CODES

ADOPTS WITHOUT AMENDMENTS:

International Fire Code 2009 (IFC 2009)

Chapter 1 Scope and Administration

Chapter 2 Definitions

Chapter 3 General Requirements

Chapter 4 Emergency Planning and Preparedness

Chapter 5 Fire Service Features

Chapter 6 Building Services and Systems

Chapter 7 Fire-Resistance-Rated Construction

Chapter 8 Interior Finish, Decorative Materials and Furnishings

Chapter 9 Fire Protection Systems

Chapter 10 Means of Egress

Chapter 11 Aviation Facilities

Chapter 12 Dry Cleaning

Chapter 13 Combustible Dust-Producing Operations

Chapter 14 Fire Safety During Construction and Demolition

Chapter 15 Flammable Finishes

Chapter 16 Fruit and Crop Ripening

Chapter 17 Fumigation and Thermal Insecticidal Fogging

Chapter 18 Semiconductor Fabrication Facilities

Chapter 19 Lumber Yards and Woodworking Facilities

Chapter 20 Manufacture of Organic Coatings

Chapter 21 Industrial Ovens

Chapter 22 Motor Fuel-Dispensing Facilities and Repair Garages

Chapter 23 High-Piled Combustible Storage

Chapter 24 Tents and Other Membrane Structures

Chapter 25 Tire Rebuilding and Tire Storage

Chapter 26 Welding and Other Hot Work

Chapter 27 Hazardous Materials - General Provisions

Chapter 28 Aerosols

Chapter 29 Combustible Fibers

Chapter 30 Compressed Gases

Chapter 31 Corrosive Materials

Chapter 32 Cryogenic Fluids

Chapter 33 Explosives and Fireworks

Chapter 34 Flammable and Combustible Liquids

Chapter 35 Flammable Gases and Flammable Cryogenic Fluids

Chapter 36 Flammable Solids

Chapter 37 Highly Toxic and Toxic Materials

Chapter 38 Liquefied Petroleum Gases

Chapter 39 Organic Peroxides

Chapter 40 Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids

Chapter 41 Pyrophoric Materials

Chapter 42 Pyroxylin (Cellulose Nitrate) Plastics

Chapter 43 Unstable (Reactive) Materials

Chapter 44 Water-Reactive Solids and Liquids

Chapter 45 Marinas

Chapter 46 Construction Requirements for Existing Buildings

Chapter 47 Referenced Standards

Appendix A Board of Appeals

Appendix B Fire-Flow Requirements for Buildings

Appendix C Fire Hydrant Locations and Distribution

Appendix D Fire Apparatus Access Roads

Appendix E Hazard Categories

Appendix F Hazard Ranking

Appendix G Cryogenic Fluids— Weight and Volume Equivalents

Appendix H Hazardous Materials Management Plan (HMMP) and Hazardous Materials Inventory Statement (HMIS) Instructions

Appendix I Fire Protection Systems—noncompliant Conditions

Appendix J Emergency Responder Radio Coverage

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.

The procedure for determining fire-flow requirements for buildings or portions of buildings hereafter constructed shall be in accordance with this appendix. This appendix does not apply to structures other than buildings.

For the purpose of this appendix, certain terms are defined as follows:

FIRE-FLOW. The flow rate of a water supply, measured at 20 pounds per square inch (psi) (138 kPa) residual pressure, that is available for fire fighting.

FIRE-FLOW CALCULATION AREA. The floor area, in square feet (m2), used to determine the required fire flow.

The fire chief is authorized to reduce the fire-flow requirements for isolated buildings or a group of buildings in rural areas or small communities where the development of full fire-flow requirements is impractical.
The fire chief is authorized to increase the fire-flow requirements where conditions indicate an unusual susceptibility to group fires or conflagrations. An increase shall not be more than twice that required for the building under consideration.
For information regarding water supplies for fire-fighting purposes in rural and suburban areas in which adequate and reliable water supply systems do not exist, the fire code official is authorized to utilize NFPA 1142 or the International Wildland-Urban Interface Code.
The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections of the roof of a building, except as modified in Section B104.3.
Portions of buildings which are separated by fire walls without openings, constructed in accordance with the International Building Code, are allowed to be considered as separate fire-flow calculation areas.

The fire-flow calculation area of buildings constructed of Type IA and Type IB construction shall be the area of the three largest successive floors.

Exception: Fire-flow calculation area for open parking garages shall be determined by the area of the largest floor.

The minimum fire-flow and flow duration requirements for one- and two-family dwellings having a fire-flow calculation area that does not exceed 3,600 square feet (344.5 m2) shall be 1,000 gallons per minute (3785.4 L/min) for 1 hour. Fire-flow and flow duration for dwellings having a fire-flow calculation area in excess of 3,600 square feet (344.5m2) shall not be less than that specified in Table B105.1.

Exception: A reduction in required fire-flow of 50 percent, as approved, is allowed when the building is equipped with an approved automatic sprinkler system.

The minimum fire-flow and flow duration for buildings other than one- and two-family dwellings shall be as specified in Table B105.1.

Exception: A reduction in required fire-flow of up to 75 percent, as approved, is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. The resulting fire-flow shall not be less than 1,500 gallons per minute (5678 L/min) for the prescribed duration as specified in Table B105.1.

ICC

IBC-09

International Building Code

B104.2,
TABLE B105.1

ICC

IWUIC-09

International Wildland-
Urban Interface Code

B103.3

NFPA

1142-07

Standard on Water Supplies for Suburban and Rural Fire Fighting

B103.3


TABLE B105.1 MINIMUM REQUIRED FIRE-FLOW AND FLOW DURATION FOR BUILDINGS

FIRE-FLOW CALCULATION AREA (square feet)
Type IA and IBa Type IIA and IIIAa Type IV and V-Aa Type IIB and IIIBa Type V-Ba FIRE-FLOW (gallons per minute)b FLOW DURATION (hours)
0-22,700 0-12,700 0-8,200 0-5,900 0-3,600 1,500 2
22,701-30,200 12,701-17,000 8,201-10,900 5,901-7,900 3,601-4,800 1,750
30,201-38,700 17,001-21,800 10,901-12,900 7,901-9,800 4,801-6,200 2,000
38,701-48,300 21,801-24,200 12,901-17,400 9,801-12,600 6,201-7,700 2,250
48,301-59,000 24,201-33,200 17,401-21,300 12,601-15,400 7,701-9,400 2,500
59,001-70,900 33,201-39,700 21,301-25,500 15,401-18,400 9,401-11,300 2,750
70,901-83,700 39,701-47,100 25,501-30,100 18,401-21,800 11,301-13,400 3,000 3
83,701-97,700 47,101-54,900 30,101-35,200 21,801-25,900 13,401-15,600 3,250
97,701-112,700 54,901-63,400 35,201-40,600 25,901-29,300 15,601-18,000 3,500
112,701-128,700 63,401-72,400 40,601-46,400 29,301-33,500 18,001-20,600 3,750
128,701-145,900 72,401-82,100 46,401-52,500 33,501-37,900 20,601-23,300 4,000 4
145,901-164,200 82,101-92,400 52,501-59,100 37,901-42,700 23,301-26,300 4,250
164,201-183,400 92,401-103,100 59,101-66,000 42,701-47,700 26,301-29,300 4,500
183,401-203,700 103,101-114,600 66,001-73,300 47,701-53,000 29,301-32,600 4,750
203,701-225,200 114,601-126,700 73,301-81,100 53,001-58,600 32,601-36,000 5,000
225,201-247,700 126,701-139,400 81,101-89,200 58,601-65,400 36,001-39,600 5,250
247,701-271,200 139,401-152,600 89,201-97,700 65,401-70,600 39,601-43,400 5,500
271,201-295,900 152,601-166,500 97,701-106,500 70,601-77,000 43,401-47,400 5,750
295,901-Greater 166,501-Greater 106,501-115,800 77,001-83,700 47,401-51,500 6,000
115,801-125,500 83,701-90,600 51,501-55,700 6,250
125,501-135,500 90,601-97,900 55,701-60,200 6,500
135,501-145,800 97,901-106,800 60,201-64,800 6,750
145,801-156,700 106,801-113,200 64,801-69,600 7,000
156,701-167,900 113,201-121,300 69,601-74,600 7,250
167,901-179,400 121,301-129,600 74,601-79,800 7,500
179,401-191,400 129,601-138,300 79,801-85,100 7,750
191,401-Greater 138,301-Greater 85,101-Greater 8,000
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895kPa.
a. Types of construction are based on the International Building Code.
b. Measured at 20 psi residual pressure.
Resources
Help us
keep law free