modal response spectrum procedure:
f. Where design of elements of the upper portion is governed by special seismic load combinations, the special loads shall be considered in the design of the lower portions.
The exception in Item a is not permitted by DSA-SS/CC.
The exception in Item a is not permitted by DSA-SS/CC.
The exception in Item a is not permitted by DSA-SS/CC.
Modify ASCE 7 Section 12.3.3.1 as follows:
12.3.3.1 Prohibited horizontal and vertical irregularities for Seismic Design Categories D through F. Structures assigned to Seismic Design Category E or F having horizontal structural irregularity Type 1b of Table 12.3-1 or vertical structural irregularities Type 1b, 5a or 5b of Table 12.3-2 shall not be permitted. Structures assigned to Seismic Design Category D having vertical irregularity Type 1b or 5b of Table 12.3-2 shall not be permitted.
Modify ASCE 7 Section 12.7.2 by adding Item 6 to read as follows:
6. Where buildings provide lateral support for walls retaining earth, and the exterior grades on opposite sides of the building differ by more than 6 feet (1829 mm), the load combination of the seismic increment of earth pressure due to earthquake acting on the higher side, as determined by a Geotechnical engineer qualified in soils engineering, plus the difference in earth pressures shall be added to the lateral forces provided in this section.
Replace ASCE 7 Section 12.8.1.3 by the following:
12.8.1.3 Maximum SDS Value in Determination of Cs and Ev. The value of Cs and Ev are permitted to be calculated using a value of SDS equal to 1.0, but not less than 70% of SDS as defined in Section 11.4.4, provided that all of the following criteria are met:
- The structure does not have irregularities, as defined in Section 12.3.2;
- The structure does not exceed five stories above the base as defined in Section 11.2;
- The structure has a fundamental period, T, that does not exceed 0.5 seconds, as determined using Section 12.8.2;
- The structure meets the requirements necessary for the redundancy factor, ρ, to be permitted to be taken as 1.0, in accordance with Section 12.3.4.2;
- The site soil properties are not classified as Site Class E or F, as defined in Section 11.4.2; and
- The structure is classified as Risk Category I or II, as defined in Section 1.5.1.
Replace ASCE 7 Section 12.9.4 as follows:
12.9.4 Scaling design values of combined response. Modal base shears used to determine forces and drifts shall not be less than the base shear calculated using the equivalent lateral force procedure of Section 12.8.
Replace ASCE 7 Exception 1 of Section 12.10.2.1 by the following:
Exception: The forces calculated above need not exceed those calculated using the load combinations of Section 12.4.3.2 with seismic forces determined by Equation 12.10-3 and transfer forces, where applicable.
Modify ASCE 7 Section 12.13.1 by adding Section 12.13.1.1 as follows:
12.13.1.1 Foundations and superstructure-to-foundation connections. The foundation shall be capable of transmitting the design base shear and the overturning forces from the structure into the supporting soil. Stability against overturning and sliding shall be in accordance with Section 1605.1.1.
In addition, the foundation and the connection of the superstructure elements to the foundation shall have the strength to resist, in addition to gravity loads, the lesser of the following seismic loads:
- The strength of the superstructure elements.
- The maximum forces that can be delivered to the foundation in a fully yielded structural system.
Forces from the Load Combinations with over-strength factor in accordance with ASCE 7 Section 12.4.3.2.
Exceptions:
- Where referenced standards specify the use of higher design loads.
- When it can be demonstrated that inelastic deformation of the foundation and super-structure-to-foundation connection will not result in a weak story or cause collapse of the structure.
- Where seismic force-resisting system consists of light-framed walls with shear panels, unless the reference standard specifies the use of higher design loads.
Where the computation of the seismic overturning moment is by the equivalent lateral-force method or the modal analysis method, reduction in overturning moment permitted by Section 12.13.4 of ASCE 7 may be used.
Where moment resistance is assumed at the base of the superstructure elements, the rotation and flexural deformation of the foundation as well as deformation of the superstructure-to-foundation connection shall be considered in the drift and deformation compatibility analyses.
Replace ASCE 7 Section 13.1.4 by the following:
13.1.4 Exemptions. The following nonstructural components are exempt from the requirements of this section:
- Furniture (except storage cabinets as noted in Table 13.5-1).
Temporary or moveable (mobile) equipment.
Exceptions:
- Equipment shall be anchored if it is permanently attached to the building utility services such as electricity, gas, or water. For the purposes of this requirement, "permanently attached" shall include all electrical connections except plugs for duplex receptacles.
- The enforcement agency shall be permitted to require temporary attachments for mov able equipment which is usually stationed in one place and heavier than 400 pounds or has a center of mass located 4 feet (1.22 m) or more above the adjacent floor or roof level that directly supports the component when they are not in use for a period longer than 8 hours at a time.
Mechanical and electrical components in Seismic Design Categories D, E or F where all of the following apply:
- The component is positively attached to the structure;
Flexible connections are provided at seismic separation joints and between the component and associated ductwork, piping and conduit; and either:
The component weighs 400 lb (1780 N) or less and has a center of mass located 4 ft. (1.22 m) or less above the adjacent floor or roof level;
Exception: Special Seismic Certification requirements of this code in accordance with Section 1705A.12.3 shall be applicable.
or
The component weighs 20 lb (89 N) or less or, in the case of a distributed system, 5 lb/ft (73 N/m) or less.
Exception: The enforcement agency shall be permitted to require attachments for equipment with hazardous contents to be shown on construction documents irrespective of weight.
Replace ASCE 7, Section 13.5.6 by the following:
13.5.6 Suspended ceilings. Suspended ceilings shall be in accordance with this section.
13.5.6.1 Seismic forces. The weight of the ceiling, Wp, shall include the ceiling grid; ceiling tiles or panels; light fixtures if attached to, clipped to, or laterally supported by the ceiling grid; and other components that are laterally supported by the ceiling. Wp shall be taken as not less than 4 psf (19 N/m2).
The seismic force, Fp, shall be transmitted through the ceiling attachments to the building structural elements or the ceiling-structure boundary.
13.5.6.2 Industry standard construction for acoustical tile or lay-in panel ceilings. Unless designed in accordance with ASTM E580 Section 5.2.8, or seismically qualified in accordance with Sections 13.2.5 or 13.2.6, acoustical tile or lay-in panel ceilings shall be designed and constructed in accordance with this section.
13.5.6.2.1 Seismic Design Categories D through F. Acoustical tile or lay-in panel ceilings in Seismic Design Categories D, E and F shall be designed and installed in accordance with ASTM C635, ASTM C636, and ASTM E580, Section 5 - Seismic Design Categories D, E and F as modified by this section.
Exception to Section 13.5.8.1 shall not be used in accordance with ASTM E580 Section 5.5.
13.5.6.2.2 Modification to ASTM E580. Modify ASTM E580 by the following:
- Exitways. Lay-in ceiling assemblies in exitways of hospitals and essential services buildings shall be installed with a main runner or cross runner surrounding all sides of each piece of tile, board or panel and each light fixture or grille. A cross runner that supports another cross runner shall be considered as a main runner for the purpose of structural classification. Splices or intersections of such runners shall be attached with through connectors such as pop rivets, screws, pins, plates with end tabs or other approved connectors. Lateral force diagonal bracing may be omitted in the short or transverse direction of exitways, not exceeding 8 feet wide, when perimeter support in accordance with ASTM E580 Sections 5.2.2 and 5.2.3 is provided and the perimeter wall laterally supporting the ceiling in the short or transverse direction is designed to carry the ceiling lateral forces. The connections between the ceiling grid, wall angle and the wall shall be designed to resist the ceiling lateral forces.
- Corridors and lobbies. Expansion joints shall be provided in the ceiling at intersections of corridors and at junctions of corridors and lobbies or other similar areas.
- Lay-in panels. Metal panels and panels weighing more than 1/2 pounds per square foot (24 N/m2) other than acoustical tiles shall be positively attached to the ceiling suspension runners.
- Lateral force bracing. Lateral force bracing is required for all ceiling areas except that they shall be permitted to be omitted in rooms with floor areas up to 144 square feet when perimeter support in accordance with ASTM E580 Sections 5.2.2 and 5.2.3 are provided and perimeter walls are designed to carry the ceiling lateral forces. The connections between the ceiling grid, wall angle and the wall shall be designed to resist the ceiling lateral forces. Horizontal restraint point spacing shall be justified by analysis or test and shall not exceed a spacing of 12 feet by 12 feet. Bracing wires shall be secured with four tight twists in 11/2 inches, or an approved alternate connection.
- Ceiling support and bracing wires shall be spaced a minimum of 6" from all pipes, ducts, conduits and equipment that are not braced for horizontal forces, unless approved otherwise by the building official.
Modify ASCE 7, Section 13.6.5.6, Exceptions 1 and 2, as follows:
Exceptions:
Design for the seismic forces of Section 13.3 shall not be required for raceways where either:
- Trapeze assemblies are used to support raceways and the total weight of the raceway supported by trapeze assemblies is less than 10 lb/ft (146 N/m), or
- The raceway is supported by hangers and each hanger in the raceway run is 12 in. (305 mm) or less in length from the raceway support point to the supporting structure. Where rod hangers are used, they shall be equipped with swivels to prevent inelastic bending in the rod.
- Design for the seismic forces of Section 13.3 shall not be required for conduit, regardless of the value of Ip, where the conduit is less than 2.5 in. (64 mm) trade size.
Replace ASCE 7, Section 13.6.7, Exceptions 1 and 2, by the following:
Exceptions:
The following exceptions pertain to ductwork not designed to carry toxic, highly toxic or flammable gases, or used for smoke control:
Design for the seismic forces of Section 13.3 shall not be required for ductwork where either:
- Trapeze assemblies are used to support ductwork and the total weight of the ductwork supported by trapeze assemblies is less than 10 lb/ft (146 N/m); or
- The ductwork is supported by hangers and each hanger in the duct run is 12 in. (305 mm) or less in length from the duct support point to the supporting structure. Where rod hangers are used, they shall be equipped with swivels to prevent inelastic bending in the rod.
- Design for the seismic forces of Section 13.3 shall not be required where provisions are made to avoid impact with larger ducts or mechanical components or to protect the ducts in the event of such impact; and HVAC ducts have a cross-sectional area of 6 ft2 (0.557 m2) or less, or weigh 10 lb/ft (146 N/m) or less.
Replace ASCE 7, Section 13.6.8.3 with the following:
13.6.8.3 Exceptions. Design of piping systems and attachments for the seismic forces of Section 13.3 shall not be required where one of the following conditions apply:
- Trapeze assemblies are used to support piping whereby no single pipe exceeds the limits set forth in 3a. or b. below and the total weight of the piping supported by the trapeze assemblies is less than 10 lb/ft (146 N/m).
- The piping is supported by hangers and each hanger in the piping run is 12 in. (305 mm) or less in length from the top of the pipe to the supporting structure. Where pipes are supported on a trapeze, the trapeze shall be supported by hangers having a length of 12 in. (305 mm) or less. Where rod hangers are used, they shall be equipped with swivels, eye nuts or other devices to prevent bending in the rod.
Piping having an Rp in Table 13.6-1 of 4.5 or greater is used and provisions are made to avoid impact with other structural or nonstructural components or to protect the piping in the event of such impact and where the following size requirements are satisfied:
- For Seismic Design Categories D, E or F and values of Ip greater than one, the nominal pipe size shall be 1 inch (25 mm) or less.
- For Seismic Design Categories D, E or F where Ip = 1.0 the nominal pipe size shall be 3 inches (80 mm) or less.
The exceptions above shall not apply to elevator piping.
Modify ASCE 7 Section 13.6.10.1 by adding Section 13.6.10.1.1, as follows:
13.6.10.1.1 Elevators guide rail support. The design of guide rail support bracket fastenings and the supporting structural framing shall use the weight of the counterweight or maximum weight of the car plus not more than 40 percent of its rated load. The seismic forces shall be assumed to be distributed one-third to the top guiding members and two-thirds to the bottom guiding members of cars and counterweights, unless other substantiating data are provided. In addition to the requirements of ASCE 7 Section 13.6.10.1, the minimum seismic forces shall be 0.5g acting in any horizontal direction.
Replace ASCE 7 Section 13.6.10.4, as follows:
13.6.10.4 Retainer plates. Retainer plates are required at the top and bottom of the car and counterweight, except where safety devices acceptable to the enforcement agency are provided which meet all requirements of the retainer plates, including full engagement of the machined portion of the rail. The design of the car, cab stabilizers, counterweight guide rails and counterweight frames for seismic forces shall be based on the following requirements:
- The seismic force shall be computed per the requirements of ASCE 7 Section 13.6.10.1. The minimum horizontal acceleration shall be 0.5g for all buildings.
- Wp shall equal the weight of the counterweight or the maximum weight of the car plus not less than 40 percent of its rated load.
- With the car or counterweight located in the most adverse position, the stress in the rail shall not exceed the limitations specified in these regulations, nor shall the deflection of the rail relative to its supports exceed the deflection listed below in Table 1224.4.11.
- Where guide rails are continuous over supports and rail joints are within 2 feet (610 mm) of their supporting brackets, a simple span may be assumed.
- The use of spreader brackets is allowed.
- Cab stabilizers and counterweight frames shall be designed to withstand computed lateral load with a minimum horizontal acceleration of 0.5g.
TABLE 1224.4.11
ALLOWABLE RAIL DEFLECTION
RAIL SIZE (weight per foot of length, pounds) | WIDTH OF MACHINED SURFACE (inches) | ALLOWABLE RAIL DEFLECTION (inches) |
8 | 11/4 | 0.20 |
11 | 11/2 | 0.30 |
12 | 13/4 | 0.40 |
15 | 131/32 | 0.50 |
181/2 | 131/32 | 0.50 |
221/2 | 2 | 0.50 |
30 | 21/4 | 0.50 |
For SI: 1 inch = 25 mm, 1 foot = 305 mm, 1 pound = 0.454 kg.
Note: Deflection limitations are given to maintain a consistent factor of safety against disengagement of retainer plates from the guide rails during an earthquake.
Remove ASCE 7 Sections 16.1.4.1 and 16.1.4.2 and modify 16.1.4 by the following:
Maximum scaled base shears used to determine forces and drifts shall not be less than the base shear calculated using the equivalent lateral force procedure of Section 12.8.
Modify ASCE 7 Section 16.2.4 by the following:
Where site is located within 3.1 miles (5 km) of an active fault at least seven ground motions shall be analyzed and response parameters shall be based on larger of the average of the maximum response with ground motions applied as follows:
- Each of the ground motions shall have their maximum component at the fundamental period aligned in one direction.
- Each of the ground motion's maximum component shall be rotated orthogonal to the previous analysis direction.
- Where site is located more than 3.1 miles (5 km) from an active fault at least 10 ground motions shall be analyzed. The ground motions shall be applied such that one-half shall have their maximum component aligned in one direction and the other half aligned in the orthogonal direction. The average of the maximum response of all the analyses shall be used for design.
Modify ASCE 7 Section 17.2.4.7 by adding the following to the end of the section:
The effects of uplift shall be explicitly accounted for in the analysis and in the testing of the isolator units.