Table 1 Percent of Cross Section of Conduit and Tubing for Conductors and Cables
Number of Conductors and/or Cables | Cross-Sectional Area (%) |
---|---|
1 | 53 |
2 | 31 |
Over 2 | 40 |
Informational Note No. 1: Table 1 is based on common conditions of proper cabling and alignment of conductors where the length of the pull and the number of bends are within reasonable limits. It should be recognized that, for certain conditions, a larger size conduit or a lesser conduit fill should be considered.
Informational Note No. 2: When pulling three conductors or cables into a raceway, if the ratio of the raceway (inside diameter) to the conductor or cable (outside diameter) is between 2.8 and 3.2, jamming can occur. While jamming can occur when pulling four or more conductors or cables into a raceway, the probability is very low.
Notes to Tables
- See Informative Annex C for the maximum number of conductors and fixture wires, all of the same size (total cross-sectional area including insulation) permitted in trade sizes of the applicable conduit or tubing.
- Table 1 applies only to complete conduit or tubing systems and is not intended to apply to sections of conduit or tubing used to protect exposed wiring and cables from physical damage.
- Equipment grounding or bonding conductors, where installed, shall be included when calculating conduit or tubing fill. The actual dimensions of the equipment grounding or bonding conductor (insulated or bare) shall be used in the calculation.
- Where conduit or tubing nipples having a maximum length not to exceed 600 mm (24 in.) are installed between boxes, cabinets, and similar enclosures, the nipples shall be permitted to be filled to 60 percent of their total cross-sectional area, and 310.15(C)(1) adjustment factors need not apply to this condition.
- For conductors not included in Chapter 9, such as multiconductor cables and optical fiber cables, the actual dimensions shall be used.
- For combinations of conductors of different sizes, use actual dimensions or Table 5 and Table 5A for dimensions of conductors and Table 4 for the applicable conduit or tubing dimensions.
- When calculating the maximum number of conductors or cables permitted in a conduit or tubing, all of the same size (total cross-sectional area including insulation), the next higher whole number shall be used to determine the maximum number of conductors permitted when the calculation results in a decimal greater than or equal to 0.8. When calculating the size for conduit or tubing permitted for a single conductor, one conductor shall be permitted when the calculation results in a decimal greater than or equal to 0.8.
- Where bare conductors are permitted by other sections of this Code, the dimensions for bare conductors in Table 8 shall be permitted.
- A multiconductor cable, optical fiber cable, or flexible cord of two or more conductors shall be treated as a single conductor for calculating percentage conduit or tubing fill area. For cables that have elliptical cross sections, the cross-sectional area calculation shall be based on using the major diameter of the ellipse as a circle diameter. Assemblies of single insulated conductors without an overall covering shall not be considered a cable when determining conduit or tubing fill area. The conduit or tubing fill for the assemblies shall be calculated based upon the individual conductors.
- The values for approximate conductor diameter and area shown in Table 5 are based on worst-case scenario and indicate round concentric-lay-stranded conductors. Solid and round concentric-lay-stranded conductor values are grouped together for the purpose of Table 5. Round compact-stranded conductor values are shown in Table 5A. If the actual values of the conductor diameter and area are known, they shall be permitted to be used.
Table 2 Radius of Conduit and Tubing Bends
Conduit or Tubing Size | One Shot and Full Shoe Benders | Other Bends | |||||
---|---|---|---|---|---|---|---|
Metric Designator | Trade Size | mm | in. | mm | in. | ||
16 | 1/2 | 101.6 | 4 | 101.6 | 4 | ||
21 | 3/4 | 114.3 | 41/2 | 127 | 5 | ||
27 | 1 | 146.05 | 53/4 | 152.4 | 6 | ||
35 | 11/4 | 184.15 | 71/4 | 203.2 | 8 | ||
41 | 11/2 | 209.55 | 81/4 | 254 | 10 | ||
53 | 2 | 241.3 | 91/2 | 304.8 | 12 | ||
63 | 21/2 | 266.7 | 101/2 | 381 | 15 | ||
78 | 3 | 330.2 | 13 | 457.2 | 18 | ||
91 | 31/2 | 381 | 15 | 533.4 | 21 | ||
103 | 4 | 406.4 | 16 | 609.6 | 24 | ||
129 | 5 | 609.6 | 24 | 762 | 30 | ||
155 | 6 | 762 | 30 | 914.4 | 36 |
Table 4 Dimensions and Percent Area of Conduit and Tubing (Areas of Conduit or Tubing for the Combinations of Wires Permitted in Table 1, Chapter 9)
Article 358 — Electrical Metallic Tubing (EMT) | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
16 | 1/2 | 78 | 0.122 | 118 | 0.182 | 104 | 0.161 | 61 | 0.094 | 15.8 | 0.622 | 196 | 0.304 | |||||
21 | 3/4 | 137 | 0.213 | 206 | 0.320 | 182 | 0.283 | 106 | 0.165 | 20.9 | 0.824 | 343 | 0.533 | |||||
27 | 1 | 222 | 0.346 | 333 | 0.519 | 295 | 0.458 | 172 | 0.268 | 26.6 | 1.049 | 556 | 0.864 | |||||
35 | 11/4 | 387 | 0.598 | 581 | 0.897 | 513 | 0.793 | 300 | 0.464 | 35.1 | 1.380 | 968 | 1.496 | |||||
41 | 11/2 | 526 | 0.814 | 788 | 1.221 | 696 | 1.079 | 407 | 0.631 | 40.9 | 1.610 | 1314 | 2.036 | |||||
53 | 2 | 866 | 1.342 | 1299 | 2.013 | 1147 | 1.778 | 671 | 1.040 | 52.5 | 2.067 | 2165 | 3.356 | |||||
63 | 21/2 | 1513 | 2.343 | 2270 | 3.515 | 2005 | 3.105 | 1173 | 1.816 | 69.4 | 2.731 | 3783 | 5.858 | |||||
78 | 3 | 2280 | 3.538 | 3421 | 5.307 | 3022 | 4.688 | 1767 | 2.742 | 85.2 | 3.356 | 5701 | 8.846 | |||||
91 | 31/2 | 2980 | 4.618 | 4471 | 6.927 | 3949 | 6.119 | 2310 | 3.579 | 97.4 | 3.834 | 7451 | 11.545 | |||||
103 | 4 | 3808 | 5.901 | 5712 | 8.852 | 5046 | 7.819 | 2951 | 4.573 | 110.1 | 4.334 | 9521 | 14.753 | |||||
Article 362 — Electrical Nonmetallic Tubing (ENT) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
16 | 1/2 | 73 | 0.114 | 110 | 0.171 | 97 | 0.151 | 57 | 0.088 | 15.3 | 0.602 | 184 | 0.285 | |||||
21 | 3/4 | 131 | 0.203 | 197 | 0.305 | 174 | 0.269 | 102 | 0.157 | 20.4 | 0.804 | 328 | 0.508 | |||||
27 | 1 | 215 | 0.333 | 322 | 0.499 | 284 | 0.441 | 166 | 0.258 | 26.1 | 1.029 | 537 | 0.832 | |||||
35 | 11/4 | 375 | 0.581 | 562 | 0.872 | 497 | 0.770 | 291 | 0.450 | 34.5 | 1.36 | 937 | 1.453 | |||||
41 | 11/2 | 512 | 0.794 | 769 | 1.191 | 679 | 1.052 | 397 | 0.616 | 40.4 | 1.59 | 1281 | 1.986 | |||||
53 | 2 | 849 | 1.316 | 1274 | 1.975 | 1125 | 1.744 | 658 | 1.020 | 52 | 2.047 | 2123 | 3.291 | |||||
63 | 21/2 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
78 | 3 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
91 | 31/2 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
Article 348 — Flexible Metal Conduit (FMC) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | 30 | 0.046 | 44 | 0.069 | 39 | 0.061 | 23 | 0.036 | 9.7 | 0.384 | 74 | 0.116 | |||||
16 | 1/2 | 81 | 0.127 | 122 | 0.190 | 108 | 0.168 | 63 | 0.098 | 16.1 | 0.635 | 204 | 0.317 | |||||
21 | 3/4 | 137 | 0.213 | 206 | 0.320 | 182 | 0.283 | 106 | 0.165 | 20.9 | 0.824 | 343 | 0.533 | |||||
27 | 1 | 211 | 0.327 | 316 | 0.490 | 279 | 0.433 | 163 | 0.253 | 25.9 | 1.020 | 527 | 0.817 | |||||
35 | 11/4 | 330 | 0.511 | 495 | 0.766 | 437 | 0.677 | 256 | 0.396 | 32.4 | 1.275 | 824 | 1.277 | |||||
41 | 11/2 | 480 | 0.743 | 720 | 1.115 | 636 | 0.985 | 372 | 0.576 | 39.1 | 1.538 | 1201 | 1.858 | |||||
53 | 2 | 843 | 1.307 | 1264 | 1.961 | 1117 | 1.732 | 653 | 1.013 | 51.8 | 2.040 | 2107 | 3.269 | |||||
63 | 21/2 | 1267 | 1.963 | 1900 | 2.945 | 1678 | 2.602 | 982 | 1.522 | 63.5 | 2.500 | 3167 | 4.909 | |||||
78 | 3 | 1824 | 2.827 | 2736 | 4.241 | 2417 | 3.746 | 1414 | 2.191 | 76.2 | 3.000 | 4560 | 7.069 | |||||
91 | 31/2 | 2483 | 3.848 | 3724 | 5.773 | 3290 | 5.099 | 1924 | 2.983 | 88.9 | 3.500 | 6207 | 9.621 | |||||
103 | 4 | 3243 | 5.027 | 4864 | 7.540 | 4297 | 6.660 | 2513 | 3.896 | 101.6 | 4.000 | 8107 | 12.566 | |||||
Article 342 — Intermediate Metal Conduit (IMC) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
16 | 1/2 | 89 | 0.137 | 133 | 0.205 | 117 | 0.181 | 69 | 0.106 | 16.8 | 0.660 | 222 | 0.342 | |||||
21 | 3/4 | 151 | 0.235 | 226 | 0.352 | 200 | 0.311 | 117 | 0.182 | 21.9 | 0.864 | 377 | 0.586 | |||||
27 | 1 | 248 | 0.384 | 372 | 0.575 | 329 | 0.508 | 192 | 0.297 | 28.1 | 1.105 | 620 | 0.959 | |||||
35 | 11/4 | 425 | 0.659 | 638 | 0.988 | 564 | 0.873 | 330 | 0.510 | 36.8 | 1.448 | 1064 | 1.647 | |||||
41 | 11/2 | 573 | 0.890 | 859 | 1.335 | 759 | 1.179 | 444 | 0.690 | 42.7 | 1.683 | 1432 | 2.225 | |||||
53 | 2 | 937 | 1.452 | 1405 | 2.178 | 1241 | 1.924 | 726 | 1.125 | 54.6 | 2.150 | 2341 | 3.630 | |||||
63 | 21/2 | 1323 | 2.054 | 1985 | 3.081 | 1753 | 2.722 | 1026 | 1.592 | 64.9 | 2.557 | 3308 | 5.135 | |||||
78 | 3 | 2046 | 3.169 | 3069 | 4.753 | 2711 | 4.199 | 1586 | 2.456 | 80.7 | 3.176 | 5115 | 7.922 | |||||
91 | 31/2 | 2729 | 4.234 | 4093 | 6.351 | 3616 | 5.610 | 2115 | 3.281 | 93.2 | 3.671 | 6822 | 10.584 | |||||
103 | 4 | 3490 | 5.452 | 5235 | 8.179 | 4624 | 7.224 | 2705 | 4.226 | 105.4 | 4.166 | 8725 | 13.631 | |||||
Article 356 — Liquidtight Flexible Nonmetallic Conduit (LFNC-A*) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | 50 | 0.077 | 75 | 0.115 | 66 | 0.102 | 39 | 0.060 | 12.6 | 0.495 | 125 | 0.192 | |||||
16 | 1/2 | 80 | 0.125 | 121 | 0.187 | 107 | 0.165 | 62 | 0.097 | 16.0 | 0.630 | 201 | 0.312 | |||||
21 | 3/4 | 139 | 0.214 | 208 | 0.321 | 184 | 0.283 | 107 | 0.166 | 21.0 | 0.825 | 346 | 0.535 | |||||
27 | 1 | 221 | 0.342 | 331 | 0.513 | 292 | 0.453 | 171 | 0.265 | 26.5 | 1.043 | 552 | 0.854 | |||||
35 | 11/4 | 387 | 0.601 | 581 | 0.901 | 513 | 0.796 | 300 | 0.466 | 35.1 | 1.383 | 968 | 1.502 | |||||
41 | 11/2 | 520 | 0.807 | 781 | 1.211 | 690 | 1.070 | 403 | 0.626 | 40.7 | 1.603 | 1301 | 2.018 | |||||
53 | 2 | 863 | 1.337 | 1294 | 2.006 | 1143 | 1.772 | 669 | 1.036 | 52.4 | 2.063 | 2157 | 3.343 | |||||
*Corresponds to 356.2(1). | ||||||||||||||||||
Article 356 — Liquidtight Flexible Nonmetallic Conduit (LFNC-B*) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | 49 | 0.077 | 74 | 0.115 | 65 | 0.102 | 38 | 0.059 | 12.5 | 0.494 | 123 | 0.192 | |||||
16 | 1/2 | 81 | 0.125 | 122 | 0.188 | 108 | 0.166 | 63 | 0.097 | 16.1 | 0.632 | 204 | 0.314 | |||||
21 | 3/4 | 140 | 0.216 | 210 | 0.325 | 185 | 0.287 | 108 | 0.168 | 21.1 | 0.830 | 350 | 0.541 | |||||
27 | 1 | 226 | 0.349 | 338 | 0.524 | 299 | 0.462 | 175 | 0.270 | 26.8 | 1.054 | 564 | 0.873 | |||||
35 | 11/4 | 394 | 0.611 | 591 | 0.917 | 522 | 0.810 | 305 | 0.474 | 35.4 | 1.395 | 984 | 1.528 | |||||
41 | 11/2 | 510 | 0.792 | 765 | 1.188 | 676 | 1.050 | 395 | 0.614 | 40.3 | 1.588 | 1276 | 1.981 | |||||
53 | 2 | 836 | 1.298 | 1255 | 1.948 | 1108 | 1.720 | 648 | 1.006 | 51.6 | 2.033 | 2091 | 3.246 | |||||
*Corresponds to 356.2(2). | ||||||||||||||||||
Article 356 — Liquidtight Flexible Nonmetallic Conduit (LFNC-C*) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | 47.7 | 0.074 | 71.5 | 0.111 | 63.2 | 0.098 | 36.9 | 0.057 | 12.3 | 0.485 | 119.19 | 0.185 | |||||
16 | 1/2 | 77.9 | 0.121 | 116.9 | 0.181 | 103.2 | 0.160 | 60.4 | 0.094 | 15.7 | 0.620 | 194.778 | 0.302 | |||||
21 | 3/4 | 134.6 | 0.209 | 201.9 | 0.313 | 178.4 | 0.276 | 104.3 | 0.162 | 20.7 | 0.815 | 336.568 | 0.522 | |||||
27 | 1 | 215.0 | 0.333 | 322.5 | 0.500 | 284.9 | 0.442 | 166.6 | 0.258 | 26.2 | 1.030 | 537.566 | 0.833 | |||||
35 | 11/4 | 380.4 | 0.590 | 570.6 | 0.884 | 504.1 | 0.781 | 294.8 | 0.457 | 34.8 | 1.370 | 951.039 | 1.474 | |||||
41 | 11/2 | 509.2 | 0.789 | 763.8 | 1.184 | 674.7 | 1.046 | 394.6 | 0.612 | 40.3 | 1.585 | 1272.963 | 1.973 | |||||
53 | 2 | 847.6 | 1.314 | 1271.4 | 1.971 | 1123.1 | 1.741 | 656.9 | 1.018 | 51.9 | 2.045 | 2119.063 | 3.285 | |||||
*Corresponds to 356.2(3). | ||||||||||||||||||
Article 350 — Liquidtight Flexible Metal Conduit (LFMC) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | 49 | 0.077 | 74 | 0.115 | 65 | 0.102 | 38 | 0.059 | 12.5 | 0.494 | 123 | 0.192 | |||||
16 | 1/2 | 81 | 0.125 | 122 | 0.188 | 108 | 0.166 | 63 | 0.097 | 16.1 | 0.632 | 204 | 0.314 | |||||
21 | 3/4 | 140 | 0.216 | 210 | 0.325 | 185 | 0.287 | 108 | 0.168 | 21.1 | 0.830 | 350 | 0.541 | |||||
27 | 1 | 226 | 0.349 | 338 | 0.524 | 299 | 0.462 | 175 | 0.270 | 26.8 | 1.054 | 564 | 0.873 | |||||
35 | 11/4 | 394 | 0.611 | 591 | 0.917 | 522 | 0.810 | 305 | 0.474 | 35.4 | 1.395 | 984 | 1.528 | |||||
41 | 11/2 | 510 | 0.792 | 765 | 1.188 | 676 | 1.050 | 395 | 0.614 | 40.3 | 1.588 | 1276 | 1.981 | |||||
53 | 2 | 836 | 1.298 | 1255 | 1.948 | 1108 | 1.720 | 648 | 1.006 | 51.6 | 2.033 | 2091 | 3.246 | |||||
63 | 21/2 | 1259 | 1.953 | 1888 | 2.929 | 1668 | 2.587 | 976 | 1.513 | 63.3 | 2.493 | 3147 | 4.881 | |||||
78 | 3 | 1931 | 2.990 | 2896 | 4.485 | 2559 | 3.962 | 1497 | 2.317 | 78.4 | 3.085 | 4827 | 7.475 | |||||
91 | 31/2 | 2511 | 3.893 | 3766 | 5.839 | 3327 | 5.158 | 1946 | 3.017 | 89.4 | 3.520 | 6277 | 9.731 | |||||
103 | 4 | 3275 | 5.077 | 4912 | 7.615 | 4339 | 6.727 | 2538 | 3.935 | 102.1 | 4.020 | 8187 | 12.692 | |||||
129 | 5 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
155 | 6 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
Article 344 — Rigid Metal Conduit (RMC) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
16 | 1/2 | 81 | 0.125 | 122 | 0.188 | 108 | 0.166 | 63 | 0.097 | 16.1 | 0.632 | 204 | 0.314 | |||||
21 | 3/4 | 141 | 0.220 | 212 | 0.329 | 187 | 0.291 | 109 | 0.170 | 21.2 | 0.836 | 353 | 0.549 | |||||
27 | 1 | 229 | 0.355 | 344 | 0.532 | 303 | 0.470 | 177 | 0.275 | 27.0 | 1.063 | 573 | 0.887 | |||||
35 | 11/4 | 394 | 0.610 | 591 | 0.916 | 522 | 0.809 | 305 | 0.473 | 35.4 | 1.394 | 984 | 1.526 | |||||
41 | 11/2 | 533 | 0.829 | 800 | 1.243 | 707 | 1.098 | 413 | 0.642 | 41.2 | 1.624 | 1333 | 2.071 | |||||
53 | 2 | 879 | 1.363 | 1319 | 2.045 | 1165 | 1.806 | 681 | 1.056 | 52.9 | 2.083 | 2198 | 3.408 | |||||
63 | 21/2 | 1255 | 1.946 | 1882 | 2.919 | 1663 | 2.579 | 972 | 1.508 | 63.2 | 2.489 | 3137 | 4.866 | |||||
78 | 3 | 1936 | 3.000 | 2904 | 4.499 | 2565 | 3.974 | 1500 | 2.325 | 78.5 | 3.090 | 4840 | 7.499 | |||||
91 | 31/2 | 2584 | 4.004 | 3877 | 6.006 | 3424 | 5.305 | 2003 | 3.103 | 90.7 | 3.570 | 6461 | 10.010 | |||||
103 | 4 | 3326 | 5.153 | 4990 | 7.729 | 4408 | 6.828 | 2578 | 3.994 | 102.9 | 4.050 | 8316 | 12.882 | |||||
129 | 5 | 5220 | 8.085 | 7830 | 12.127 | 6916 | 10.713 | 4045 | 6.266 | 128.9 | 5.073 | 13050 | 20.212 | |||||
155 | 6 | 7528 | 11.663 | 11292 | 17.495 | 9975 | 15.454 | 5834 | 9.039 | 154.8 | 6.093 | 18821 | 29.158 | |||||
Article 352 — Rigid PVC Conduit (PVC), Schedule 80 | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
16 | 1/2 | 56 | 0.087 | 85 | 0.130 | 75 | 0.115 | 44 | 0.067 | 13.4 | 0.526 | 141 | 0.217 | |||||
21 | 3/4 | 105 | 0.164 | 158 | 0.246 | 139 | 0.217 | 82 | 0.127 | 18.3 | 0.722 | 263 | 0.409 | |||||
27 | 1 | 178 | 0.275 | 267 | 0.413 | 236 | 0.365 | 138 | 0.213 | 23.8 | 0.936 | 445 | 0.688 | |||||
35 | 11/4 | 320 | 0.495 | 480 | 0.742 | 424 | 0.656 | 248 | 0.383 | 31.9 | 1.255 | 799 | 1.237 | |||||
41 | 11/2 | 442 | 0.684 | 663 | 1.027 | 585 | 0.907 | 342 | 0.530 | 37.5 | 1.476 | 1104 | 1.711 | |||||
53 | 2 | 742 | 1.150 | 1113 | 1.725 | 983 | 1.523 | 575 | 0.891 | 48.6 | 1.913 | 1855 | 2.874 | |||||
63 | 21/2 | 1064 | 1.647 | 1596 | 2.471 | 1410 | 2.183 | 825 | 1.277 | 58.2 | 2.290 | 2660 | 4.119 | |||||
78 | 3 | 1660 | 2.577 | 2491 | 3.865 | 2200 | 3.414 | 1287 | 1.997 | 72.7 | 2.864 | 4151 | 6.442 | |||||
91 | 31/2 | 2243 | 3.475 | 3365 | 5.213 | 2972 | 4.605 | 1738 | 2.693 | 84.5 | 3.326 | 5608 | 8.688 | |||||
103 | 4 | 2907 | 4.503 | 4361 | 6.755 | 3852 | 5.967 | 2253 | 3.490 | 96.2 | 3.786 | 7268 | 11.258 | |||||
129 | 5 | 4607 | 7.142 | 6911 | 10.713 | 6105 | 9.463 | 3571 | 5.535 | 121.1 | 4.768 | 11518 | 17.855 | |||||
155 | 6 | 6605 | 10.239 | 9908 | 15.359 | 8752 | 13.567 | 5119 | 7.935 | 145.0 | 5.709 | 16513 | 25.598 | |||||
Articles 352 and 353 — Rigid PVC Conduit (PVC), Schedule 40, and HDPE Conduit (HDPE) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
12 | 3/8 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
16 | 1/2 | 74 | 0.114 | 110 | 0.171 | 97 | 0.151 | 57 | 0.088 | 15.3 | 0.602 | 184 | 0.285 | |||||
21 | 3/4 | 131 | 0.203 | 196 | 0.305 | 173 | 0.269 | 101 | 0.157 | 20.4 | 0.804 | 327 | 0.508 | |||||
27 | 1 | 214 | 0.333 | 321 | 0.499 | 284 | 0.441 | 166 | 0.258 | 26.1 | 1.029 | 535 | 0.832 | |||||
35 | 11/4 | 374 | 0.581 | 561 | 0.872 | 495 | 0.770 | 290 | 0.450 | 34.5 | 1.360 | 935 | 1.453 | |||||
41 | 11/2 | 513 | 0.794 | 769 | 1.191 | 679 | 1.052 | 397 | 0.616 | 40.4 | 1.590 | 1282 | 1.986 | |||||
53 | 2 | 849 | 1.316 | 1274 | 1.975 | 1126 | 1.744 | 658 | 1.020 | 52.0 | 2.047 | 2124 | 3.291 | |||||
63 | 21/2 | 1212 | 1.878 | 1817 | 2.817 | 1605 | 2.488 | 939 | 1.455 | 62.1 | 2.445 | 3029 | 4.695 | |||||
78 | 3 | 1877 | 2.907 | 2816 | 4.361 | 2487 | 3.852 | 1455 | 2.253 | 77.3 | 3.042 | 4693 | 7.268 | |||||
91 | 31/2 | 2511 | 3.895 | 3766 | 5.842 | 3327 | 5.161 | 1946 | 3.018 | 89.4 | 3.521 | 6277 | 9.737 | |||||
103 | 4 | 3237 | 5.022 | 4855 | 7.532 | 4288 | 6.654 | 2508 | 3.892 | 101.5 | 3.998 | 8091 | 12.554 | |||||
129 | 5 | 5099 | 7.904 | 7649 | 11.856 | 6756 | 10.473 | 3952 | 6.126 | 127.4 | 5.016 | 12748 | 19.761 | |||||
155 | 6 | 7373 | 11.427 | 11060 | 17.140 | 9770 | 15.141 | 5714 | 8.856 | 153.2 | 6.031 | 18433 | 28.567 | |||||
Article 352 — Type A, Rigid PVC Conduit (PVC) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
16 | 1/2 | 100 | 0.154 | 149 | 0.231 | 132 | 0.204 | 77 | 0.119 | 17.8 | 0.700 | 249 | 0.385 | |||||
21 | 3/4 | 168 | 0.260 | 251 | 0.390 | 222 | 0.345 | 130 | 0.202 | 23.1 | 0.910 | 419 | 0.650 | |||||
27 | 1 | 279 | 0.434 | 418 | 0.651 | 370 | 0.575 | 216 | 0.336 | 29.8 | 1.175 | 697 | 1.084 | |||||
35 | 11/4 | 456 | 0.707 | 684 | 1.060 | 604 | 0.937 | 353 | 0.548 | 38.1 | 1.500 | 1140 | 1.767 | |||||
41 | 11/2 | 600 | 0.929 | 900 | 1.394 | 795 | 1.231 | 465 | 0.720 | 43.7 | 1.720 | 1500 | 2.324 | |||||
53 | 2 | 940 | 1.459 | 1410 | 2.188 | 1245 | 1.933 | 728 | 1.131 | 54.7 | 2.155 | 2350 | 3.647 | |||||
63 | 21/2 | 1406 | 2.181 | 2109 | 3.272 | 1863 | 2.890 | 1090 | 1.690 | 66.9 | 2.635 | 3515 | 5.453 | |||||
78 | 3 | 2112 | 3.278 | 3169 | 4.916 | 2799 | 4.343 | 1637 | 2.540 | 82.0 | 3.230 | 5281 | 8.194 | |||||
91 | 31/2 | 2758 | 4.278 | 4137 | 6.416 | 3655 | 5.668 | 2138 | 3.315 | 93.7 | 3.690 | 6896 | 10.694 | |||||
103 | 4 | 3543 | 5.489 | 5315 | 8.234 | 4695 | 7.273 | 2746 | 4.254 | 106.2 | 4.180 | 8858 | 13.723 | |||||
129 | 5 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
155 | 6 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
Article 352 — Type EB, Rigid PVC Conduit (PVC) | ||||||||||||||||||
Metric Designator | Trade Size | Over 2 Wires 40% | 60% | 1 Wire 53% | 2 Wires 31% | Nominal Internal Diameter | Total Area 100% | |||||||||||
mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm2 | in.2 | mm | in. | mm2 | in.2 | |||||||
16 | 1/2 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
21 | 3/4 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
27 | 1 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
35 | 11/4 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
41 | 11/2 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
53 | 2 | 999 | 1.550 | 1499 | 2.325 | 1324 | 2.053 | 774 | 1.201 | 56.4 | 2.221 | 2498 | 3.874 | |||||
63 | 21/2 | — | — | — | — | — | — | — | — | — | — | — | — | |||||
78 | 3 | 2248 | 3.484 | 3373 | 5.226 | 2979 | 4.616 | 1743 | 2.700 | 84.6 | 3.330 | 5621 | 8.709 | |||||
91 | 31/2 | 2932 | 4.546 | 4397 | 6.819 | 3884 | 6.023 | 2272 | 3.523 | 96.6 | 3.804 | 7329 | 11.365 | |||||
103 | 4 | 3726 | 5.779 | 5589 | 8.669 | 4937 | 7.657 | 2887 | 4.479 | 108.9 | 4.289 | 9314 | 14.448 | |||||
129 | 5 | 5726 | 8.878 | 8588 | 13.317 | 7586 | 11.763 | 4437 | 6.881 | 135.0 | 5.316 | 14314 | 22.195 | |||||
155 | 6 | 8133 | 12.612 | 12200 | 18.918 | 10776 | 16.711 | 6303 | 9.774 | 160.9 | 6.336 | 20333 | 31.530 |
Table 5 Dimensions of Insulated Conductors and Fixture Wires
Type | Size (AWG or kcmil) | Approximate Area | Approximate Diameter | |||
---|---|---|---|---|---|---|
mm2 | in.2 | mm | in. | |||
Type: FFH-2, RFH-1, RFH-2, RFHH-2, RHH*, RHW*, RHW-2*, RHH, RHW, RHW-2, SF-1, SF-2, SFF-1, SFF-2, TF, TFF, THHW, THW, THW-2, TW, XF, XFF | ||||||
RFH-2, FFH-2, RFHH-2 | 18 | 9.355 | 0.0145 | 3.454 | 0.136 | |
16 | 11.10 | 0.0172 | 3.759 | 0.148 | ||
RHH, RHW, RHW-2 | 14 | 18.90 | 0.0293 | 4.902 | 0.193 | |
12 | 22.77 | 0.0353 | 5.385 | 0.212 | ||
10 | 28.19 | 0.0437 | 5.994 | 0.236 | ||
8 | 53.87 | 0.0835 | 8.280 | 0.326 | ||
6 | 67.16 | 0.1041 | 9.246 | 0.364 | ||
4 | 86.00 | 0.1333 | 10.46 | 0.412 | ||
3 | 98.13 | 0.1521 | 11.18 | 0.440 | ||
2 | 112.9 | 0.1750 | 11.99 | 0.472 | ||
1 | 171.6 | 0.2660 | 14.78 | 0.582 | ||
1/0 | 196.1 | 0.3039 | 15.80 | 0.622 | ||
2/0 | 226.1 | 0.3505 | 16.97 | 0.668 | ||
3/0 | 262.7 | 0.4072 | 18.29 | 0.720 | ||
4/0 | 306.7 | 0.4754 | 19.76 | 0.778 | ||
250 | 405.9 | 0.6291 | 22.73 | 0.895 | ||
300 | 457.3 | 0.7088 | 24.13 | 0.950 | ||
350 | 507.7 | 0.7870 | 25.43 | 1.001 | ||
400 | 556.5 | 0.8626 | 26.62 | 1.048 | ||
500 | 650.5 | 1.0082 | 28.78 | 1.133 | ||
600 | 782.9 | 1.2135 | 31.57 | 1.243 | ||
700 | 874.9 | 1.3561 | 33.38 | 1.314 | ||
750 | 920.8 | 1.4272 | 34.24 | 1.348 | ||
800 | 965.0 | 1.4957 | 35.05 | 1.380 | ||
900 | 1057 | 1.6377 | 36.68 | 1.444 | ||
1000 | 1143 | 1.7719 | 38.15 | 1.502 | ||
1250 | 1515 | 2.3479 | 43.92 | 1.729 | ||
1500 | 1738 | 2.6938 | 47.04 | 1.852 | ||
1750 | 1959 | 3.0357 | 49.94 | 1.966 | ||
2000 | 2175 | 3.3719 | 52.63 | 2.072 | ||
SF-2, SFF-2 | 18 | 7.419 | 0.0115 | 3.073 | 0.121 | |
16 | 8.968 | 0.0139 | 3.378 | 0.133 | ||
14 | 11.10 | 0.0172 | 3.759 | 0.148 | ||
SF-1, SFF-1 | 18 | 4.194 | 0.0065 | 2.311 | 0.091 | |
RFH-1,TF, TFF, XF, XFF | 18 | 5.161 | 0.0088 | 2.692 | 0.106 | |
TF, TFF, XF, XFF | 16 | 7.032 | 0.0109 | 2.997 | 0.118 | |
TW, XF, XFF, THHW, THW, THW-2 | 14 | 8.968 | 0.0139 | 3.378 | 0.133 | |
TW, THHW, THW, THW-2 | 12 | 11.68 | 0.0181 | 3.861 | 0.152 | |
10 | 15.68 | 0.0243 | 4.470 | 0.176 | ||
8 | 28.19 | 0.0437 | 5.994 | 0.236 | ||
RHH*, RHW*, RHW-2* | 14 | 13.48 | 0.0209 | 4.140 | 0.163 | |
RHH*, RHW*, RHW-2*, XF, XFF | 12 | 16.77 | 0.0260 | 4.623 | 0.182 | |
Type: RHH*, RHW*, RHW-2*, THHN, THHW, THW, THW-2, TFN, TFFN, THWN, THWN-2, XF, XFF | ||||||
RHH,* RHW,* RHW-2,* XF, XFF | 10 | 21.48 | 0.0333 | 5.232 | 0.206 | |
RHH*, RHW*, RHW-2* | 8 | 35.87 | 0.0556 | 6.756 | 0.266 | |
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2* | 6 | 46.84 | 0.0726 | 7.722 | 0.304 | |
4 | 62.77 | 0.0973 | 8.941 | 0.352 | ||
3 | 73.16 | 0.1134 | 9.652 | 0.380 | ||
2 | 86.00 | 0.1333 | 10.46 | 0.412 | ||
1 | 122.6 | 0.1901 | 12.50 | 0.492 | ||
1/0 | 143.4 | 0.2223 | 13.51 | 0.532 | ||
2/0 | 169.3 | 0.2624 | 14.68 | 0.578 | ||
3/0 | 201.1 | 0.3117 | 16.00 | 0.630 | ||
4/0 | 239.9 | 0.3718 | 17.48 | 0.688 | ||
250 | 296.5 | 0.4596 | 19.43 | 0.765 | ||
300 | 340.7 | 0.5281 | 20.83 | 0.820 | ||
350 | 384.4 | 0.5958 | 22.12 | 0.871 | ||
400 | 427.0 | 0.6619 | 23.32 | 0.918 | ||
500 | 509.7 | 0.7901 | 25.48 | 1.003 | ||
600 | 627.7 | 0.9729 | 28.27 | 1.113 | ||
700 | 710.3 | 1.1010 | 30.07 | 1.184 | ||
750 | 751.7 | 1.1652 | 30.94 | 1.218 | ||
800 | 791.7 | 1.2272 | 31.75 | 1.250 | ||
900 | 874.9 | 1.3561 | 33.38 | 1.314 | ||
1000 | 953.8 | 1.4784 | 34.85 | 1.372 | ||
1250 | 1200 | 1.8602 | 39.09 | 1.539 | ||
1500 | 1400 | 2.1695 | 42.21 | 1.662 | ||
1750 | 1598 | 2.4773 | 45.11 | 1.776 | ||
2000 | 1795 | 2.7818 | 47.80 | 1.882 | ||
TFN, TFFN | 18 | 3.548 | 0.0055 | 2.134 | 0.084 | |
16 | 4.645 | 0.0072 | 2.438 | 0.096 | ||
THHN, THWN, THWN-2 | 14 | 6.258 | 0.0097 | 2.819 | 0.111 | |
12 | 8.581 | 0.0133 | 3.302 | 0.130 | ||
10 | 13.61 | 0.0211 | 4.166 | 0.164 | ||
8 | 23.61 | 0.0366 | 5.486 | 0.216 | ||
6 | 32.71 | 0.0507 | 6.452 | 0.254 | ||
4 | 53.16 | 0.0824 | 8.230 | 0.324 | ||
3 | 62.77 | 0.0973 | 8.941 | 0.352 | ||
2 | 74.71 | 0.1158 | 9.754 | 0.384 | ||
1 | 100.8 | 0.1562 | 11.33 | 0.446 | ||
1/0 | 119.7 | 0.1855 | 12.34 | 0.486 | ||
2/0 | 143.4 | 0.2223 | 13.51 | 0.532 | ||
3/0 | 172.8 | 0.2679 | 14.83 | 0.584 | ||
4/0 | 208.8 | 0.3237 | 16.31 | 0.642 | ||
250 | 256.1 | 0.3970 | 18.06 | 0.711 | ||
300 | 297.3 | 0.4608 | 19.46 | 0.766 | ||
Type: FEP, FEPB, PAF, PAFF, PF, PFA, PFAH, PFF, PGF, PGFF, PTF, PTFF, TFE, THHN, THWN, THWN-2, Z, ZF, ZFF, ZHF | ||||||
THHN, THWN, THWN-2 | 350 | 338.2 | 0.5242 | 20.75 | 0.817 | |
400 | 378.3 | 0.5863 | 21.95 | 0.864 | ||
500 | 456.3 | 0.7073 | 24.10 | 0.949 | ||
600 | 559.7 | 0.8676 | 26.70 | 1.051 | ||
700 | 637.9 | 0.9887 | 28.50 | 1.122 | ||
750 | 677.2 | 1.0496 | 29.36 | 1.156 | ||
800 | 715.2 | 1.1085 | 30.18 | 1.188 | ||
900 | 794.3 | 1.2311 | 31.80 | 1.252 | ||
1000 | 869.5 | 1.3478 | 33.27 | 1.310 | ||
PF, PGFF, PGF, PFF, PTF, PAF, PTFF, PAFF | 18 | 3.742 | 0.0058 | 2.184 | 0.086 | |
16 | 4.839 | 0.0075 | 2.489 | 0.098 | ||
PF, PGFF, PGF, PFF, PTF, PAF, PTFF, PAFF, TFE, FEP, PFA, FEPB, PFAH | 14 | 6.452 | 0.0100 | 2.870 | 0.113 | |
TFE, FEP, PFA, FEPB, PFAH | 12 | 8.839 | 0.0137 | 3.353 | 0.132 | |
10 | 12.32 | 0.0191 | 3.962 | 0.156 | ||
8 | 21.48 | 0.0333 | 5.232 | 0.206 | ||
6 | 30.19 | 0.0468 | 6.198 | 0.244 | ||
4 | 43.23 | 0.0670 | 7.417 | 0.292 | ||
3 | 51.87 | 0.0804 | 8.128 | 0.320 | ||
2 | 62.77 | 0.0973 | 8.941 | 0.352 | ||
TFE, PFAH, PFA | 1 | 90.26 | 0.1399 | 10.72 | 0.422 | |
TFE, PFA, PFAH, Z | 1/0 | 108.1 | 0.1676 | 11.73 | 0.462 | |
2/0 | 130.8 | 0.2027 | 12.90 | 0.508 | ||
3/0 | 158.9 | 0.2463 | 14.22 | 0.560 | ||
4/0 | 193.5 | 0.3000 | 15.70 | 0.618 | ||
ZF, ZFF, ZHF | 18 | 2.903 | 0.0045 | 1.930 | 0.076 | |
16 | 3.935 | 0.0061 | 2.235 | 0.088 | ||
Z, ZF, ZFF, ZHF | 14 | 5.355 | 0.0083 | 2.616 | 0.103 | |
Z | 12 | 7.548 | 0.0117 | 3.099 | 0.122 | |
10 | 12.32 | 0.0191 | 3.962 | 0.156 | ||
8 | 19.48 | 0.0302 | 4.978 | 0.196 | ||
6 | 27.74 | 0.0430 | 5.944 | 0.234 | ||
4 | 40.32 | 0.0625 | 7.163 | 0.282 | ||
3 | 55.16 | 0.0855 | 8.382 | 0.330 | ||
2 | 66.39 | 0.1029 | 9.195 | 0.362 | ||
1 | 81.87 | 0.1269 | 10.21 | 0.402 | ||
Type: KF-1, KF-2, KFF-1, KFF-2, XHH, XHHW, XHHW-2, ZW | ||||||
XHHW, ZW, XHHW-2, XHH | 14 | 8.968 | 0.0139 | 3.378 | 0.133 | |
12 | 11.68 | 0.0181 | 3.861 | 0.152 | ||
10 | 15.68 | 0.0243 | 4.470 | 0.176 | ||
8 | 28.19 | 0.0437 | 5.994 | 0.236 | ||
6 | 38.06 | 0.0590 | 6.960 | 0.274 | ||
4 | 52.52 | 0.0814 | 8.179 | 0.322 | ||
3 | 62.06 | 0.0962 | 8.890 | 0.350 | ||
2 | 73.94 | 0.1146 | 9.703 | 0.382 | ||
XHHW, XHHW-2, XHH | 1 | 98.97 | 0.1534 | 11.23 | 0.442 | |
1/0 | 117.7 | 0.1825 | 12.24 | 0.482 | ||
2/0 | 141.3 | 0.2190 | 13.41 | 0.528 | ||
3/0 | 170.5 | 0.2642 | 14.73 | 0.58 | ||
4/0 | 206.3 | 0.3197 | 16.21 | 0.638 | ||
250 | 251.9 | 0.3904 | 17.91 | 0.705 | ||
300 | 292.6 | 0.4536 | 19.30 | 0.76 | ||
350 | 333.3 | 0.5166 | 20.60 | 0.811 | ||
400 | 373.0 | 0.5782 | 21.79 | 0.858 | ||
500 | 450.6 | 0.6984 | 23.95 | 0.943 | ||
600 | 561.9 | 0.8709 | 26.75 | 1.053 | ||
700 | 640.2 | 0.9923 | 28.55 | 1.124 | ||
750 | 679.5 | 1.0532 | 29.41 | 1.158 | ||
800 | 717.5 | 1.1122 | 30.23 | 1.190 | ||
900 | 796.8 | 1.2351 | 31.85 | 1.254 | ||
1000 | 872.2 | 1.3519 | 33.32 | 1.312 | ||
1250 | 1108 | 1.7180 | 37.57 | 1.479 | ||
1500 | 1300 | 2.0156 | 40.69 | 1.602 | ||
1750 | 1492 | 2.3127 | 43.59 | 1.716 | ||
2000 | 1682 | 2.6073 | 46.28 | 1.822 | ||
KF-2, KFF-2 | 18 | 2.000 | 0.003 | 1.575 | 0.062 | |
16 | 2.839 | 0.0043 | 1.88 | 0.074 | ||
14 | 4.129 | 0.0064 | 2.286 | 0.090 | ||
12 | 6.000 | 0.0092 | 2.743 | 0.108 | ||
10 | 8.968 | 0.0139 | 3.378 | 0.133 | ||
KF-1, KFF-1 | 18 | 1.677 | 0.0026 | 1.448 | 0.057 | |
16 | 2.387 | 0.0037 | 1.753 | 0.069 | ||
14 | 3.548 | 0.0055 | 2.134 | 0.084 | ||
12 | 5.355 | 0.0083 | 2.616 | 0.103 | ||
10 | 8.194 | 0.0127 | 3.226 | 0.127 | ||
*Types RHH, RHW, and RHW-2 without outer covering. |
Table 5A Compact Copper and Aluminum Building Wire Nominal Dimensions** and Areas
Size (AWG or kcmil) | Bare Conductor | Types RHH* | Types THW and THHW | Type THHN | Type XHHW | Size (AWG or kcmil) | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter | Approximate Diameter | Approximate Area | Approximate Diameter | Approximate Area | Approximate Diameter | Approximate Area | Approximate Diameter | Approximate Area | |||||||||||
mm | in. | mm | in. | mm2 | in.2 | mm | in. | mm2 | in.2 | mm | in. | mm2 | in.2 | mm | in. | mm2 | in.2 | ||
8 | 3.404 | 0.134 | 6.604 | 0.260 | 34.25 | 0.0531 | 6.477 | 0.255 | 32.90 | 0.0510 | — | — | — | — | 5.690 | 0.224 | 25.42 | 0.0394 | 8 |
6 | 4.293 | 0.169 | 7.493 | 0.295 | 44.10 | 0.0683 | 7.366 | 0.290 | 42.58 | 0.0660 | 6.096 | 0.240 | 29.16 | 0.0452 | 6.604 | 0.260 | 34.19 | 0.0530 | 6 |
4 | 5.410 | 0.213 | 8.509 | 0.335 | 56.84 | 0.0881 | 8.509 | 0.335 | 56.84 | 0.0881 | 7.747 | 0.305 | 47.10 | 0.0730 | 7.747 | 0.305 | 47.10 | 0.0730 | 4 |
2 | 6.807 | 0.268 | 9.906 | 0.390 | 77.03 | 0.1194 | 9.906 | 0.390 | 77.03 | 0.1194 | 9.144 | 0.360 | 65.61 | 0.1017 | 9.144 | 0.360 | 65.61 | 0.1017 | 2 |
1 | 7.595 | 0.299 | 11.81 | 0.465 | 109.5 | 0.1698 | 11.81 | 0.465 | 109.5 | 0.1698 | 10.54 | 0.415 | 87.23 | 0.1352 | 10.54 | 0.415 | 87.23 | 0.1352 | 1 |
1/0 | 8.534 | 0.336 | 12.70 | 0.500 | 126.6 | 0.1963 | 12.70 | 0.500 | 126.6 | 0.1963 | 11.43 | 0.450 | 102.6 | 0.1590 | 11.43 | 0.450 | 102.6 | 0.1590 | 1/0 |
2/0 | 9.550 | 0.376 | 13.72 | 0.540 | 147.8 | 0.2290 | 13.84 | 0.545 | 150.5 | 0.2332 | 12.57 | 0.495 | 124.1 | 0.1924 | 12.45 | 0.490 | 121.6 | 0.1885 | 2/0 |
3/0 | 10.74 | 0.423 | 14.99 | 0.590 | 176.3 | 0.2733 | 14.99 | 0.590 | 176.3 | 0.2733 | 13.72 | 0.540 | 147.7 | 0.2290 | 13.72 | 0.540 | 147.7 | 0.2290 | 3/0 |
4/0 | 12.07 | 0.475 | 16.26 | 0.640 | 207.6 | 0.3217 | 16.38 | 0.645 | 210.8 | 0.3267 | 15.11 | 0.595 | 179.4 | 0.2780 | 14.99 | 0.590 | 176.3 | 0.2733 | 4/0 |
250 | 13.21 | 0.520 | 18.16 | 0.715 | 259.0 | 0.4015 | 18.42 | 0.725 | 266.3 | 0.4128 | 17.02 | 0.670 | 227.4 | 0.3525 | 16.76 | 0.660 | 220.7 | 0.3421 | 250 |
300 | 14.48 | 0.570 | 19.43 | 0.765 | 296.5 | 0.4596 | 19.69 | 0.775 | 304.3 | 0.4717 | 18.29 | 0.720 | 262.6 | 0.4071 | 18.16 | 0.715 | 259.0 | 0.4015 | 300 |
350 | 15.65 | 0.616 | 20.57 | 0.810 | 332.3 | 0.5153 | 20.83 | 0.820 | 340.7 | 0.5281 | 19.56 | 0.770 | 300.4 | 0.4656 | 19.30 | 0.760 | 292.6 | 0.4536 | 350 |
400 | 16.74 | 0.659 | 21.72 | 0.855 | 370.5 | 0.5741 | 21.97 | 0.865 | 379.1 | 0.5876 | 20.70 | 0.815 | 336.5 | 0.5216 | 20.32 | 0.800 | 324.3 | 0.5026 | 400 |
500 | 18.69 | 0.736 | 23.62 | 0.930 | 438.2 | 0.6793 | 23.88 | 0.940 | 447.7 | 0.6939 | 22.48 | 0.885 | 396.8 | 0.6151 | 22.35 | 0.880 | 392.4 | 0.6082 | 500 |
600 | 20.65 | 0.813 | 26.29 | 1.035 | 542.8 | 0.8413 | 26.67 | 1.050 | 558.6 | 0.8659 | 25.02 | 0.985 | 491.6 | 0.7620 | 24.89 | 0.980 | 486.6 | 0.7542 | 600 |
700 | 22.28 | 0.877 | 27.94 | 1.100 | 613.1 | 0.9503 | 28.19 | 1.110 | 624.3 | 0.9676 | 26.67 | 1.050 | 558.6 | 0.8659 | 26.67 | 1.050 | 558.6 | 0.8659 | 700 |
750 | 23.06 | 0.908 | 28.83 | 1.135 | 652.8 | 1.0118 | 29.21 | 1.150 | 670.1 | 1.0386 | 27.31 | 1.075 | 585.5 | 0.9076 | 27.69 | 1.090 | 602.0 | 0.9331 | 750 |
900 | 25.37 | 0.999 | 31.50 | 1.240 | 779.3 | 1.2076 | 31.09 | 1.224 | 759.1 | 1.1766 | 30.33 | 1.194 | 722.5 | 1.1196 | 29.69 | 1.169 | 692.3 | 1.0733 | 900 |
1000 | 26.92 | 1.060 | 32.64 | 1.285 | 836.6 | 1.2968 | 32.64 | 1.285 | 836.6 | 1.2968 | 31.88 | 1.255 | 798.1 | 1.2370 | 31.24 | 1.230 | 766.6 | 1.1882 | 1000 |
*Types RHH and RHW without outer coverings. | |||||||||||||||||||
**Dimensions are from industry sources. |
Table 8 Conductor Properties
Size (AWG or kcmil) | Area | Conductors | Direct-Current Resistance at 75°C (167°F) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Stranding | Overall | Copper | |||||||||||||
Diameter | Diameter | Area | Uncoated | Coated | Aluminum | ||||||||||
mm2 | Circular mils | Quantity | mm | in. | mm | in. | mm2 | in.2 | ohm/km | ohm/kFT | ohm/km | ohm/kFT | ohm/km | ohm/kFT | |
18 | 0.823 | 1620 | 1 | — | — | 1.02 | 0.040 | 0.823 | 0.001 | 25.5 | 7.77 | 26.5 | 8.08 | 42.0 | 12.8 |
18 | 0.823 | 1620 | 7 | 0.39 | 0.015 | 1.16 | 0.046 | 1.06 | 0.002 | 26.1 | 7.95 | 27.7 | 8.45 | 42.8 | 13.1 |
16 | 1.31 | 2580 | 1 | — | — | 1.29 | 0.051 | 1.31 | 0.002 | 16.0 | 4.89 | 16.7 | 5.08 | 26.4 | 8.05 |
16 | 1.31 | 2580 | 7 | 0.49 | 0.019 | 1.46 | 0.058 | 1.68 | 0.003 | 16.4 | 4.99 | 17.3 | 5.29 | 26.9 | 8.21 |
14 | 2.08 | 4110 | 1 | — | — | 1.63 | 0.064 | 2.08 | 0.003 | 10.1 | 3.07 | 10.4 | 3.19 | 16.6 | 5.06 |
14 | 2.08 | 4110 | 7 | 0.62 | 0.024 | 1.85 | 0.073 | 2.68 | 0.004 | 10.3 | 3.14 | 10.7 | 3.26 | 16.9 | 5.17 |
12 | 3.31 | 6530 | 1 | — | — | 2.05 | 0.081 | 3.31 | 0.005 | 6.34 | 1.93 | 6.57 | 2.01 | 10.45 | 3.18 |
12 | 3.31 | 6530 | 7 | 0.78 | 0.030 | 2.32 | 0.092 | 4.25 | 0.006 | 6.50 | 1.98 | 6.73 | 2.05 | 10.69 | 3.25 |
10 | 5.261 | 10380 | 1 | — | — | 2.588 | 0.102 | 5.26 | 0.008 | 3.984 | 1.21 | 4.148 | 1.26 | 6.561 | 2.00 |
10 | 5.261 | 10380 | 7 | 0.98 | 0.038 | 2.95 | 0.116 | 6.76 | 0.011 | 4.070 | 1.24 | 4.226 | 1.29 | 6.679 | 2.04 |
8 | 8.367 | 16510 | 1 | — | — | 3.264 | 0.128 | 8.37 | 0.013 | 2.506 | 0.764 | 2.579 | 0.786 | 4.125 | 1.26 |
8 | 8.367 | 16510 | 7 | 1.23 | 0.049 | 3.71 | 0.146 | 10.76 | 0.017 | 2.551 | 0.778 | 2.653 | 0.809 | 4.204 | 1.28 |
6 | 13.30 | 26240 | 7 | 1.56 | 0.061 | 4.67 | 0.184 | 17.09 | 0.027 | 1.608 | 0.491 | 1.671 | 0.510 | 2.652 | 0.808 |
4 | 21.15 | 41740 | 7 | 1.96 | 0.077 | 5.89 | 0.232 | 27.19 | 0.042 | 1.010 | 0.308 | 1.053 | 0.321 | 1.666 | 0.508 |
3 | 26.67 | 52620 | 7 | 2.20 | 0.087 | 6.60 | 0.260 | 34.28 | 0.053 | 0.802 | 0.245 | 0.833 | 0.254 | 1.320 | 0.403 |
2 | 33.62 | 66360 | 7 | 2.47 | 0.097 | 7.42 | 0.292 | 43.23 | 0.067 | 0.634 | 0.194 | 0.661 | 0.201 | 1.045 | 0.319 |
1 | 42.41 | 83690 | 19 | 1.69 | 0.066 | 8.43 | 0.332 | 55.80 | 0.087 | 0.505 | 0.154 | 0.524 | 0.160 | 0.829 | 0.253 |
1/0
|
53.49 | 105600 | 19 | 1.89 | 0.074 | 9.45 | 0.372 | 70.41 | 0.109 | 0.399 | 0.122 | 0.415 | 0.127 | 0.660 | 0.201 |
2/0
|
67.43 | 133100 | 19 | 2.13 | 0.084 | 10.62 | 0.418 | 88.74 | 0.137 | 0.3170 | 0.0967 | 0.329 | 0.101 | 0.523 | 0.159 |
3/0
|
85.01 | 167800 | 19 | 2.39 | 0.094 | 11.94 | 0.470 | 111.9 | 0.173 | 0.2512 | 0.0766 | 0.2610 | 0.0797 | 0.413 | 0.126 |
4/0
|
107.2 | 211600 | 19 | 2.68 | 0.106 | 13.41 | 0.528 | 141.1 | 0.219 | 0.1996 | 0.0608 | 0.2050 | 0.0626 | 0.328 | 0.100 |
250 | 127 | — | 37 | 2.09 | 0.082 | 14.61 | 0.575 | 168 | 0.260 | 0.1687 | 0.0515 | 0.1753 | 0.0535 | 0.2778 | 0.0847 |
300 | 152 | — | 37 | 2.29 | 0.090 | 16.00 | 0.630 | 201 | 0.312 | 0.1409 | 0.0429 | 0.1463 | 0.0446 | 0.2318 | 0.0707 |
350 | 177 | — | 37 | 2.47 | 0.097 | 17.30 | 0.681 | 235 | 0.364 | 0.1205 | 0.0367 | 0.1252 | 0.0382 | 0.1984 | 0.0605 |
400 | 203 | — | 37 | 2.64 | 0.104 | 18.49 | 0.728 | 268 | 0.416 | 0.1053 | 0.0321 | 0.1084 | 0.0331 | 0.1737 | 0.0529 |
500 | 253 | — | 37 | 2.95 | 0.116 | 20.65 | 0.813 | 336 | 0.519 | 0.0845 | 0.0258 | 0.0869 | 0.0265 | 0.1391 | 0.0424 |
600 | 304 | — | 61 | 2.52 | 0.099 | 22.68 | 0.893 | 404 | 0.626 | 0.0704 | 0.0214 | 0.0732 | 0.0223 | 0.1159 | 0.0353 |
700 | 355 | — | 61 | 2.72 | 0.107 | 24.49 | 0.964 | 471 | 0.730 | 0.0603 | 0.0184 | 0.0622 | 0.0189 | 0.0994 | 0.0303 |
750 | 380 | — | 61 | 2.82 | 0.111 | 25.35 | 0.998 | 505 | 0.782 | 0.0563 | 0.0171 | 0.0579 | 0.0176 | 0.0927 | 0.0282 |
800 | 405 | — | 61 | 2.91 | 0.114 | 26.16 | 1.030 | 538 | 0.834 | 0.0528 | 0.0161 | 0.0544 | 0.0166 | 0.0868 | 0.0265 |
900 | 456 | — | 61 | 3.09 | 0.122 | 27.79 | 1.094 | 606 | 0.940 | 0.0470 | 0.0143 | 0.0481 | 0.0147 | 0.0770 | 0.0235 |
1000 | 507 | — | 61 | 3.25 | 0.128 | 29.26 | 1.152 | 673 | 1.042 | 0.0423 | 0.0129 | 0.0434 | 0.0132 | 0.0695 | 0.0212 |
1250 | 633 | — | 91 | 2.98 | 0.117 | 32.74 | 1.289 | 842 | 1.305 | 0.0338 | 0.0103 | 0.0347 | 0.0106 | 0.0554 | 0.0169 |
1500 | 760 | — | 91 | 3.26 | 0.128 | 35.86 | 1.412 | 1011 | 1.566 | 0.02814 | 0.00858 | 0.02814 | 0.00883 | 0.0464 | 0.0141 |
1750 | 887 | — | 127 | 2.98 | 0.117 | 38.76 | 1.526 | 1180 | 1.829 | 0.02410 | 0.00735 | 0.02410 | 0.00756 | 0.0397 | 0.0121 |
2000 | 1013 | — | 127 | 3.19 | 0.126 | 41.45 | 1.632 | 1349 | 2.092 | 0.02109 | 0.00643 | 0.02109 | 0.00662 | 0.0348 | 0.0106 |
Notes: 1. These resistance values are valid only for the parameters as given. Using conductors having coated strands, different stranding type, and, especially, other temperatures changes the resistance. |
|||||||||||||||
2. Equation for temperature change: R2 = R1 [1 + a (T2—75)], where αcu = 0.00323, αAL = 0.00330 at 75°C. | |||||||||||||||
3. Conductors with compact and compressed stranding have about 9 percent and 3 percent, respectively, smaller bare conductor diameters than those shown. See Table 5A for actual compact cable dimensions. | |||||||||||||||
4. The IACS conductivities used: bare copper = 100%, aluminum = 61%. | |||||||||||||||
5. Class B stranding is listed as well as solid for some sizes. Its overall diameter and area are those of its circumscribing circle. | |||||||||||||||
Informational Note: The construction information is in accordance with NEMA WC/70-2009 or ANSI/UL 1581-2017. | |||||||||||||||
The resistance is calculated in accordance with National Bureau of Standards Handbook 100, dated 1966, and Handbook 109, dated 1972. |
Table 9 Alternating-Current Resistance and Reactance for 600-Volt Cables, 3-Phase, 60 Hz, 75°C (167°F) — Three Single Conductors in Conduit
Size (AWG or kcmil) | Ohms to Neutral per Kilometer Ohms to Neutral per 1000 Feet |
Size (AWG or kcmil) | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
XL (Reactance) for All Wires | Alternating-Current Resistance for Uncoated Copper Wires | Alternating-Current Resistance for Aluminum Wires | Effective Z at 0.85 PF for Uncoated Copper Wires | Effective Z at 0.85 PF for Aluminum Wires | |||||||||||
PVC, Aluminum Conduits | Steel Conduit | PVC Conduit | Aluminum Conduit | Steel Conduit | PVC Conduit | Aluminum Conduit | Steel Conduit | PVC Conduit | Aluminum Conduit | Steel Conduit | PVC Conduit | Aluminum Conduit | Steel Conduit | ||
14 | 0.190 | 0.240 | 10.2 | 10.2 | 10.2 | — | — | — | 8.9 | 8.9 | 8.9 | — | — | — | 14 |
0.058 | 0.073 | 3.1 | 3.1 | 3.1 | — | — | — | 2.7 | 2.7 | 2.7 | — | — | — | ||
12 | 0.177 | 0.223 | 6.6 | 6.6 | 6.6 | 10.5 | 10.5 | 10.5 | 5.6 | 5.6 | 5.6 | 9.2 | 9.2 | 9.2 | 12 |
0.054 | 0.068 | 2.0 | 2.0 | 2.0 | 3.2 | 3.2 | 3.2 | 1.7 | 1.7 | 1.7 | 2.8 | 2.8 | 2.8 | ||
10 | 0.164 | 0.207 | 3.9 | 3.9 | 3.9 | 6.6 | 6.6 | 6.6 | 3.6 | 3.6 | 3.6 | 5.9 | 5.9 | 5.9 | 10 |
0.050 | 0.063 | 1.2 | 1.2 | 1.2 | 2.0 | 2.0 | 2.0 | 1.1 | 1.1 | 1.1 | 1.8 | 1.8 | 1.8 | ||
8 | 0.171 | 0.213 | 2.56 | 2.56 | 2.56 | 4.3 | 4.3 | 4.3 | 2.26 | 2.26 | 2.30 | 3.6 | 3.6 | 3.6 | 8 |
0.052 | 0.065 | 0.78 | 0.78 | 0.78 | 1.3 | 1.3 | 1.3 | 0.69 | 0.69 | 0.70 | 1.1 | 1.1 | 1.1 | ||
6 | 0.167 | 0.210 | 1.61 | 1.61 | 1.61 | 2.66 | 2.66 | 2.66 | 1.44 | 1.48 | 1.48 | 2.33 | 2.36 | 2.36 | 6 |
0.051 | 0.064 | 0.49 | 0.49 | 0.49 | 0.81 | 0.81 | 0.81 | 0.44 | 0.45 | 0.45 | 0.71 | 0.72 | 0.72 | ||
4 | 0.157 | 0.197 | 1.02 | 1.02 | 1.02 | 1.67 | 1.67 | 1.67 | 0.95 | 0.95 | 0.98 | 1.51 | 1.51 | 1.51 | 4 |
0.048 | 0.060 | 0.31 | 0.31 | 0.31 | 0.51 | 0.51 | 0.51 | 0.29 | 0.29 | 0.30 | 0.46 | 0.46 | 0.46 | ||
3 | 0.154 | 0.194 | 0.82 | 0.82 | 0.82 | 1.31 | 1.35 | 1.31 | 0.75 | 0.79 | 0.79 | 1.21 | 1.21 | 1.21 | 3 |
0.047 | 0.059 | 0.25 | 0.25 | 0.25 | 0.40 | 0.41 | 0.40 | 0.23 | 0.24 | 0.24 | 0.37 | 0.37 | 0.37 | ||
2 | 0.148 | 0.187 | 0.62 | 0.66 | 0.66 | 1.05 | 1.05 | 1.05 | 0.62 | 0.62 | 0.66 | 0.98 | 0.98 | 0.98 | 2 |
0.045 | 0.057 | 0.19 | 0.20 | 0.20 | 0.32 | 0.32 | 0.32 | 0.19 | 0.19 | 0.20 | 0.30 | 0.30 | 0.30 | ||
1 | 0.151 | 0.187 | 0.49 | 0.52 | 0.52 | 0.82 | 0.85 | 0.82 | 0.52 | 0.52 | 0.52 | 0.79 | 0.79 | 0.82 | 1 |
0.046 | 0.057 | 0.15 | 0.16 | 0.16 | 0.25 | 0.26 | 0.25 | 0.16 | 0.16 | 0.16 | 0.24 | 0.24 | 0.25 | ||
1/0 | 0.144 | 0.180 | 0.39 | 0.43 | 0.39 | 0.66 | 0.69 | 0.66 | 0.43 | 0.43 | 0.43 | 0.62 | 0.66 | 0.66 | 1/0 |
0.044 | 0.055 | 0.12 | 0.13 | 0.12 | 0.20 | 0.21 | 0.20 | 0.13 | 0.13 | 0.13 | 0.19 | 0.20 | 0.20 | ||
2/0 | 0.141 | 0.177 | 0.33 | 0.33 | 0.33 | 0.52 | 0.52 | 0.52 | 0.36 | 0.36 | 0.36 | 0.52 | 0.52 | 0.52 | 2/0 |
0.043 | 0.054 | 0.10 | 0.10 | 0.10 | 0.16 | 0.16 | 0.16 | 0.11 | 0.11 | 0.11 | 0.16 | 0.16 | 0.16 | ||
3/0 | 0.138 | 0.171 | 0.253 | 0.269 | 0.259 | 0.43 | 0.43 | 0.43 | 0.289 | 0.302 | 0.308 | 0.43 | 0.43 | 0.46 | 3/0 |
0.042 | 0.052 | 0.077 | 0.082 | 0.079 | 0.13 | 0.13 | 0.13 | 0.088 | 0.092 | 0.094 | 0.13 | 0.13 | 0.14 | ||
4/0 | 0.135 | 0.167 | 0.203 | 0.220 | 0.207 | 0.33 | 0.36 | 0.33 | 0.243 | 0.256 | 0.262 | 0.36 | 0.36 | 0.36 | 4/0 |
0.041 | 0.051 | 0.062 | 0.067 | 0.063 | 0.10 | 0.11 | 0.10 | 0.074 | 0.078 | 0.080 | 0.11 | 0.11 | 0.11 | ||
250 | 0.135 | 0.171 | 0.171 | 0.187 | 0.177 | 0.279 | 0.295 | 0.282 | 0.217 | 0.230 | 0.240 | 0.308 | 0.322 | 0.33 | 250 |
0.041 | 0.052 | 0.052 | 0.057 | 0.054 | 0.085 | 0.090 | 0.086 | 0.066 | 0.070 | 0.073 | 0.094 | 0.098 | 0.10 | ||
300 | 0.135 | 0.167 | 0.144 | 0.161 | 0.148 | 0.233 | 0.249 | 0.236 | 0.194 | 0.207 | 0.213 | 0.269 | 0.282 | 0.289 | 300 |
0.041 | 0.051 | 0.044 | 0.049 | 0.045 | 0.071 | 0.076 | 0.072 | 0.059 | 0.063 | 0.065 | 0.082 | 0.086 | 0.088 | ||
350 | 0.131 | 0.164 | 0.125 | 0.141 | 0.128 | 0.200 | 0.217 | 0.207 | 0.174 | 0.190 | 0.197 | 0.240 | 0.253 | 0.262 | 350 |
0.040 | 0.050 | 0.038 | 0.043 | 0.039 | 0.061 | 0.066 | 0.063 | 0.053 | 0.058 | 0.060 | 0.073 | 0.077 | 0.080 | ||
400 | 0.131 | 0.161 | 0.108 | 0.125 | 0.115 | 0.177 | 0.194 | 0.180 | 0.161 | 0.174 | 0.184 | 0.217 | 0.233 | 0.240 | 400 |
0.040 | 0.049 | 0.033 | 0.038 | 0.035 | 0.054 | 0.059 | 0.055 | 0.049 | 0.053 | 0.056 | 0.066 | 0.071 | 0.073 | ||
500 | 0.128 | 0.157 | 0.089 | 0.105 | 0.095 | 0.141 | 0.157 | 0.148 | 0.141 | 0.157 | 0.164 | 0.187 | 0.200 | 0.210 | 500 |
0.039 | 0.048 | 0.027 | 0.032 | 0.029 | 0.043 | 0.048 | 0.045 | 0.043 | 0.048 | 0.050 | 0.057 | 0.061 | 0.064 | ||
600 | 0.128 | 0.157 | 0.075 | 0.092 | 0.082 | 0.118 | 0.135 | 0.125 | 0.131 | 0.144 | 0.154 | 0.167 | 0.180 | 0.190 | 600 |
0.039 | 0.048 | 0.023 | 0.028 | 0.025 | 0.036 | 0.041 | 0.038 | 0.040 | 0.044 | 0.047 | 0.051 | 0.055 | 0.058 | ||
750 | 0.125 | 0.157 | 0.062 | 0.079 | 0.069 | 0.095 | 0.112 | 0.102 | 0.118 | 0.131 | 0.141 | 0.148 | 0.161 | 0.171 | 750 |
0.038 | 0.048 | 0.019 | 0.024 | 0.021 | 0.029 | 0.034 | 0.031 | 0.036 | 0.040 | 0.043 | 0.045 | 0.049 | 0.052 | ||
1000 | 0.121 | 0.151 | 0.049 | 0.062 | 0.059 | 0.075 | 0.089 | 0.082 | 0.105 | 0.118 | 0.131 | 0.128 | 0.138 | 0.151 | 1000 |
0.037 | 0.046 | 0.015 | 0.019 | 0.018 | 0.023 | 0.027 | 0.025 | 0.032 | 0.036 | 0.040 | 0.039 | 0.042 | 0.046 | ||
Notes: 1. These values are based on the following constants: UL-Type RHH wires with Class B stranding, in cradled configuration. Wire conductivities are 100 percent IACS copper and 61 percent IACS aluminum, and aluminum conduit is 45 percent IACS. Capacitive reactance is ignored, since it is negligible at these voltages. These resistance values are valid only at 75°C (167°F) and for the parameters as given, but are representative for 600-volt wire types operating at 60 Hz. |
|||||||||||||||
2. Effective Z is defined as R cos(θ) + X sin(θ), where θ is the power factor angle of the circuit. Multiplying current by effective impedance gives a good approximation for line-to-neutral voltage drop. Effective impedance values shown in this table are valid only at 0.85 power factor. For another circuit power factor (PF), effective impedance (Ze) can be calculated from R and XL values given in this table as follows: Ze = R × PF + XLsin[arccos(PF)]. |
Table 10 Conductor Stranding
Conductor Size | Number of Strands | |||
---|---|---|---|---|
Copper | Aluminum | |||
AWG or kcmil | mm2 | Class Ba | Class C | Class Ba |
24—30 | 0.20—0.05 | b | — | — |
22 | 0.32 | 7 | — | — |
20 | 0.52 | 10 | — | — |
18 | 0.82 | 16 | — | — |
16 | 1.3 | 26 | — | — |
14—2 | 2.1—33.6 | 7 | 19 | 7c |
1—4/0 | 42.4—107 | 19 | 37 | 19 |
250—500 | 127—253 | 37 | 61 | 37 |
600—1000 | 304—508 | 61 | 91 | 61 |
1250—1500 | 635—759 | 91 | 127 | 91 |
1750—2000 | 886—1016 | 127 | 271 | 127 |
aConductors with a lesser number of strands shall be permitted based on an evaluation for connectability and bending. | ||||
bNumber of strands vary. | ||||
cAluminum 14 AWG (2.1 mm2) is not available. | ||||
With the permission of Underwriters Laboratories, Inc., material is reproduced from UL Standard 486A-B, Wire Connectors, which is copyrighted by Underwriters Laboratories, Inc., Northbrook, Illinois. While use of this material has been authorized, UL shall not be responsible for the manner in which the information is presented, nor for any interpretations thereof. For more information on UL or to purchase standards, please visit our Standards website at www.comm-2000.com or call 1-888-853-3503. |
Table 11(A) and Table 11(B)
For listing purposes, Table 11(A) and Table 11(B) provide the required power source limitations for Class 2 and Class 3 power sources. Table 11 (A) applies for alternating-current sources, and Table 11(B) applies for direct-current sources.
The power for Class 2 and Class 3 circuits shall be either (1) inherently limited, requiring no overcurrent protection, or (2) not inherently limited, requiring a combination of power source and overcurrent protection. Power sources designed for interconnection shall be listed for the purpose.
As part of the listing, the Class 2 or Class 3 power source shall be durably marked where plainly visible to indicate the class of supply and its electrical rating. A Class 2 power source not suitable for wet location use shall be so marked.
Exception: Limited power circuits used by listed information technology equipment.
Overcurrent devices, where required, shall be located at the point where the conductor to be protected receives its supply and shall not be interchangeable with devices of higher ratings. The overcurrent device shall be permitted as an integral part of the power source.
Table 11(A) Class 2 and Class 3 Alternating-Current Power Source Limitations
Power Source | Inherently Limited Power Source (Overcurrent Protection Not Required) | Not Inherently Limited Power Source (Overcurrent Protection Required) | |||||||
---|---|---|---|---|---|---|---|---|---|
Class 2 | Class 3 | Class 2 | Class 3 | ||||||
Source voltage Vmax (volts) (see Note 1) |
0 through 20* | Over 20 and through 30* | Over 30 and through 150 | Over 30 and through 100 | 0 through 20* | Over 20 and through 30* | Over 30 and through 100 | Over 100 and through 150 | |
Power limitations VAmax (volt-amperes) (see Note 1) |
— | — | — | — | 250 (see Note 3) | 250 | 250 | N.A. | |
Current limitations Imax (amperes) (see Note 1) |
8.0 | 8.0 | 0.005 | 150/Vmax | 1000/Vmax | 1000/Vmax | 1000/Vmax | 1.0 | |
Maximum overcurrent protection (amperes) | — | — | — | — | 5.0 | 100/Vmax | 100/Vmax | 1.0 | |
Power source maximum nameplate rating | VA (volt-amperes) | 5.0 × Vmax | 100 | 0.005 × Vmax | 100 | 5.0 × Vmax | 100 | 100 | 100 |
Current (amperes) | 5.0 | 100/Vmax | 0.005 | 100/Vmax | 5.0 | 100/Vmax | 100/Vmax | 100/Vmax | |
Note: Notes for this table can be found following Table 11(B). | |||||||||
*Voltage ranges shown are for sinusoidal ac in indoor locations or where wet contact is not likely to occur. For nonsinusoidal or wet contact conditions, see Note 2. |
Table 11(B) Class 2 and Class 3 Direct-Current Power Source Limitations
Power Source | Inherently Limited Power Source (Overcurrent Protection Not Required) |
Not Inherently Limited Power Source (Overcurrent Protection Required) |
||||||||
---|---|---|---|---|---|---|---|---|---|---|
Class 2 | Class 3 | Class 2 | Class 3 | |||||||
Source voltage Vmax (volts) (see Note 1) |
0 through 20* | Over 20 and through 30* | Over 30 and through 60* | Over 60 and through 150 | Over 60 and through 100 | 0 through 20* | Over 20 and through 60* | Over 60 and through 100 | Over 100 and through 150 | |
Power limitations VA max (volt-amperes)(see Note 1) | — | — | — | — | — | 250 (see Note 3) | 250 | 250 | N.A. | |
Current limitations Imax (amperes) (see Note 1) |
8.0 | 8.0 | 150/Vmax | 0.005 | 150/Vmax | 1000/Vmax | 1000/Vmax | 1000/Vmax | 1.0 | |
Maximum overcurrent protection (amperes) | — | — | — | — | — | 5.0 | 100/Vmax | 100/Vmax | 1.0 | |
Power source maximum nameplate rating | VA (volt-amperes) | 5.0 × Vmax | 100 | 100 | 0.005 × Vmax | 100 | 5.0 × Vmax | 100 | 100 | 100 |
Current (amperes) | 5.0 | 100/Vmax | 100/Vmax | 0.005 | 100/Vmax | 5.0 | 100/Vmax | 100/Vmax | 100/Vmax | |
*Voltage ranges shown are for continuous dc in indoor locations or where wet contact is not likely to occur. | ||||||||||
For interrupted dc or wet contact conditions, see Note 4. | ||||||||||
Notes for Table 11(A) and Table 11(B) | ||||||||||
1. Vmax, Imax, and VAmax are determined with the current-limiting impedance in the circuit (not bypassed) as follows: | ||||||||||
Vmax: Maximum output voltage regardless of load with rated input applied. | ||||||||||
Imax: Maximum output current under any noncapacitive load, including short circuit, and with overcurrent protection bypassed if used. Where a transformer limits the output current, Imax limits apply after 1 minute of operation. Where a current-limiting impedance, listed for the purpose, or as part of a listed product, is used in combination with a non—power-limited transformer or a stored energy source, e.g., storage battery, to limit the output current, Imax limits apply after 5 seconds. | ||||||||||
VAmax: Maximum volt-ampere output after 1 minute of operation regardless of load and overcurrent protection bypassed if used. | ||||||||||
2. For nonsinusoidal ac, Vmax shall not be greater than 42.4 volts peak. Where wet contact (immersion not included) is likely to occur, Class 3 wiring methods shall be used or Vmax shall not be greater than 15 volts for sinusoidal ac and 21.2 volts peak for nonsinusoidal ac. | ||||||||||
3. If the power source is a transformer, VAmax is 350 or less when Vmax is 15 or less. | ||||||||||
4. For dc interrupted at a rate of 10 to 200 Hz, Vmax shall not be greater than 24.8 volts peak. Where wet contact (immersion not included) is likely to occur, Class 3 wiring methods shall be used, or Vmax shall not be greater than 30 volts for continuous dc; 12.4 volts peak for dc that is interrupted at a rate of 10 to 200 Hz. |
Table 12(A) and Table 12(B)
For listing purposes, Table 12(A) and Table 12(B) provide the required power source limitations for power-limited fire alarm sources. Table 12(A) applies for alternating-current sources, and Table 12(B) applies for direct-current sources. The power for power-limited fire alarm circuits shall be either (1) inherently limited, requiring no overcurrent protection, or (2) not inherently limited, requiring the power to be limited by a combination of power source and overcurrent protection.
As part of the listing, the PLFA power source shall be durably marked where plainly visible to indicate that it is a power-limited fire alarm power source. The overcurrent device, where required, shall be located at the point where the conductor to be protected receives its supply and shall not be interchangeable with devices of higher ratings. The overcurrent device shall be permitted as an integral part of the power source.
Table 12(A) PLFA Alternating-Current Power Source Limitations
Power Source | Inherently Limited Power Source (Overcurrent Protection Not Required) |
Not Inherently Limited Power Source (Overcurrent Protection Required) |
||||||||
---|---|---|---|---|---|---|---|---|---|---|
Circuit voltage Vmax (volts) (see Note 1) |
0 through 20 | Over 20 and through 30 | Over 30 and through 100 | 0 through 20 | Over 20 and through 100 | Over 100 and through 150 | ||||
Power limitations VAmax(volt-amperes) (see Note 1) |
— | — | — | 250 (see Note 2) | 250 | N.A. | ||||
Current limitations Imax (amperes) (see Note 1) |
8.0 | 8.0 | 150/Vmax | 1000/Vmax | 1000/Vmax | 1.0 | ||||
Maximum overcurrent protection (amperes) |
— | — | — | 5.0 | 100/Vmax | 1.0 | ||||
Power source maximum nameplate ratings | VA (volt-amperes) | 5.0 × Vmax | 100 | 100 | 5.0 × Vmax | 100 | 100 | |||
Current (amperes) | 5.0 | 100/Vmax | 100/Vmax | 5.0 | 100/Vmax | 100/Vmax | ||||
Note: Notes for this table can be found following Table 12(B). |
Table 12(B) PLFA Direct-Current Power Source Limitations
Power Source | Inherently Limited Power Source (Overcurrent Protection Not Required) |
Not Inherently Limited Power Source (Overcurrent Protection Required) |
|||||
---|---|---|---|---|---|---|---|
Circuit voltage Vmax (volts) (see Note 1) |
0 through 20 | Over 20 and through 30 | Over 30 and through 100 | 0 through 20 | Over 20 and through 100 | Over 100 and through 150 | |
Power limitations VAmax (volt-amperes) (see Note 1) |
— | — | — | 250 (see Note 2) | 250 | N.A. | |
Current limitations I max (amperes) (see Note 1) |
8.0 | 8.0 | 150/Vmax | 1000/Vmax | 1000/Vmax | 1.0 | |
Maximum overcurrent protection (amperes) |
— | — | — | 5.0 | 100/Vmax | 1.0 | |
Power source maximum nameplate ratings | VA (volt- amperes) | 5.0 × Vmax | 100 | 100 | 5.0 × Vmax | 100 | 100 |
Current (amperes) | 5.0 | 100/Vmax | 100/Vmax | 5.0 | 100/Vmax | 100/Vmax | |
Notes for Table 12(A) and Table 12(B) | |||||||
1. V max, I max, and VA max are determined as follows: V max: Maximum output voltage regardless of load with rated input applied. |
|||||||
I max: Maximum output current under any noncapacitive load, including short circuit, and with overcurrent protection bypassed if used. Where a transformer limits the output current, Imax limits apply after 1 minute of operation. Where a current-limiting impedance, listed for the purpose, is used in combination with a nonpower-limited transformer or a stored energy source, e.g., storage battery, to limit the output current, Imax limits apply after 5 seconds. | |||||||
VA max: Maximum volt-ampere output after 1 minute of operation regardless of load and overcurrent protection bypassed if used. Current limiting impedance shall not be bypassed when determining Imax and VAmax. | |||||||
2. If the power source is a transformer, VAmax is 350 or less when Vmax is 15 or less. |