Cover [PDF]

Standards [PDF]

Foreword [PDF]

Acknowledgements [PDF]

Dedication [PDF]

Contents [PDF]

Chapter 1 General

Chapter 2 Combinations of Loads

Chapter 3 Dead Loads, Soil Loads, and Hydrostatic Pressure

Chapter 4 Live Loads

Chapter 5 Flood Loads

Chapter 6 Reserved for Future Provisions

Chapter 7 Snow Loads

Chapter 8 Rain Loads

Chapter 9 Reserved for Future Provisions

Chapter 10 Ice Loads - Atmospheric Icing

Chapter 11 Seismic Design Criteria

Chapter 12 Seismic Design Requirements for Building Structures

Chapter 13 Seismic Design Requirements for Nonstructural Components

Chapter 14 Material Specific Seismic Design and Detailing Requirements

Chapter 15 Seismic Design Requirements for Nonbuilding Structures

Chapter 16 Seismic Response History Procedures

Chapter 17 Seismic Design Requirements for Seismically Isolated Structures

Chapter 18 Seismic Design Requirements for Structures with Damping Systems

Chapter 19 Soil-Structure Interaction for Seismic Design

Chapter 20 Site Classification Procedure for Seismic Design

Chapter 21 Site-Specific Ground Motion Procedures for Seismic Design

Chapter 22 Seismic Ground Motion Long-Period Transition and Risk Coefficient Maps

Chapter 23 Seismic Design Reference Documents

Chapter 24

Chapter 25

Chapter 26 Wind Loads: General Requirements

Chapter 27 Wind Loads on Buildings‒MWFRS (Directional Procedure)

Chapter 28 Wind Loads on Buildings‒MWFRS (Envelope Procedure)

Chapter 29 Wind Loads on Other Structures and Building Appurtenances‒MWFRS

Chapter 30 Wind Loads ‒ Components and Cladding (C&C)

Chapter 31 Wind Tunnel Procedure

Appendix 11A Quality Assurance Provisions

Appendix 11B Existing Building Provisions

Appendix C Serviceability Considerations

Appendix D Buildings Exempted from Torisional Wind Load Cases

The provisions of this section apply to buildings and other structures located in areas prone to flooding as defined on a flood hazard map.
The following definitions apply to the provisions of this chapter:
    APPROVED:  Acceptable to the authority having jurisdiction.
    BASE FLOOD: The flood having a 1% chance of being equaled or exceeded in any given year.
    BASE FLOOD ELEVATION (BFE): The elevation of flooding, including wave height, having a 1% chance of being equaled or exceeded in any given year.
    BREAKAWAY WALL: Any type of wall subject to flooding that is not required to provide structural support to a building or other structure and that is designed and constructed such that, under base flood or lesser flood conditions, it will collapse in such a way that (1) it allows the free passage of floodwaters, and (2) it does not damage the structure or supporting foundation system.
    COASTAL A-ZONE: An area within a special flood hazard area, landward of a V-Zone or landward of an open coast without mapped V-Zones. To be classified as a Coastal A-Zone, the principal source of flooding must be astronomical tides, storm surges, seiches, or tsunamis, not riverine flooding, and the potential for breaking wave heights greater than or equal to 1.5 ft (0.46 m) must exist during the base flood.
    COASTAL HIGH HAZARD AREA (V-ZONE): An area within a special flood hazard area, extending from offshore to the inland limit of a primary frontal dune along an open coast, and any other area that is subject to high-velocity wave action from storms or seismic sources. This area is designated on flood insurance rate maps (FIRMs) as V, VE, VO, or V1-30.
    DESIGN FLOOD: The greater of the following two flood events: (1) the base flood, affecting those areas identified as special flood hazard areas on the community's FIRM; or (2) the flood corresponding to the area designated as a flood hazard area on a community's flood hazard map or otherwise legally designated.
    DESIGN FLOOD ELEVATION (DFE): The elevation of the design flood, including wave height, relative to the datum specified on a community's flood hazard map.
    FLOOD HAZARD AREA: The area subject to flooding during the design flood.
    FLOOD HAZARD MAP: The map delineating flood hazard areas adopted by the authority having jurisdiction.
    FLOOD INSURANCE RATE MAP (FIRM): An official map of a community on which the Federal Insurance and Mitigation Administration has delineated both special flood hazard areas and the risk premium zones applicable to the community.
    SPECIAL FLOOD HAZARD AREA (AREA OF SPECIAL FLOOD HAZARD): The land in the floodplain subject to a 1% or greater chance of flooding in any given year. These areas are delineated on a community's FIRM as A-Zones (A, AE, Al-30, A99, AR, AO, or AH) or V-Zones (V, VE, VO, or Vl-30).
Structural systems of buildings or other structures shall be designed, constructed, connected, and anchored to resist flotation, collapse, and permanent lateral displacement due to action of flood loads associated with the design flood (see Section 5.3.3) and other loads in accordance with the load combinations of Chapter 2.
The effects of erosion and scour shall be included in the calculation of loads on buildings and other structures in flood hazard areas.
Walls and partitions required by ASCE/SEI 24 to break away, including their connections to the structure, shall be designed for the largest of the following loads acting perpendicular to the plane of the wall:
  1. the wind load specified in Chapter 26
  2. the earthquake load specified in Chapter 12, and
  3. 10 psf (0.48 kN/m2).
       The loading at which breakaway walls are intended to collapse shall not exceed 20 psf (0.96 kN/m2 ) unless the design meets the following conditions:
  1. Breakaway wall collapse is designed to result from a flood load less than that which occurs during the base flood.
  2. The supporting foundation and the elevated portion of the building shall be designed against collapse, permanent lateral displacement, and other structural damage due to the effects of flood loads in combination with other loads as specified in Chapter 2.
In flood hazard areas, the structural design shall be based on the design flood.
Hydrostatic loads caused by a depth of water to the level of the DFE shall be applied over all surfaces involved, both above and below ground level, except that for surfaces exposed to free water, the design depth shall be increased by 1 ft (0.30 m).
   Reduced uplift and lateral loads on surfaces of enclosed spaces below the DFE shall apply only if provision is made for entry and exit of floodwater.
Dynamic effects of moving water shall be determined by a detailed analysis utilizing basic concepts of fluid mechanics.
   EXCEPTION: Where water velocities do not exceed 10 ft/s (3.05 m/s), dynamic effects of moving water shall be permitted to be converted into equivalent hydrostatic loads by increasing the DFE for design purposes by an equivalent surcharge depth, dh, on the headwater side and above the ground level only, equal to
(5.4-1)
where
V = average velocity of water in ft/s (m/s)
g = acceleration due to gravity, 32.2 ft/s2 (9.81 m/s2)
a = coefficient of drag or shape factor (not less than 1.25)

   The equivalent surcharge depth shall be added to the DFE design depth and the resultant hydrostatic pressures applied to, and uniformly distributed across, the vertical projected area of the building or structure that is perpendicular to the flow. Surfaces parallel to the flow or surfaces wetted by the tail water shall be subject to the hydrostatic pressures for depths to the DFE only.
Wave loads shall be determined by one of the following three methods: (1) by using the analytical procedures outlined in this section, (2) by more advanced numerical modeling procedures, or (3) by laboratory test procedures (physical modeling).
   Wave loads are those loads that result from water waves propagating over the water surface and striking a building or other structure. Design and construction of buildings and other structures subject to wave loads shall account for the following loads: waves breaking on any portion of the building or structure; uplift forces caused by shoaling waves beneath a building or structure, or portion thereof; wave runup striking any portion of the building or structure; wave-induced drag and inertia forces; and wave-induced scour at the base of a building or structure, or its foundation. Wave loads shall be included for both V-Zones and A-Zones. In V-Zones, waves are 3 ft (0.91 m) high, or higher; in coastal floodplains landward of the V-Zone, waves are less than 3 ft high (0.91 m).
   Nonbreaking and broken wave loads shall be calculated using the procedures described in Sections 5.4.2 and 5.4.3 that show how to calculate hydrostatic and hydrodynamic loads.
   Breaking wave loads shall be calculated using the procedures described in Sections 5.4.4.1 through 5.4.4.4. Breaking wave heights used in the procedures described in Sections 5.4.4.1 through 5.4.4.4 shall be calculated for V-Zones and Coastal A-Zones using Eqs. 5.4-2 and 5.4-3.
(5.4-2)
where
Hb = breaking wave height in ft (m)
ds = local still water depth in ft (m)

    The local still water depth shall be calculated using Eq. 5.4-3, unless more advanced procedures or laboratory tests permitted by this section are used.

Table 5.4-1 Value of Dynamic Pressure Coefficient, Cp
Risk Categorya Cp
I 1.6
II 2.8
III 3.2
IV 3.5

aFor Risk Category, see Table 1.5-1.
(5.4-3)
where
BFE = BFE in ft (m)
G = ground elevation in ft (m)
The net force resulting from a breaking wave acting on a rigid vertical pile or column shall be assumed to act at the still water elevation and shall be calculated by the following:
(5.4-4)
where
FD = net wave force, in lb (kN)
γw = unit weight of water, in lb per cubic ft (kN/m3), = 62.4 pcf (9.80 kN/m3) for fresh water and 64.0 pcf (10.05 kN/m3) for salt water
CD = coefficient of drag for breaking waves, = 1.75 for round piles or columns and = 2.25 for square piles or columns
D = pile or column diameter, in ft (m) for circular sections, or for a square pile or column, 1.4 times the width of the pile or column in ft (m)
Hb = breaking wave height, in ft (m)
Maximum pressures and net forces resulting from a normally incident breaking wave (depth limited in size, with Hb = 0.78ds) acting on a rigid vertical wall shall be calculated by the following:
(5.4-5)
and
(5.4-6)
where
Pmax = maximum combined dynamic ( Cpγwds) and static (1.2γwds) wave pressures, also referred to as shock pressures in lb/ft2 (kN/m2)
Ft = net breaking wave force per unit length of structure, also referred to as shock, impulse, or wave impact force in lb/ft (kN/m), acting near the still water elevation
Cp = dynamic pressure coefficient (1.6 < Cp < 3.5) (see Table 5.4-1)
γw = unit weight of water, in lb per cubic ft (kN/m3), = 62.4 pcf (9.80 kN/m3) for fresh water and 64.0 pcf (10.05 kN/m3) for salt water
ds = still water depth in ft (m) at base of building or other structure where the wave breaks


Table 5.4-1 Value of Dynamic Pressure Coefficient, Cp
Risk Categorya Cp
I 1.6
II 2.8
III 3.2
IV 3.5
aFor Risk Category, see Table 1.5-1.

    This procedure assumes the vertical wall causes a reflected or standing wave against the waterward side of the wall with the crest of the wave at a height of 1.2ds above the still water level. Thus, the dynamic static and total pressure distributions against the wall are as shown in Fig. 5.4-1.
FIGURE 5.4-1 Normally Incident Breaking Wave Pressures against a Vertical Wall (Space behind Vertical Wall Is Dry)
    This procedure also assumes the space behind the vertical wall is dry, with no fluid balancing the static component of the wave force on the outside of the wall. If free water exists behind the wall, a portion of the hydrostatic component of the wave pressure and force disappears (see Fig. 5.4-2) and the net force shall be computed by Eq. 5.4-7 (the maximum combined wave pressure is still computed with Eq. 5.4-5).


(5.4-7)
where
Ft = net breaking wave force per unit length of structure, also referred to as shock, impulse, or wave impact force in lb/ft (kN/m), acting near the still water elevation
Cp = dynamic pressure coefficient (1.6 < Cp < 3.5) (see Table 5.4-1)
γw = unit weight of water, in lb per cubic ft (kN/m3), = 62.4 pcf (9.80 kN/m3) for fresh water and 64.0 pcf (10.05 kN/m3) for salt water
ds = still water depth in ft (m) at base of building or other structure where the wave breaks
FIGURE 5.4-2 Normally Incident Breaking Wave Pressures against a Vertical Wall (Still Water Level Equal on Both Sides of Wall)
Breaking wave forces given by Eqs. 5.4-6 and 5.4-7 shall be modified in instances where the walls or surfaces upon which the breaking waves act are nonvertical. The horizontal component of breaking wave force shall be given by
(5.4-8)
where
F = horizontal component of breaking wave force in lb/ft (kN/m)
Ft = net breaking wave force acting on a vertical surface in lb/ft (kN/m)
α = vertical angle between nonvertical surface and the horizontal
Breaking wave forces given by Eqs. 5.4-6 and 5.4-7 shall be modified in instances where waves are obliquely incident. Breaking wave forces from nonnormally incident waves shall be given by
(5.4-9)
where
Foi = horizontal component of obliquely incident breaking wave force in lb/ft (kN/m)
Ft = net breaking wave force (normally incident waves) acting on a vertical surface in lb/ft (kN/m)
α = horizontal angle between the direction of wave approach and the vertical surface
Impact loads result from debris, ice, and any object transported by floodwaters striking against buildings and structures, or parts thereof. Impact loads shall be determined using a rational approach as concentrated loads acting horizontally at the most critical location at or below the DFE.
This section lists the consensus standards and other documents that are adopted by reference within this chapter:

ASCE/SEI
American Society of Civil Engineers
Structural Engineering Institute
1801 Alexander Bell Drive
Reston, VA 20191-4400

ASCE/SEI 24
Section 5.3.3
Flood Resistant Design and Construction, 1998