Heads up: There are no amended sections in this chapter.

(This is a normative appendix and is part of this standard.)

This normative appendix contains the climatic data necessary to determine building envelope and mechanical requirements for various U.S., Canadian, and international locations. (See Section 5.1.4 for additional information regarding the selection of climatic data.) The following definition applies: NA = not available.

TABLE D-1 U.S. and U.S. Territory Climatic Data

State/City Latitude Longitude Elev.,
ft
HDD65 CDD50 Heating
Design Temperature
Cooling Design Temperature Number of Hours
8 a.m.—4 p.m.
Dry-Bulb Wet-Bulb
99.6% 1.0% 1.0% 55 < Tdb <69
Alabama (AL)
Alexander City 32.95 N 85.93 W 640 2910 5102 NA NA NA NA
Anniston FAA AP 33.58 N 85.85 W 611 2854 5217 19 93 76 NA
Auburn Agronomy Farm 32.60 N 85.50 W 652 2612 5428 NA NA NA NA
Birmingham FAA AP 33.57 N 86.75 W 625 2918 5206 18 92 75 760
Dothan 31.32 N 85.45 W 400 1703 6659 28 93 76 NA
Gadsden Steam Plant 34.03 N 86.00 W 565 3317 4805 NA NA NA NA
Huntsville WSO AP 34.65 N 86.77 W 624 3323 4855 15 92 74 NA
Mobile WSO AP 30.68 N 88.25 W 211 1702 6761 26 92 76 774
Montgomery WSO AP 32.30 N 86.40 W 221 2224 5990 24 93 76 734
Selma 32.42 N 87.00 W 147 2249 6080 NA NA NA NA
Talladega 33.43 N 86.08 W 555 2790 5097 NA NA NA NA
Tuscaloosa FAA AP 33.23 N 87.62 W 169 2661 5624 20 94 77 NA
Alaska (AK)
Anchorage WSCMO AP 61.17 N 150.02 W 114 10,570 688 —14 68 57 521
Barrow WSO AP 71.30 N 156.78 W 31 20,226 0 —41 52 49 NA
Fairbanks WSFO AP 64.82 N 147.87 W 436 13,940 1040 —47 77 59 682
Juneau AP 58.37 N 134.58 W 12 8897 559 4 69 58 540
Kodiak WSO AP 57.75 N 152.50 W 111 8817 451 7 65 56 384
Nome WSO AP 64.50 N 165.43 W 13 14,129 274 -31 65 55 210
Arizona (AZ)
Douglas FAA AP 31.47 N 109.60 W 4098 2767 4786 NA NA NA NA
Flagstaff WSO AP 35.13 N 111.67 W 7006 7131 1661 1 83 55 NA
Kingman 35.20 N 114.02 W 3539 3212 5040 22 97 63 NA
Nogales 31.42 N 110.95 W 3560 2928 4554 NA NA NA NA
Phoenix WSFO AP 33.43 N 112.02 W 1110 1350 8425 34 108 70 746
Prescott 34.57 N 112.43 W 5205 4995 2875 15 91 60 725
Tucson WSO AP 32.13 N 110.93 W 2584 1678 6921 31 102 65 716
Winslow WSO AP 35.02 N 110.73 W 4890 4776 3681 10 93 60 634
Yuma WSO AP 32.67 N 114.60 W 206 927 8897 40 109 72 697
Arkansas (AR)
Blytheville AFB 35.97 N 89.95 W 256 3656 5133 12 95 77 NA
Camden 33.60 N 92.82 W 116 2953 5309 NA NA NA NA
Fayetteville 36.00 N 94.17 W 1250 4040 4452 6 93 75 NA
Ft. Smith WSO AP 35.33 N 94.37 W 449 3478 5078 13 96 76 547
Hot Springs 34.52 N 93.05 W 680 3181 5243 NA NA NA NA
Jonesboro 35.88 N 90.70 W 390 3504 5118 NA NA NA NA
Little Rock FAA AP 34.73 N 92.23 W 257 3155 5299 16 95 77 626
Pine Bluff 34.22 N 92.02 W 215 3016 5467 NA NA NA NA
Texarkana FAA AP 33.45 N 94.00 W 361 2295 6152 20 95 77 NA
California (CA)
Bakersfield WSO AP 35.42 N 119.05 W 495 2182 6049 32 101 69 848
Blythe FAA Airport 33.62 N 114.72 W 390 1144 8789 NA NA NA NA
Burbank Hollywood 34.20 N 118.37 W 774 1204 5849 39 95 69 NA
Chico University Farm 39.70 N 121.82 W 185 2953 4454 NA NA NA NA
Crescent City 41.77 N 124.20 W 40 4397 1628 NA NA NA NA
El Centro 32.77 N 115.57 W —30 1156 8132 NA NA NA NA
Eureka WSO City 40.80 N 124.17 W 60 4496 1529 NA NA NA NA
Fairfield/Travis AFB 38.27 N 121.93 W 62 2556 4223 31 94 67 NA
Fresno WSO AP 36.77 N 119.72 W 328 2556 5350 30 101 70 785
Laguna Beach 33.55 N 117.78 W 35 2157 3881 NA NA NA NA
Livermore 37.67 N 121.77 W 480 2909 3810 NA NA NA NA
Lompoc 34.65 N 120.45 W 95 2651 3240 NA NA NA NA
Long Beach WSO AP 33.82 N 118.15 W 34 1430 5281 40 88 67 1502
Los Angeles WSO AP 33.93 N 118.38 W 100 1458 4777 43 81 64 1849
Merced/Castle AFB 37.37 N 120.57 W 187 2687 4694 30 97 69 NA
Monterey 36.60 N 121.90 W 385 3125 2574 NA NA NA NA
Napa State Hospital 38.28 N 122.27 W 60 2844 3463 NA NA NA NA
Needles FAA Airport 34.77 N 114.62 W 914 1309 8645 NA NA NA NA
Oakland/Intl 37.73 N 122.20 W 7 2644 3126 NA NA NA 1905
Oceanside Marina 33.22 N 117.40 W 10 2010 4069 NA NA NA NA
Ontario/Intl 34.05 N 117.62 W 961 1488 5823 35 98 70 NA
Oxnard 34.20 N 119.18 W 49 1992 3980 39 79 64 NA
Palm Springs 33.83 N 116.50 W 425 985 8555 NA NA NA NA
Palmdale 34.58 N 118.10 W 2596 2948 4863 NA NA NA NA
Pasadena 34.15 N 118.15 W 864 1453 5476 NA NA NA NA
Petaluma Fire Stn 3 38.23 N 122.63 W 27 3050 3188 NA NA NA NA
Pomona Cal Poly 34.07 N 117.82 W 740 1713 5145 NA NA NA NA
Redding WSO 40.50 N 122.30 W 502 2855 4964 NA NA NA NA
Redlands 34.05 N 117.18 W 1318 1875 5435 NA NA NA NA
Richmond 37.93 N 122.35 W 55 2574 3285 NA NA NA NA
Riverside/March AFB 33.90 N 117.25 W 1535 1861 5295 34 98 68 NA
Sacramento FAA AP 38.52 N 121.50 W 18 2749 4474 30 97 68 990
Salinas FAA AP 36.67 N 121.60 W 69 2964 2951 33 78 62 NA
San Bernardino/Norton 34.10 N 117.23 W 1155 1821 5450 34 101 70 NA
San Diego WSO AP 32.73 N 117.17 W 13 1256 5223 44 81 67 1911
San Francisco WSO AP 37.62 N 122.38 W 8 3016 2883 37 78 62 1796
San Jose 37.35 N 121.90 W 67 2387 3935 35 89 66 NA
San Luis Obispo Poly 35.30 N 120.67 W 315 2498 3492 NA NA NA NA
Santa Ana Fire Station 33.75 N 117.87 W 135 1238 5430 NA NA NA NA
Santa Barbara FAA AP 34.43 N 119.83 W 9 2438 3449 34 80 64 NA
Santa Cruz 36.98 N 122.02 W 130 2969 2913 NA NA NA NA
Santa Maria WSO AP 34.90 N 120.45 W 254 2984 2918 32 82 62 2016
Santa Monica Pier 34.00 N 118.50 W 14 1819 4145 NA NA NA NA
Santa Paula 34.32 N 119.15 W 237 2039 4114 NA NA NA NA
Santa Rosa 38.45 N 122.70 W 167 2883 3432 NA NA NA NA
Stockton WSO AP 37.90 N 121.25 W 22 2707 4755 30 97 68 NA
Ukiah 39.15 N 123.20 W 623 2954 3868 NA NA NA NA
Visalia 36.33 N 119.30 W 325 2511 5186 NA NA NA NA
Yreka 41.72 N 122.63 W 2625 5386 2611 NA NA NA NA
Colorado (CO)
Alamosa WSO AP 37.45 N 105.87 W 7536 8749 1374 —17 82 55 NA
Boulder 40.03 N 105.28 W 5420 5554 2820 NA NA NA NA
Colorado Sprgs WSO AP 38.82 N 104.72 W 6090 6415 2312 —2 87 58 725
Denver WSFO AP 39.77 N 104.87 W 5286 6020 2732 —3 90 59 739
Durango 37.28 N 107.88 W 6600 6911 1942 NA NA NA NA
Ft. Collins 40.58 N 105.08 W 5004 6368 2411 NA NA NA NA
Grand Junction WSO AP 39.10 N 108.55 W 4849 5548 3632 2 94 60 518
Greeley UNC 40.42 N 104.70 W 4715 6306 2698 NA NA NA NA
La Junta FAA AP 38.05 N 103.52 W 4190 5265 3795 NA NA NA NA
Pueblo WSO AP 38.28 N 104.52 W 4640 5413 3358 —1 94 62 720
Sterling 40.62 N 103.22 W 3938 6541 2809 NA NA NA NA
Trinidad FAA AP 37.25 N 104.33 W 5746 5483 2976 —2 90 60 NA
Connecticut (CT)
Bridgeport WSO AP 41.17 N 73.13 W 10 5537 2997 8 84 72 NA
Hartford-Brainard Fld 41.73 N 72.65 W 15 6155 2768 2 88 72 598
Norwalk Gas Plant 41.12 N 73.42 W 37 5865 2768 NA NA NA NA
Norwich Pub Util Plt 41.53 N 72.07 W 20 5869 2687 NA NA NA NA
Delaware (DE)
Dover 39.15 N 75.52 W 30 4337 3894 14 89 75 NA
Wilmington WSO AP 39.67 N 75.60 W 79 4937 3557 10 89 74 617
Florida (FL)
Belle Glade Exp Stn 26.67 N 80.63 W 16 451 8285 NA NA NA NA
Daytona Beach WSO AP 29.18 N 81.05 W 29 909 7567 34 90 77 641
Ft. Lauderdale 26.07 N 80.15 W 10 171 9735 46 90 78 NA
Ft. Myers FAA AP 26.58 N 81.87 W 15 418 8924 42 93 77 NA
Ft. Pierce 27.47 N 80.35 W 25 490 8448 NA NA NA NA
Gainesville Mun AP 29.68 N 82.27 W 138 1267 7009 30 92 77 NA
Jacksonville WSO AP 30.50 N 81.70 W 26 1434 6847 29 93 77 674
Key West WSO AP 24.55 N 81.75 W 4 100 10,174 55 89 79 NA
Lakeland 28.02 N 81.92 W 145 588 8472 NA NA NA NA
Miami WSCMO AP 25.80 N 80.30 W 12 200 9474 46 90 77 259
Ocala 29.20 N 82.08 W 75 930 7696 NA NA NA NA
Orlando WSO Mc Coy 28.43 N 81.33 W 91 686 8227 37 93 76 571
Panama City/Tyndall 30.07 N 85.58 W 16 1216 7023 33 89 79 NA
Pensacola FAA AP 30.47 N 87.20 W 112 1617 6816 28 92 78 NA
St Augustine WFOY 29.90 N 81.32 W 8 1040 7261 NA NA NA NA
St Petersburg 27.77 N 82.63 W 8 603 8537 43 93 79 NA
Tallahassee WSO AP 30.38 N 84.37 W 55 1705 6639 25 93 76 747
Tampa WSCMO AP 27.97 N 82.53 W 19 725 8239 36 91 77 592
West Palm Beach WSO AP 26.68 N 80.12 W 18 323 9049 43 90 78 308
Georgia (GA)
Albany 31.53 N 84.13 W 180 2205 6020 27 95 76 NA
Americus 32.05 N 84.25 W 490 2430 5634 NA NA NA NA
Athens WSO AP 33.95 N 83.32 W 802 2893 5079 20 92 75 NA
Atlanta WSO AP 33.65 N 84.43 W 1010 2991 5038 18 91 74 749
Augusta WSO AP 33.37 N 81.97 W 148 2565 5519 21 94 76 774
Brunswick 31.17 N 81.50 W 13 1578 6729 30 91 79 NA
Columbus WSO AP 32.52 N 84.95 W 449 2261 6052 23 93 75 NA
Dalton 34.75 N 84.95 W 700 3552 4546 NA NA NA NA
Dublin 32.50 N 82.90 W 215 2476 5664 NA NA NA NA
Gainesville 34.30 N 83.85 W 1170 3500 4310 NA NA NA NA
La Grange 33.05 N 85.02 W 715 2667 5216 NA NA NA NA
Macon WSO AP 32.70 N 83.65 W 354 2334 5826 23 94 75 787
Savannah WSO AP 32.13 N 81.20 W 46 1847 6389 26 93 76 NA
Valdosta/Moody AFB 30.97 N 83.20 W 233 1552 7216 30 94 77 NA
Waycross 31.25 N 82.32 W 145 2025 6172 29 94 76 NA
Hawaii (HI)
Hilo (Hawaii) 19.72 N 155.07 W 36 0 8759 61 84 74 153
Honolulu WSFO AP (Oahu) 21.33 N 157.92 W 7 0 9949 61 88 73 69
Kaneohe Mauka (Oahu) 21.42 N 157.82 W 190 0 8955 67 85 74 NA
Idaho (ID)
Boise WSFO AP 43.57 N 116.22 W 2838 5861 2807 2 94 63 647
Burley FAA AP 42.53 N 113.77 W 4157 6745 2174 —5 90 62 NA
Coeur D'Alene RS 47.68 N 116.75 W 2158 6239 2216 NA NA NA NA
Idaho Falls FAA AP 43.52 N 112.07 W 4730 8063 1853 —12 89 60 NA
Lewiston WSO AP 46.38 N 117.02 W 1436 5270 2964 6 93 64 748
Moscow-Univ of Idaho 46.73 N 116.97 W 2660 6782 1789 NA NA NA NA
Mountain Home 43.13 N 115.70 W 3190 6176 2725 0 96 62 NA
Pocatello WSO AP 42.92 N 112.60 W 4454 7180 2142 —7 90 60 546
Twin Falls WSO 42.55 N 114.35 W 3960 6769 1995 NA NA NA NA
Illinois (IL)
Aurora 41.75 N 88.35 W 644 6699 2880 NA NA NA NA
Belleville/Scott AFB 38.55 N 89.85 W 453 4878 4146 3 93 77 NA
Carbondale Sewage Plt 37.73 N 89.17 W 390 4865 3934 NA NA NA NA
Champaign 40.03 N 88.28 W 755 5689 3697 NA NA NA NA
Chicago Midway AP 41.73 N 87.77 W 620 6176 3251 NA NA NA NA
Chicago O'Hare WSO AP 41.98 N 87.90 W 674 6536 2941 —6 88 73 613
Chicago University 41.78 N 87.60 W 594 5753 3391 NA NA NA NA
Danville 40.13 N 87.65 W 558 5610 3471 —4 90 77 NA
Decatur 39.83 N 89.02 W 620 5522 3652 —2 91 75 NA
Dixon 41.83 N 89.52 W 700 6873 2965 NA NA NA NA
Freeport Waste Wtr Plt 42.30 N 89.60 W 750 7169 2739 NA NA NA NA
Galesburg 40.95 N 90.38 W 771 6314 3249 NA NA NA NA
Joliet Brandon Rd Dam 41.50 N 88.10 W 543 6463 3025 NA NA NA NA
Moline WSO AP 41.45 N 90.50 W 582 6474 3207 —8 90 74 640
Mt. Vernon 38.35 N 88.87 W 490 5189 3818 NA NA NA NA
Peoria WSO AP 40.67 N 89.68 W 650 6148 3339 —6 89 74 NA
Quincy FAA AP 39.93 N 91.20 W 763 5763 3574 —4 91 75 NA
Rantoul 40.32 N 88.17 W 740 6183 3288 NA NA NA NA
Rockford WSO AP 42.20 N 89.10 W 724 6969 2852 —10 88 73 NA
Springfield WSO AP 39.85 N 89.68 W 594 5688 3635 —4 91 75 600
Waukegan 42.35 N 87.88 W 700 7136 2515 NA NA NA NA
Indiana (IN)
Anderson Sewage Plant 40.10 N 85.72 W 847 5916 3091 NA NA NA NA
Bloomington Indiana U 39.17 N 86.52 W 825 5309 3585 NA NA NA NA
Columbus 39.20 N 85.92 W 621 5536 3353 NA NA NA NA
Evansville WSO AP 38.05 N 87.53 W 380 4708 4074 3 92 76 611
Ft. Wayne WSO AP 41.00 N 85.20 W 797 6273 3077 —4 88 73 601
Goshen College 41.57 N 85.83 W 805 6282 2941 NA NA NA NA
Hobart 41.53 N 87.25 W 600 6043 3168 NA NA NA NA
Indianapolis WSFO 39.73 N 86.27 W 792 5615 3453 —3 88 74 NA
Kokomo 40.42 N 86.05 W 855 6429 2978 NA NA NA NA
Lafayette 40.35 N 86.87 W 600 6228 3069 —5 90 75 NA
Marion 40.57 N 85.67 W 790 6260 2996 NA NA NA NA
Muncie Ball State Univ 40.22 N 85.42 W 940 6027 3196 NA NA NA NA
Peru/Grissom AFB 40.65 N 86.15 W 814 5908 3439 —3 89 75 NA
Richmond Wtr Wks 39.88 N 84.88 W 1015 5963 3004 NA NA NA NA
Shelbyville Sewage Plt 39.52 N 85.78 W 750 5784 3291 NA NA NA NA
South Bend WSO AP 41.70 N 86.32 W 773 6331 2920 —2 87 72 635
Terre Haute 39.35 N 87.42 W 555 5581 3490 —3 90 76 NA
Valparaiso Waterworks 41.52 N 87.03 W 800 6267 2942 NA NA NA NA
Iowa (IA)
Ames 42.03 N 93.80 W 1099 6776 3079 NA NA NA NA
Burlington 40.78 N 91.12 W 597 5943 3601 —4 91 76 649
Cedar Rapids FAA AP 41.88 N 91.70 W 863 6924 3003 —11 89 74 NA
Clinton 41.80 N 90.27 W 585 6324 3291 NA NA NA NA
Des Moines WSFO AP 41.53 N 93.65 W 938 6497 3371 —9 90 74 667
Dubuque WSO AP 42.40 N 90.70 W 1065 7327 2672 NA NA NA NA
Ft. Dodge 42.50 N 94.20 W 1115 7261 2902 —13 88 73 NA
Iowa City 41.65 N 91.53 W 640 6227 3434 NA NA NA NA
Keokuk Lock and Dam 40.40 N 91.37 W 527 5969 3467 NA NA NA NA
Marshalltown 42.07 N 92.93 W 870 7170 2813 NA NA NA NA
Mason City FAA AP 43.17 N 93.33 W 1194 7837 2653 —15 88 73 610
Newton 41.70 N 93.05 W 938 6783 3131 NA NA NA NA
Ottumwa Airport 41.10 N 92.45 W 842 6269 3414 —5 92 75 NA
Sioux City WSO AP 42.40 N 96.38 W 1103 6893 3149 —11 90 74 602
Waterloo WSO AP 42.55 N 92.40 W 868 7406 2813 —14 88 73 NA
Kansas (KS)
Atchison 39.57 N 95.12 W 945 5184 3940 NA NA NA NA
Chanute FAA Airport 37.67 N 95.48 W 978 4650 4226 NA NA NA NA
Dodge City WSO AP 37.77 N 99.97 W 2582 5001 4090 0 97 70 637
El Dorado 37.82 N 96.83 W 1340 4587 4317 NA NA NA NA
Garden City FAA AP 37.93 N 100.72 W 2882 5216 3936 —3 97 69 NA
Goodland WSO AP 39.37 N 101.70 W 3650 5974 3018 —3 94 66 625
Great Bend 38.35 N 98.77 W 1850 4679 4425 NA NA NA NA
Hutchinson 37.93 N 98.03 W 1570 5103 4106 NA NA NA NA
Liberal 37.05 N 100.92 W 2834 4706 4185 NA NA NA NA
Manhattan 39.20 N 96.58 W 1065 5043 4155 NA NA NA NA
Parsons 37.37 N 95.28 W 910 4606 4339 NA NA NA NA
Russell FAA AP 38.87 N 98.82 W 1864 5338 3939 —4 96 72 NA
Salina FAA AP 38.80 N 97.63 W 1257 5101 4167 —3 97 73 NA
Topeka WSFO AP 39.07 N 95.63 W 877 5265 3880 —2 93 75 608
Wichita WSO AP 37.65 N 97.43 W 1321 4791 4351 2 97 73 NA
Kentucky (KY)
Ashland 38.45 N 82.62 W 555 5225 3280 NA NA NA NA
Bowling Green FAA AP 36.97 N 86.42 W 547 4328 4132 7 91 75 NA
Covington WSO AP 39.07 N 84.67 W 869 5248 3488 1 89 73 661
Hopkinsville/Campbell 36.67 N 87.50 W 571 3928 4654 NA NA NA NA
Lexington WSO AP 38.03 N 84.60 W 966 4783 3754 4 89 73 618
Louisville WSFO AP 38.18 N 85.73 W 477 4514 4000 6 90 75 636
Madisonville 37.35 N 87.52 W 440 4167 4290 NA NA NA NA
Owensboro 37.77 N 87.15 W 405 4334 4222 NA NA NA NA
Paducah WSO 37.07 N 88.77 W 410 4279 4317 7 93 76 NA
Louisiana (LA)        
Alexandria 31.32 N 92.47 W 87 2003 6407 27 94 78 NA
Baton Rouge WSO AP 30.53 N 91.13 W 64 1669 6845 27 92 77 677
Bogalusa 30.78 N 89.87 W 100 1911 6457 NA NA NA NA
Houma 29.58 N 90.73 W 15 1429 6974 NA NA NA NA
Lafayette FAA AP 30.20 N 91.98 W 38 1587 6877 28 93 78 NA
Lake Charles WSO AP 30.12 N 93.22 W 9 1616 6813 29 91 78 668
Minden 32.58 N 93.28 W 185 2533 5823 NA NA NA NA
Monroe FAA AP 32.52 N 92.05 W 78 2407 6039 22 94 78 NA
Natchitoches 31.77 N 93.08 W 130 2152 6273 NA NA NA NA
New Orleans WSCMO AP 29.98 N 90.25 W 4 1513 6910 30 92 78 789
Shreveport WSO AP 32.47 N 93.82 W 254 2,264 6166 22 95 77 697
Maine (ME)
Augusta FAA AP 44.32 N 69.80 W 350 7550 2093 —3 84 69 NA
Bangor FAA AP 44.80 N 68.82 W 163 7930 1916 —7 84 69 669
Caribou WSO AP 46.87 N 68.02 W 624 9651 1470 —14 82 67 692
Lewiston 44.10 N 70.22 W 180 7244 2261 NA NA NA NA
Millinocket 45.65 N 68.70 W 360 8902 1708 NA NA NA NA
Portland WSMO AP 43.65 N 70.32 W 57 7378 1943 —3 83 70 665
Waterville Pmp Stn 44.55 N 69.65 W 90 7382 2180 NA NA NA NA
Maryland (MD)
Baltimore WSO AP 39.18 N 76.67 W 196 4707 3709 11 91 74 NA
Cumberland 39.63 N 78.75 W 730 5036 3432 NA NA NA NA
Hagerstown 39.65 N 77.73 W 660 5293 3341 NA NA NA NA
Salisbury 38.37 N 75.58 W 10 4027 4002 13 90 76 NA
Massachusetts (MA)
Boston WSO AP 42.37 N 71.03 W 20 5641 2897 7 87 71 713
Clinton 42.40 N 71.68 W 398 6698 2457 NA NA NA NA
Framingham 42.28 N 71.42 W 170 6262 2695 NA NA NA NA
Lawrence 42.70 N 71.17 W 57 6322 2648 NA NA NA NA
Lowell 42.65 N 71.37 W 110 6339 2715 NA NA NA NA
New Bedford 41.63 N 70.93 W 120 5426 2973 NA NA NA NA
Springfield 42.10 N 72.58 W 190 5754 3037 NA NA NA NA
Taunton 41.90 N 71.07 W 20 6346 2461 NA NA NA NA
Worcester WSO AP 42.27 N 71.87 W 986 6979 2203 0 83 69 NA
Michigan (MI)
Adrian 41.92 N 84.02 W 760 6737 2586 NA NA NA NA
Alpena WSO AP 45.07 N 83.57 W 689 8284 1779 —7 84 69 695
Battle Creek/Kellogg 42.30 N 85.23 W 942 6416 3399 NA NA NA NA
Benton Harbor AP 42.13 N 86.43 W 649 6303 2829 NA NA NA NA
Detroit City Airport 42.42 N 83.02 W 625 6167 3046 0 87 72 NA
Escanaba 45.75 N 87.03 W 600 8593 1664 NA NA NA NA
Flint WSO AP 42.97 N 83.75 W 766 6979 2451 —2 86 71 634
Grand Rapids WSO AP 42.88 N 85.52 W 707 6973 2537 0 86 71 622
Holland 42.80 N 86.12 W 610 6747 2536 NA NA NA NA
Jackson FAA AP 42.27 N 84.45 W 1005 6791 2707 —3 86 73 NA
Kalamazoo State Hosp 42.28 N 85.60 W 945 6230 3015 NA NA NA NA
Lansing WSO AP 42.77 N 84.60 W 841 7101 2449 —3 86 72 NA
Marquette 46.55 N 87.38 W 665 8356 1730 —13 82 67 NA
Mt. Pleasant University 43.58 N 84.77 W 796 7436 2319 NA NA NA NA
Muskegon WSO AP 43.17 N 86.23 W 628 6924 2361 3 83 70 NA
Pontiac State Hospital 42.65 N 83.30 W 982 6653 2770 NA NA NA NA
Port Huron 42.98 N 82.42 W 590 6898 2541 NA NA NA NA
Saginaw FAA AP 43.53 N 84.08 W 660 7139 2476 0 87 72 NA
Sault Ste Marie WSO 46.47 N 84.37 W 724 9316 1421 —12 80 68 733
Traverse City FAA AP 44.73 N 85.58 W 623 7749 2127 —3 86 70 679
Ypsilanti East Mich U 42.25 N 83.62 W 779 6466 2878 NA NA NA NA
Minnesota (MN)
Albert Lea 43.62 N 93.42 W 1230 8146 2608 NA NA NA NA
Alexandria FAA AP 45.87 N 95.38 W 1416 8999 2316 —20 86 70 NA
Bemidji Airport 47.50 N 94.93 W 1377 10200 1781 NA NA NA NA
Brainerd 46.37 N 94.20 W 1180 9437 1958 —24 85 68 NA
Duluth WSO AP 46.83 N 92.18 W 1428 9818 1536 —21 81 67 650
Faribault 44.30 N 93.27 W 940 8279 2498 NA NA NA NA
International Falls WSO AP 48.57 N 93.38 W 1179 10,487 1630 —29 83 67 656
Mankato 44.15 N 94.02 W 836 8005 2691 NA NA NA NA
Minneapolis-St Paul WSO AP 44.88 N 93.22 W 834 7981 2680 —16 88 71 566
Rochester WSO AP 43.92 N 92.50 W 1297 8250 2376 —17 85 71 652
St Cloud WSO AP 45.55 N 94.07 W 1037 8928 2149 —20 88 71 NA
Virginia 47.50 N 92.55 W 1435 10,024 1583 NA NA NA NA
Willmar State Hospital 45.13 N 95.02 W 1128 8637 2465 NA NA NA NA
Winona 44.05 N 91.63 W 652 7694 2695 NA NA NA NA
Mississippi (MS)
Biloxi/Keesler AFB 30.42 N 88.92 W 26 1486 6946 31 91 78 NA
Clarksdale 34.20 N 90.57 W 173 3188 5357 NA NA NA NA
Columbus AFB 33.65 N 88.45 W 220 2769 5565 20 94 78 NA
Greenville 33.38 N 91.02 W 132 2778 5661 NA NA NA NA
Greenwood FAA AP 33.50 N 90.08 W 155 2698 5760 20 94 78 NA
Hattiesburg 31.32 N 89.30 W 161 2180 6085 NA NA NA NA
Jackson WSFO AP 32.32 N 90.08 W 330 2467 5900 21 93 76 640
Laurel 31.68 N 89.12 W 225 2327 5893 NA NA NA NA
McComb FAA AP 31.23 N 90.47 W 413 2115 6025 23 92 76 NA
Meridian WSO AP 32.33 N 88.75 W 294 2444 5804 21 94 76 719
Natchez 31.55 N 91.38 W 195 1903 6378 NA NA NA NA
Tupelo WSO AP 34.27 N 88.73 W 361 3079 5224 18 94 76 NA
Vicksburg Military Pk 32.35 N 90.85 W 255 2196 6059 NA NA NA NA
Missouri (MO)
Cape Girardeau FAA AP 37.23 N 89.57 W 337 4386 4359 6 94 77 NA
Columbia WSO AP 38.82 N 92.22 W 887 5212 3752 —1 92 75 633
Farmington 37.70 N 90.38 W 935 5041 3653 NA NA NA NA
Hannibal 39.72 N 91.37 W 712 5628 3685 NA NA NA NA
Jefferson City Wtr Plt 38.58 N 92.15 W 670 5302 3705 NA NA NA NA
Joplin FAA AP 37.17 N 94.50 W 980 4303 4417 3 94 75 NA
Kansas City WSO AP 39.32 N 94.72 W 973 5393 3852 —1 93 75 NA
Kirksville Radio KIRX 40.22 N 92.58 W 970 5867 3494 NA NA NA NA
Mexico 39.18 N 91.88 W 775 5590 3664 NA NA NA NA
Moberly Radio KWIX 39.40 N 92.43 W 840 5204 3948 NA NA NA NA
Poplar Bluff R S 36.77 N 90.42 W 380 4328 4368 8 92 76 NA
Rolla 38.13 N 91.77 W 1148 4748 4186 NA NA NA NA
Rolla Univ of MO 37.95 N 91.77 W 1180 4959 3986 NA NA NA NA
St Joseph 39.77 N 94.92 W 811 5590 3783 NA NA NA NA
St Louis WSCMO AP 38.75 N 90.37 W 535 4758 4283 2 93 75 NA
Montana (MT)
Billings WSO AP 45.80 N 108.53 W 3567 7164 2466 —13 90 62 617
Bozeman 45.82 N 110.88 W 5950 9908 672 —20 87 60 NA
Butte FAA AP 45.95 N 112.50 W 5540 9517 1152 —22 84 56 NA
Cut Bank FAA AP 48.60 N 112.37 W 3838 8904 1475 —21 84 59 672
Glasgow WSO AP 48.22 N 106.62 W 2284 8745 2244 —22 90 63 570
Glendive 47.10 N 104.72 W 2076 8178 2619 NA NA NA NA
Great Falls WSCMO AP 47.48 N 111.37 W 3663 7741 1993 —19 88 60 641
Havre WSO AP 48.55 N 109.77 W 2584 8447 2132 —25 90 62 NA
Helena WSO AP 46.60 N 112.00 W 3893 8031 1922 —18 87 59 651
Kalispell WSO AP 48.30 N 114.27 W 2965 8378 1345 —12 86 61 NA
Lewistown FAA AP 47.07 N 109.45 W 4132 8479 1580 —18 86 60 673
Livingston FAA AP 45.70 N 110.45 W 4653 7220 1900 NA NA NA NA
Miles City FAA AP 46.43 N 105.87 W 2628 7796 2680 —19 93 65 565
Missoula WSO AP 46.92 N 114.08 W 3190 7792 1679 —9 88 61 658
Nebraska (NE)
Chadron FAA AP 42.83 N 03.08 W 3312 7020 2692 NA NA NA NA
Columbus 41.47 N 97.33 W 1450 6543 3345 NA NA NA NA
Fremont 41.43 N 96.48 W 1180 6140 3421 NA NA NA NA
Grand Island WSO AP 40.97 N 98.32 W 1841 6421 3243 —8 93 72 611
Hastings 40.58 N 98.35 W 1925 6506 3217 NA NA NA NA
Kearney 40.73 N 99.02 W 2130 6548 3090 NA NA NA NA
Lincoln WSO AP 40.85 N 96.75 W 1190 6278 3455 —7 94 74 NA
Mc Cook 40.22 N 100.58 W 2580 6115 3236 NA NA NA NA
Norfolk WSO AP 41.98 N 97.43 W 1551 6873 3072 —11 92 72 NA
North Platte WSO AP 41.13 N 100.68 W 2775 6859 2737 —10 92 69 592
Omaha (Eppley Field) 41.30 N 95.90 W 980 6300 3398 —7 92 75 NA
Scottsbluff WSO AP 41.87 N 103.60 W 3945 6729 2680 —11 92 64 620
Sidney 41.23 N 103.00 W 4,320 6966 2409 —8 92 63 NA
Nevada (NV)
Carson City 39.15 N 119.77 W 4651 5691 2312 NA NA NA NA
Elko FAA AP 40.83 N 115.78 W 5075 7077 2144 —5 92 59 569
Ely WSO AP 39.28 N 114.85 W 6262 7621 1717 —6 87 56 683
Las Vegas WSO AP 36.08 N 115.17 W 2162 2407 6745 27 106 66 719
Lovelock FAA AP 40.07 N 118.55 W 3900 5869 2886 NA NA NA 606
Reno WSFO AP 39.50 N 119.78 W 4404 5674 2504 8 92 60 752
Tonopah AP 38.07 N 117.08 W 5426 5733 2840 7 92 57 660
Winnemucca WSO AP 40.90 N 117.80 W 4297 6315 2379 1 94 60 608
New Hampshire (NH)
Berlin 44.45 N 71.18 W 930 8645 1718 NA NA NA NA
Concord WSO AP 43.20 N 71.50 W 346 7554 2087 —8 87 70 683
Keene 42.92 N 72.27 W 480 6948 2398 NA NA NA NA
Portsmouth/Pease AFB 43.08 N 70.82 W 102 6572 2418 4 85 70 NA
New Jersey (NJ)
Atlantic City WSO AP 39.45 N 74.57 W 138 5169 3198 8 88 73 NA
Long Branch Oakhurst 40.27 N 74.00 W 30 5253 3057 NA NA NA NA
Newark WSO AP 40.70 N 74.17 W 30 4888 3748 10 90 73 644
New Mexico (NM)
Alamogordo/Holloman 32.85 N 106.10 W 4094 3232 4726 20 96 63 NA
Albuquerque WSFO AP 35.05 N 106.62 W 5326 4425 3908 13 93 60 703
Artesia 32.77 N 104.38 W 3320 3527 4583 NA NA NA NA
Carlsbad FAA AP 32.33 N 104.27 W 3232 2812 5512 19 98 66 NA
Clovis/Cannon AFB 34.38 N 103.32 W 4295 3983 4178 10 93 64 NA
Farmington 36.73 N 108.23 W 5502 5464 3307 8 92 60 NA
Gallup FAA AP 35.52 N 108.78 W 6468 6244 2355 —1 87 56 NA
Grants Airport 35.17 N 107.90 W 6520 5907 2481 NA NA NA NA
Hobbs 32.70 N 103.13 W 3615 2851 5160 NA NA NA NA
Raton Filter Plant 36.92 N 104.43 W 6932 6103 2187 NA NA NA NA
Roswell FAA AP 33.30 N 104.53 W 3669 3267 4962 14 96 65 677
Socorro 34.08 N 106.88 W 4585 4074 3845 NA NA NA NA
Tucumcari 35.20 N 103.68 W 4086 3912 4196 9 95 65 710
New York (NY)
Albany WSFO AP 42.75 N 73.80 W 275 6894 2525 —7 86 70 605
Auburn 42.92 N 76.53 W 770 6782 2531 NA NA NA NA
Batavia 42.98 N 78.18 W 890 6657 2536 NA NA NA NA
Binghamton WSO AP 42.22 N 75.98 W 1600 7273 2193 —2 82 69 662
Buffalo WSCMO AP 42.93 N 78.73 W 705 6747 2468 2 84 69 697
Cortland 42.60 N 76.18 W 1129 7168 2225 NA NA NA NA
Elmira/Chemung Co 42.17 N 76.90 W 951 6845 2420 —2 87 71 NA
Geneva Research Farm 42.88 N 77.03 W 718 6939 2364 NA NA NA NA
Glens Falls FAA AP 43.35 N 73.62 W 321 7635 2182 —10 85 71 NA
Gloversville 43.05 N 74.35 W 812 7664 2118 NA NA NA NA
Ithaca Cornell Univ 42.45 N 76.45 W 960 7207 2117 NA NA NA NA
Lockport 43.18 N 78.65 W 520 6703 2482 NA NA NA NA
Massena FAA AP 44.93 N 74.85 W 214 8255 2046 —15 84 71 627
NY Central Pk WSO City 40.78 N 73.97 W 132 4805 3634 NA NA NA 790
NY Kennedy WSO AP 40.65 N 73.78 W 16 5027 3342 11 88 72 NA
NY La Guardia WSO AP 40.77 N 73.90 W 11 4910 3547 13 89 73 790
Oswego East 43.47 N 76.50 W 350 6733 2431 NA NA NA NA
Plattsburgh AFB 44.65 N 73.47 W 165 7837 2175 —9 83 69 NA
Poughkeepsie FAA AP 41.63 N 73.88 W 155 6391 2663 2 88 72 NA
Rochester WSO AP 43.12 N 77.67 W 547 6734 2406 1 86 71 608
Rome/Griffiss AFB 43.23 N 75.40 W 505 7244 2344 —5 86 70 NA
Schenectady 42.83 N 73.92 W 220 6881 2500 NA NA NA NA
Syracuse WSO AP 43.12 N 76.12 W 421 6834 2399 —3 85 71 730
Utica 43.10 N 75.28 W 500 7066 2354 NA NA NA NA
Watertown 43.97 N 75.87 W 497 7540 2294 —12 83 70 NA
North Carolina (NC)
Asheville WSO AP 35.43 N 82.55 W 2140 4308 3365 11 85 71 915
Charlotte WSO AP 35.22 N 80.93 W 700 3341 4704 18 91 74 777
Durham 36.03 N 78.97 W 406 3867 4159 NA NA NA NA
Elizabeth City FAA AP 36.27 N 76.18 W 10 3139 4765 NA NA NA NA
Fayetteville/Pope AFB 35.17 N 79.02 W 217 2917 5308 22 94 76 NA
Goldsboro 35.33 N 77.97 W 109 3040 5018 22 94 76 NA
Greensboro WSO AP 36.08 N 79.95 W 886 3865 4144 15 90 74 718
Greenville 35.62 N 77.38 W 30 3129 4824 NA NA NA NA
Henderson 36.37 N 78.42 W 480 4038 4002 NA NA NA NA
Hickory FAA AP 35.73 N 81.38 W 1143 3728 4199 18 91 72 NA
Jacksonville/New River 34.70 N 77.43 W 26 2456 5678 23 92 78 NA
Lumberton 34.70 N 79.07 W 130 3212 4723 NA NA NA NA
New Bern FAA AP 35.07 N 77.05 W 18 2742 5262 22 92 78 NA
Raleigh-Durham WSFO AP 35.87 N 78.78 W 376 3457 4499 16 90 75 740
Rocky Mount 35.90 N 77.72 W 110 3321 4586 NA NA NA NA
Wilmington WSO AP 34.27 N 77.90 W 72 2470 5557 23 91 78 NA
North Dakota (ND)
Bismarck WSFO AP 46.77 N 100.77 W 1647 8968 2144 —21 90 67 556
Devils Lake KDLR 48.12 N 98.87 W 1464 9950 1973 —23 87 67 NA
Dickinson FAA AP 46.78 N 102.80 W 2581 8657 2152 NA NA NA NA
Fargo WSO AP 46.90 N 96.80 W 900 9254 2289 —22 88 70 546
Grand Forks FAA AP 47.95 N 97.17 W 847 9733 2084 —20 88 69 NA
Jamestown FAA AP 46.92 N 98.68 W 1492 9168 2262 NA NA NA NA
Minot FAA AP 48.27 N 101.28 W 1715 9193 2135 —20 88 66 581
Ohio (OH)
Akron-Canton WSO AP 40.92 N 81.43 W 1208 6160 2779 0 85 71 680
Ashtabula 41.85 N 80.80 W 690 6429 2604 NA NA NA NA
Bowling Green 41.38 N 83.62 W 675 6482 2876 NA NA NA NA
Cambridge 40.02 N 81.58 W 800 5488 3118 NA NA NA NA
Cincinnati-Abbe WSO 39.15 N 84.52 W 760 4988 3733 5 90 75 NA
Cleveland WSFO AP 41.42 N 81.87 W 770 6201 2755 1 86 72 NA
Columbus WSO AP 40.00 N 82.88 W 812 5708 3119 1 88 73 708
Dayton WSCMO AP 39.90 N 84.20 W 995 5708 3249 —1 88 73 611
Defiance 41.28 N 84.38 W 700 6628 2810 NA NA NA NA
Findlay FAA AP 41.02 N 83.67 W 797 6302 2907 —2 87 72 NA
Fremont 41.33 N 83.12 W 600 6439 2823 NA NA NA NA
Lancaster 39.73 N 82.63 W 860 5988 2935 NA NA NA NA
Lima Sewage Plant 40.72 N 84.13 W 850 6253 3050 NA NA NA NA
Mansfield WSO AP 40.82 N 82.52 W 1295 6258 2818 —1 85 72 NA
Marion 40.62 N 83.13 W 965 6407 2836 NA NA NA NA
Newark Water Works 40.08 N 82.42 W 835 5657 3107 NA NA NA NA
Norwalk 41.27 N 82.62 W 670 6434 2715 NA NA NA NA
Portsmouth 38.75 N 82.88 W 540 4913 3581 NA NA NA NA
Sandusky 41.45 N 82.72 W 584 6131 2986 NA NA NA NA
Springfield New Wtr Wk 39.97 N 83.82 W 930 6254 2790 NA NA NA NA
Steubenville 40.38 N 80.63 W 992 5700 3054 NA NA NA NA
Toledo Express WSO AP 41.58 N 83.80 W 669 6579 2720 —2 87 72 652
Warren 41.20 N 80.82 W 900 6402 2546 NA NA NA NA
Wooster Exp Station 40.78 N 81.92 W 1020 6379 2570 NA NA NA NA
Youngstown WSO AP 41.25 N 80.67 W 1178 6544 2536 —1 85 70 679
Zanesville FAA AP 39.95 N 81.90 W 881 5714 3013 2 88 73 NA
Oklahoma (OK)
Ada 34.78 N 96.68 W 1015 3182 5317 NA NA NA NA
Altus AFB 34.65 N 99.27 W 1378 3151 5708 13 100 73 NA
Ardmore 34.20 N 97.15 W 860 2702 5978 NA NA NA NA
Bartlesville 36.75 N 96.00 W 715 3777 4976 NA NA NA NA
Chickasha Exp Station 35.05 N 97.92 W 1085 3366 5298 NA NA NA NA
Enid 36.42 N 97.87 W 1245 3788 5119 5 98 74 NA
Lawton 34.62 N 98.45 W 1150 3457 5268 12 97 73 NA
McAlester FAA AP 34.88 N 95.78 W 760 3354 5233 10 96 76 NA
Muskogee 35.77 N 95.33 W 583 3413 5185 NA NA NA NA
Norman 35.18 N 97.45 W 1109 3,295 5272 NA NA NA NA
Oklahoma City WSFO AP 35.40 N 97.60 W 1280 3659 4972 9 96 74 733
Ponca City FAA AP 36.73 N 97.10 W 999 4226 4791 NA NA NA NA
Seminole 35.23 N 96.67 W 865 3097 5552 NA NA NA NA
Stillwater 36.12 N 97.10 W 895 4028 4718 NA NA NA NA
Tulsa WSO AP 36.18 N 95.90 W 668 3691 5150 9 97 76 591
Woodward 36.45 N 99.38 W 1900 3900 4884 NA NA NA NA
Oregon (OR)
Astoria WSO AP 46.15 N 123.88 W 8 5158 1437 25 72 62 1236
Baker FAA AP 44.83 N 117.82 W 3368 7155 1741 NA NA NA NA
Bend 44.07 N 121.28 W 3660 6926 1405 NA NA NA NA
Corvallis State Univ 44.63 N 123.20 W 225 4923 2051 NA NA NA NA
Eugene WSO AP 44.12 N 123.22 W 364 4546 2354 21 87 65 NA
Grants Pass 42.42 N 123.33 W 960 4219 2986 NA NA NA NA
Klamath Falls 42.20 N 121.78 W 4098 6634 1954 4 87 62 NA
Medford WSO AP 42.38 N 122.88 W 1300 4611 2989 21 95 66 749
Pendleton WSO AP 45.68 N 118.85 W 1492 5294 2787 3 93 63 NA
Portland WSFO AP 45.60 N 122.60 W 21 4522 2517 22 86 66 1060
Roseburg KQEN 43.20 N 123.35 W 465 4312 2607 NA NA NA NA
Salem WSO AP 44.92 N 123.02 W 195 4927 2100 20 87 66 916
Pennsylvania (PA)
Allentown WSO AP 40.65 N 75.43 W 388 5785 3028 5 88 72 710
Altoona FAA AP 40.30 N 78.32 W 1476 6140 2719 5 86 70 NA
Chambersburg 39.93 N 77.63 W 640 5574 3060 NA NA NA NA
Erie WSO AP 42.08 N 80.18 W 732 6279 2652 2 83 70 716
Harrisburg FAA AP 40.22 N 76.85 W 338 5347 3358 9 89 73 648
Johnstown 40.33 N 78.92 W 1214 5649 3028 NA NA NA NA
Lancaster 40.05 N 76.28 W 270 5584 3079 NA NA NA NA
Meadville 41.63 N 80.17 W 1065 6934 2209 NA NA NA NA
New Castle 41.02 N 80.37 W 825 6542 2502 NA NA NA NA
Philadelphia WSCMO AP 39.88 N 75.23 W 10 4954 3623 11 89 74 646
Pittsburgh WSCMO2 AP 40.50 N 80.22 W 1150 5968 2836 2 86 70 700
Reading 40.37 N 75.93 W 270 5796 3021 NA NA NA NA
State College 40.80 N 77.87 W 1170 6364 2629 NA NA NA NA
Uniontown 39.92 N 79.72 W 956 5684 2913 NA NA NA NA
Warren 41.85 N 79.15 W 1210 6890 2334 NA NA NA NA
West Chester 39.97 N 75.63 W 450 5283 3288 NA NA NA NA
Williamsport WSO AP 41.25 N 76.92 W 524 6087 2796 2 87 71 NA
York Pump Station 22 39.92 N 76.75 W 390 5256 3274 NA NA NA NA
Rhode Island (RI)
Newport 41.52 N 71.32 W 20 5659 2548 NA NA NA NA
Providence WSO AP 41.73 N 71.43 W 51 5884 2743 5 86 71 684
South Carolina (SC)
Anderson 34.53 N 82.67 W 800 2965 4900 NA NA NA NA
Charleston WSO AP 32.90 N 80.03 W 41 2013 6188 NA NA NA NA
Charleston WSO City 32.78 N 79.93 W 10 1866 6303 25 92 77 NA
Columbia WSFO AP 33.95 N 81.12 W 213 2649 5508 21 94 75 705
Florence FAA AP 34.18 N 79.72 W 146 2585 5597 23 94 76 NA
Georgetown 33.35 N 79.25 W 10 2081 5947 NA NA NA NA
Greenville-Spartanburg WSO AP 34.90 N 82.22 W 973 3272 4625 19 91 74 851
Greenwood 34.17 N 82.20 W 615 3288 4673 NA NA NA NA
Orangeburg 33.50 N 80.87 W 160 2534 5477 NA NA NA NA
Spartanburg 34.98 N 81.88 W 840 2887 5046 NA NA NA NA
Sumter/Shaw AFB 33.97 N 80.48 W 240 2506 5453 24 93 75 NA
South Dakota (SD)
Aberdeen WSO AP 45.45 N 98.43 W 1296 8446 2497 NA NA NA NA
Brookings 44.32 N 96.77 W 1642 8653 2228 NA NA NA NA
Huron WSO AP 44.38 N 98.22 W 1282 7923 2709 —17 91 71 545
Mitchell 43.72 N 98.00 W 1274 7558 2925 NA NA NA NA
Pierre FAA AP 44.38 N 100.28 W 1726 7411 2938 —14 95 69 557
Rapid City WSO AP 44.05 N 103.07 W 3162 7301 2412 —11 91 65 572
Sioux Falls WSFO AP 43.57 N 96.73 W 1418 7809 2735 —16 90 72 599
Watertown FAA AP 44.92 N 97.15 W 1746 8375 2499 NA NA NA NA
Yankton 42.88 N 97.35 W 1180 7304 2935 NA NA NA NA
Tennessee (TN)
Athens 35.43 N 84.58 W 940 4054 4040 NA NA NA NA
Bristol WSO AP 36.48 N 82.40 W 1525 4406 3621 9 87 72 NA
Chattanooga WSO AP 35.03 N 85.20 W 692 3587 4609 15 92 75 684
Clarksville Sew Plt 36.55 N 87.37 W 382 4159 4241 NA NA NA NA
Columbia 35.63 N 87.08 W 650 4206 4047 NA NA NA NA
Dyersburg FAA AP 36.02 N 89.40 W 337 3536 5010 NA NA NA NA
Greeneville Exp Stn 36.10 N 82.85 W 1320 4392 3710 NA NA NA NA
Jackson FAA AP 35.60 N 88.92 W 433 3540 4915 12 93 76 NA
Knoxville WSO AP 35.80 N 84.00 W 949 3937 4164 13 90 74 703
Memphis FAA-AP 35.05 N 90.00 W 265 3082 5467 16 94 77 851
Murfreesboro 35.92 N 86.37 W 550 3992 4270 NA NA NA NA
Nashville WSO AP 36.12 N 86.68 W 580 3729 4689 10 92 75 749
Tullahoma 35.35 N 86.20 W 1048 3630 4422 NA NA NA NA
Texas (TX)
Abilene WSO AP 32.42 N 99.68 W 1784 2584 6050 16 97 71 648
Alice 27.73 N 98.07 W 201 1062 8121 NA NA NA NA
Amarillo WSO AP 35.23 N 101.70 W 3590 4258 4128 6 94 66 680
Austin WSO AP 30.30 N 97.70 W 597 1688 7171 25 96 74 664
Bay City Waterworks 28.98 N 95.98 W 52 1370 7211 NA NA NA NA
Beaumont Research Ctr 30.07 N 94.28 W 27 1677 6703 29 92 79 NA
Beeville 28.45 N 97.70 W 255 1372 7393 28 98 77 NA
Big Spring 32.25 N 101.45 W 2500 2772 5621 NA NA NA NA
Brownsville WSO AP 25.90 N 97.43 W 19 635 8777 36 94 77 422
Brownwood 31.72 N 99.00 W 1385 2199 6479 NA NA NA NA
Corpus Christi WSO AP 27.77 N 97.50 W 44 1016 8023 32 94 78 543
Corsicana 32.08 N 96.47 W 425 2396 6133 NA NA NA NA
Dallas FAA AP 32.85 N 96.85 W 440 2259 6587 17 98 74 NA
Del Rio/Laughlin AFB 29.37 N 100.78 W 1079 1565 7207 28 98 73 732
Denton 33.20 N 97.10 W 630 2665 5816 NA NA NA NA
Eagle Pass 28.70 N 100.48 W 805 1441 7682 NA NA NA NA
El Paso WSO AP 31.80 N 106.40 W 3918 2708 5488 21 98 64 735
Ft. Worth/Meacham 32.82 N 97.35 W 692 2304 6557 19 98 74 NA
Galveston WSO City 29.30 N 94.80 W 7 1263 7378 NA NA NA NA
Greenville 33.20 N 96.22 W 610 2953 5527 NA NA NA NA
Harlingen 26.20 N 97.67 W 38 813 8405 NA NA NA NA
Houston /Hobby 29.65 N 95.28 W 50 1371 7357 29 93 77 NA
Houston-Bush Intercontinental Airport 29.97 N 95.35 W 96 1599 6876 27 94 77 NA
Huntsville 30.72 N 95.55 W 494 1862 6697 NA NA NA NA
Killeen/Robert-Gray 31.07 N 97.83 W 1014 2127 6477 20 96 73 NA
Lamesa 32.70 N 101.93 W 2965 3159 5107 NA NA NA NA
Laredo 27.57 N 99.50 W 430 1025 8495 32 101 74 598
Longview 32.47 N 94.73 W 330 2433 5920 NA NA NA NA
Lubbock WSFO AP 33.65 N 101.82 W 3254 3431 4833 11 95 67 743
Lufkin FAA AP 31.23 N 94.75 W 281 1951 6527 23 95 77 681
McAllen 26.20 N 98.22 W 122 778 8597 34 98 76 NA
Midland/Odessa WSO AP 31.95 N 102.18 W 2857 2751 5588 17 97 67 729
Mineral Wells FAA AP 32.78 N 98.07 W 934 2625 6015 NA NA NA NA
Palestine 31.78 N 95.60 W 465 2005 6454 NA NA NA NA
Pampa No 2 35.53 N 100.98 W 3250 4358 4131 NA NA NA NA
Pecos 31.42 N 103.50 W 2610 2505 5992 NA NA NA NA
Plainview 34.18 N 101.70 W 3370 3717 4462 NA NA NA NA
Port Arthur WSO AP 29.95 N 94.02 W 16 1499 6994 NA NA NA 697
San Angelo WSO AP 31.37 N 100.50 W 1903 2414 6070 20 97 70 619
San Antonio WSFO 29.53 N 98.47 W 794 1644 7142 26 96 73 NA
Sherman 33.63 N 96.62 W 720 2890 5682 NA NA NA 721
Snyder 32.72 N 100.92 W 2335 3185 5178 NA NA NA NA
Temple 31.08 N 97.37 W 700 2153 6487 NA NA NA NA
Tyler 32.35 N 95.40 W 545 2194 6562 NA NA NA NA
Vernon 34.08 N 99.30 W 1202 3186 5605 NA NA NA NA
Victoria WSO AP 28.85 N 96.92 W 104 1296 7507 29 94 76 NA
Waco WSO AP 31.62 N 97.22 W 500 2179 6668 22 99 75 622
Wichita Falls WSO AP 33.97 N 98.48 W 994 3042 5717 NA NA NA 723
Utah (UT)
Cedar City FAA AP 37.70 N 113.10 W 5610 5962 2770 2 91 59 629
Logan Utah State Univ 41.75 N 111.80 W 4790 6854 2541 NA NA NA NA
Moab 38.60 N 109.60 W 3965 4494 4356 NA NA NA NA
Ogden Sugar Factory 41.23 N 112.03 W 4280 5950 3053 NA NA NA NA
Richfield Radio KSVC 38.77 N 112.08 W 5270 6367 2300 NA NA NA NA
Saint George 37.10 N 113.57 W 2760 3215 5424 NA NA NA NA
Salt Lake City NWSFO 40.78 N 111.95 W 4222 5765 3276 6 94 62 586
Vernal Airport 40.45 N 109.52 W 5260 7562 2334 NA NA NA NA
Vermont (VT)
Burlington WSO AP 44.47 N 73.15 W 332 7771 2228 —11 84 69 637
Rutland 43.60 N 72.97 W 620 7066 2345 NA NA NA NA
Virginia (VA)        
Charlottesville 38.03 N 78.52 W 870 4224 3902 NA NA NA NA
Danville-Bridge St 36.58 N 79.38 W 410 3944 4236 NA NA NA NA
Fredericksburg Natl Pk 38.32 N 77.45 W 90 4554 3754 NA NA NA NA
Lynchburg WSO AP 37.33 N 79.20 W 916 4340 3728 12 90 74 NA
Norfolk WSO AP 36.90 N 76.20 W 22 3495 4478 20 91 76 685
Richmond WSO AP 37.50 N 77.33 W 164 3963 4223 14 92 75 716
Roanoke WSO AP 37.32 N 79.97 W 1149 4360 3715 12 89 72 713
Staunton Sewage Plant 38.15 N 79.03 W 1385 5273 3004 NA NA NA NA
Winchester 39.18 N 78.12 W 680 5269 3215 NA NA NA NA
Washington (WA)        
Aberdeen 46.97 N 123.82 W 10 5285 1488 NA NA NA NA
Bellingham FAA AP 48.80 N 122.53 W 149 5609 1508 15 76 64 NA
Bremerton 47.57 N 122.67 W 162 5119 1839 NA NA NA NA
Ellensburg 46.97 N 120.55 W 1480 6770 1999 NA NA NA NA
Everett 47.98 N 122.18 W 60 5311 1660 NA NA NA NA
Kennewick 46.22 N 119.10 W 390 4895 3195 NA NA NA NA
Longview 46.15 N 122.92 W 12 5094 1858 NA NA NA NA
Olympia WSO AP 46.97 N 122.90 W 192 5655 1558 18 83 65 985
Port Angeles 48.12 N 123.40 W 40 5695 1257 NA NA NA NA
Seattle EMSU WSO 47.65 N 122.30 W 20 4611 2120 NA NA NA NA
Seattle-Tacoma WSCMO AP 47.45 N 122.30 W 450 4908 2021 23 81 64 982
Spokane WSO AP 47.63 N 117.53 W 2356 6842 2032 NA NA NA 640
Tacoma/McChord AFB 47.15 N 122.48 W 322 5155 1820 18 82 63 NA
Walla Walla FAA AP 46.10 N 118.28 W 1166 4958 3161 4 95 65 NA
Wenatchee 47.42 N 120.32 W 640 5579 2956 3 92 65 NA
Yakima WSO AP 46.57 N 120.53 W 1064 5967 2348 4 92 64 703
West Virginia (WV)
Beckley WSO AP 37.78 N 81.12 W 2504 5558 2690 NA NA NA NA
Bluefield FAA AP 37.30 N 81.22 W 2870 5230 2907 5 83 69 NA
Charleston WSFO AP 38.37 N 81.60 W 1015 4646 3655 6 88 73 704
Clarksburg 39.27 N 80.35 W 945 5512 3014 NA NA NA NA
Elkins WSO AP 38.88 N 79.85 W 1992 6120 2360 —2 83 70 NA
Huntington WSO AP 38.37 N 82.55 W 827 4665 3615 6 89 73 NA
Martinsburg FAA AP 39.40 N 77.98 W 531 5192 3368 8 91 73 NA
Morgantown FAA AP 39.65 N 79.92 W 1240 5363 3155 4 87 71 NA
Parkersburg 39.27 N 81.57 W 615 5094 3507 4 88 72 NA
Wisconsin (WI)
Appleton 44.25 N 88.37 W 750 7693 2513 NA NA NA NA
Ashland Exp Farm 46.57 N 90.97 W 650 8960 1811 NA NA NA NA
Beloit 42.50 N 89.03 W 780 7161 2737 NA NA NA NA
Eau Claire FAA AP 44.87 N 91.48 W 888 8330 2407 —18 87 71 661
Fond du Lac 43.80 N 88.45 W 760 7541 2573 NA NA NA NA
Green Bay WSO AP 44.48 N 88.13 W 682 8089 2177 —13 85 72 651
La Crosse FAA AP 43.87 N 91.25 W 651 7491 2790 —14 88 73 644
Madison WSO AP 43.13 N 89.33 W 858 767 2389 —11 87 72 658
Manitowoc 44.10 N 87.68 W 660 7597 2193 NA NA NA NA
Marinette 45.10 N 87.63 W 605 8059 2272 NA NA NA NA
Milwaukee WSO AP 42.95 N 87.90 W 672 7324 2388 —7 86 72 618
Racine 42.70 N 87.77 W 595 7167 2459 NA NA NA NA
Sheboygan 43.75 N 87.72 W 648 7087 2390 NA NA NA NA
Stevens Point 44.50 N 89.57 W 1079 8009 2325 NA NA NA NA
Waukesha 43.02 N 88.23 W 860 7117 2658 NA NA NA NA
Wausau FAA AP 44.92 N 89.62 W 1196 8427 2182 —15 85 70 NA
Wyoming (WY)
Casper WSO AP 42.92 N 106.47 W 5338 7682 2082 —13 89 58 535
Cheyenne WSFO AP 41.15 N 104.82 W 6120 7326 1886 —7 85 57 608
Cody 44.52 N 109.07 W 5050 7431 2057 —14 87 58 NA
Evanston 41.27 N 110.95 W 6810 8846 1285 NA NA NA NA
Lander WSO AP 42.82 N 108.73 W 5370 7889 2184 —14 87 58 NA
Laramie FAA AP 41.32 N 105.68 W 7266 9008 1237 NA NA NA NA
Newcastle 43.85 N 104.22 W 4410 7267 2518 NA NA NA NA
Rawlins FAA AP 41.80 N 107.20 W 6736 8475 1605 NA NA NA NA
Rock Springs FAA AP 41.60 N 109.07 W 6741 8365 1734 —9 84 54 552
Sheridan WSO AP 44.77 N 106.97 W 3964 7804 2023 —14 90 61 574
Torrington Exp Farm 42.08 N 104.22 W 4098 6879 2429 NA NA NA NA
District of Columbia (DC)
R. Reagan Nat'l. Airport 38.85 N 77.03 W 66 4047 4391 15 92 76 657
Puerto Rico (PR)
San Juan/Isla Verde WSFO 18.43 N 66.00 W 10 0 11,406 69 90 78 NA
Pacific Islands (PI)
Guam (GU)—Andersen AFB 13.58 N 144.93 E 361 0 10,690 74 87 79 NA
Marshall Island (MH)—Kwajalein Atoll 8.73 N 167.73 E 26 0 11,670 76 88 79 NA
Midway Island (MH) —Midway Island NAF 28.22 N 177.37 W 13 134 8323 59 86 75 NA
Samoa (WS)—Pago Pago WSO Airport 14.33 S 170.72 W 9 0 11,018 72 88 80 NA
Wake Island—Wake Island WSO Airport 19.28 N 166.65 E 12 0 11,097 71 89 79 NA
Philippines
Philippines (PH)—Angeles, Clark AFB 15.18 N 120.55 E 475 0 11,280 68 95 77 NA

TABLE D-2 Canadian Climatic Data

Province/City Latitude Longitude Elev.,
ft
HDD65 CDD50 Heating Design
Temperature
Cooling Design Temperature
Dry-Bulb Wet-Bulb
99.6% 1.0% 1.0%
Alberta (AB)
Calgary International A 51.12 N 114.02 W 3533 9885 1167 —22 80 59
Edmonton International A 53.30 N 113.58 W 2345 11,023 1069 —28.1 78 62
Grande Prairie A 55.18 N 118.88 W 2185 11,240 1031 —32 78 60
Jasper 52.88 N 118.07 W 3480 10,244 848 NA NA NA
Lethbridge A 49.63 N 112.80 W 3047 8783 1730 —22 84 61
Medicine Hat A 50.02 N 110.72 W 2352 8988 1981 —24 87 62
Red Deer A 52.18 N 113.90 W 2969 10,765 1095 —27 79 61
British Columbia (BC)
Dawson Creek A 55.73 N 120.18 W 2148 11,435 890 NA NA NA
Ft. Nelson A 58.83 N 122.58 W 1253 12,941 1013 —33 78 60
Kamloops 50.67 N 120.33 W 1243 6779 2335 —8 88 63
Nanaimo A 49.05 N 123.87 W 98 6054 1469 NA NA NA
New Westminster BC Pen 49.22 N 122.90 W 59 5520 1691 NA NA NA
Penticton A 49.47 N 119.60 W 1128 6500 2002 5 87 64
Prince George 53.88 N 122.67 W 2267 9495 906 —25 78 59
Prince Rupert A 54.30 N 130.43 W 111 7650 572 7 63 57
Vancouver International A 49.18 N 123.17 W 9 5682 1536 18 74 64
Victoria Gonzales Hts 48.42 N 123.32 W 229 5494 1286 23 75 62
Manitoba (MB)
Brandon CDA 49.87 N 99.98 W 1190 10,969 1661 —29 84 66
Churchill A 58.73 N 94.07 W 91 16,719 275 —36 72 60
Dauphin A 51.10 N 100.05 W 1000 11,242 1520 —28 84 66
Flin Flon 54.77 N 101.85 W 1099 12,307 1352 NA NA NA
Portage La Prairie A 49.90 N 98.27 W 885 10,594 1807 —25 85 67
The Pas A 53.97 N 101.10 W 889 12,490 1231 —32 79 64
Winnipeg International A 49.90 N 97.23 W 784 10,858 1784 —27 84 67
New Brunswick (NB)
Chatham A 47.02 N 65.45 W 111 9028 1531 —12 83 67
Fredericton A 45.87 N 66.53 W 55 8666 1631 —12 83 68
Moncton A 46.12 N 64.68 W 232 8731 1427 —10 80 67
Saint John A 45.33 N 65.88 W 337 8776 1179 —9 75 64
Newfoundland (NF)
Corner Brook 48.95 N 57.95 W 16 8756 1075 NA NA NA
Gander International A 48.95 N 54.57 W 495 9354 956 —4 76 63
Goose A 53.32 N 60.42 W 150 12,017 758 —23 77 61
St John's A 47.62 N 52.73 W 439 8888 848 3 73 64
Stephenville A 48.53 N 58.55 W 26 8869 952 —2 71 64
Northwest Territories (NW)
Ft. Smith A 60.02 N 111.95 W 666 14,192 932 —34 78 61
Inuvik A 68.30 N 133.48 W 193 18,409 489 —43 75 59
Yellowknife A 62.47 N 114.45 W 672 15,555 851 —39 74 59
Nova Scotia (NS)
Halifax International A 44.88 N 63.52 W 416 8133 1464 —2 78 66
Kentville CDA 45.07 N 64.48 W 160 7683 1665 NA NA NA
Sydney A 46.17 N 60.05 W 183 8364 1287 —1 78 67
Truro 45.37 N 63.27 W 131 8596 1295 —9 77 67
Yarmouth A 43.83 N 66.08 W 141 7515 1180 7 71 64
Nunavut                  
Resolute A 74.72 N 94.98 W 219 22,864 0 —42 48 43
Ontario (ON)
Belleville 44.15 N 77.40 W 249 7556 2252 NA NA NA
Cornwall 45.02 N 74.75 W 209 8062 2187 NA NA NA
Hamilton RBG 43.28 N 79.88 W 334 6872 2450 NA NA NA
Kapuskasing A 49.42 N 82.47 W 744 11,742 1108 —30 80 65
Kenora A 49.78 N 94.37 W 1335 10,884 1626 —27 81 65
Kingston A 44.22 N 76.60 W 305 7826 1960 NA NA NA
London A 43.03 N 81.15 W 912 7565 2126 —3 83 70
North Bay A 46.35 N 79.43 W 1174 9794 1509 —18 78 66
Oshawa WPCP 43.87 N 78.83 W 275 7253 2106 NA NA NA
Ottawa International A 45.32 N 75.67 W 380 8571 2045 —13 83 69
Owen Sound MOE 44.58 N 80.93 W 587 7730 1896 NA NA NA
Peterborough 44.28 N 78.32 W 636 8037 1975 NA NA NA
St Catharines 43.20 N 79.25 W 298 6700 2564 NA NA NA
Sudbury A 46.62 N 80.80 W 1141 9990 1557 —19 81 66
Thunder Bay A 48.37 N 89.32 W 652 10,562 1198 —22 80 66
Timmins A 48.57 N 81.37 W 967 11,374 1225 —28 81 65
Toronto Downsview A 43.75 N 79.48 W 649 7306 2370 —4 84 70
Windsor A 42.27 N 82.97 W 623 6619 2679 2 86 71
Prince Edward Island (PE)
Charlottetown A 46.28 N 63.13 W 157 8598 1400 —6 77 67
Summerside A 46.43 N 63.83 W 78 8411 1536 —5 77 66
Québec (PQ)
Bagotville A 48.33 N 71.00 W 521 10,603 1300 —23 80 65
Drummondville 45.88 N 72.48 W 269 8601 2024 NA NA NA
Granby 45.38 N 72.70 W 551 8367 1984 NA NA NA
Montreal Dorval International A 45.47 N 73.75 W 101 8285 2146 —12 83 70
Québec City A 46.80 N 71.38 W 229 9449 1571 —16 80 68
Rimouski 48.45 N 68.52 W 118 9665 1215 NA NA NA
Sept-Iles A 50.22 N 66.27 W 180 11,287 690 —20 69 59
Shawinigan 46.57 N 72.75 W 400 9246 1720 NA NA NA
Sherbrooke A 45.43 N 71.68 W 780 9464 1372 —20 80 68
St Jean de Cherbourg 48.88 N 67.12 W 1151 11,277 801 NA NA NA
St Jerome 45.80 N 74.05 W 557 9171 1771 NA NA NA
Thetford Mines 46.10 N 71.35 W 1250 9687 1425 NA NA NA
Trois Rivieres 46.37 N 72.60 W 173 9124 1766 NA NA NA
Val d'Or A 48.07 N 77.78 W 1105 11,256 1193 —27 80 65
Valleyfield 45.28 N 74.10 W 150 8083 2268 NA NA NA
Saskatchewan (SK)          
Estevan A 49.22 N 102.97 W 1876 10,092 1793 —25 86 65
Moose Jaw A 50.33 N 105.55 W 1893 9989 1812 —27 87 64
North Battleford A 52.77 N 108.25 W 1797 11,127 1473 —31 82 63
Prince Albert A 53.22 N 105.68 W 1404 12,009 1252 —34 81 64
Regina A 50.43 N 104.67 W 1893 10,773 1620 —29 85 64
Saskatoon A 52.17 N 106.68 W 1643 11,118 1537 —31 84 63
Swift Current A 50.28 N 107.68 W 2683 10,128 1541 —25 84 62
Yorkton A 51.27 N 102.47 W 1633 11,431 1476 —30 82 64
Yukon Territory (YT)          
Whitehorse A 60.72 N 135.07 W 2306 12,797 611 —34 73 55

TABLE D-3 International Climatic Data

Country/City Province or Region Latitude Longitude Elev.,
ft
HDD65 CDD50 Heating Design
Temperature
Cooling Design Temperature
Dry-Bulb Wet-Bulb
99.6% 1.0% 1.0%
Argentina
Buenos Aires/Ezeiza   34.82 S 58.53 W 66 2211 4693 31 90 72
Cordoba   31.32 S 64.22 W 1555 1816 5182 31 91 72
Tucuman/Pozo   26.85 S 65.10 W 1444 1416 6622 NA NA NA
Australia
Adelaide SA 34.95 S 138.53 E 20 2082 4381 39 92 64
Alice Springs NT 23.80 S 133.90 E 1782 1142 7777 34 102 64
Brisbane QL 27.43 S 153.08 E 7 545 7009 44 86 72
Darwin Airport NT 12.43 S 130.87 E 95 0 11,736 64 92 76
Perth/Guildford WA 31.92 S 115.97 E 56 1507 5353 41 95 66
Sydney/K Smith NSW 33.95 S 151.18 E 20 1351 5259 42 85 67
Azores
Lajes Terceira 38.75 N 27.08 W 180 1279 4892 46 78 71
Bahamas
Nassau   25.05 N 77.47 W 10 29 9775 57 90 78
Belgium
Brussels Airport   50.90 N 4.47 E 128 5460 1862 15 79 66
Bermuda
St Georges/Kindley   32.37 N 64.68 W 20 170 8365 NA NA NA
Bolivia
La Paz/El Alto   16.50 S 68.18 W 13,287 7189 237 25 62 44
Brazil
Belem   1.43 S 48.48 W 79 0 11,552 72 90 78
Brasilia   15.77 S 47.93 W 3809 58 7943 48 88 65
Fortaleza   3.72 S 38.55 W 62 1 11,748 72 90 78
Porto Alegre   30.08 S 51.18 W 23 902 7076 40 92 75
Recife/Curado   8.13 S 34.92 W 36 2 10,951 70 91 78
Rio de Janeiro   22.90 S 43.17 W 16 14 9688 59 99 77
Salvador/Ondina   13.00 S 38.52 W 167 0 10,785 68 88 78
Sao Paulo   23.50 S 46.62 W 2608 447 7219 48 88 69
Bulgaria
Sofia   42.82 N 23.38 E 1952 5629 2508 10 85 65
Chile
Concepcion   36.77 S 73.05 W 39 3559 2283 35 74 62
Punta Arenas/Chabunco   53.03 S 70.85 W 108 7807 395 23 61 53
Santiago/Pedahuel   33.38 S 70.88 W 1575 2820 3471 29 88 65
China
Beijing/Peking Municipalities 39.93 N 116.28 E 180 5252 4115 12 92 72
Hong Kong Intl Arpt Special Admin. Region 22.33 N 114.18 E 79 543 7894 48 91 79
Shanghai Municipalities 31.40 N 121.47 E 13 3182 5124 29 92 80
Shanghai/Hongqiao Municipalities 31.17 N 121.43 E 23 3184 5127 26 92 82
Tianjin/Tientsin Municipalities 39.10 N 117.17 E 16 4948 4450 14 91 74
Anqing Anhui 30.53 N 117.05 E 66 3093 5476 28 94 80
Bengbu Anhui 32.95 N 117.37 E 72 3,44 5053 23 93 79
Fuyang Anhui 32.93 N 115.83 E 128 3639 5004 23 93 79
Hefei/Luogang Anhui 31.87 N 117.23 E 118 3468 5110 25 93 80
Huang Shan (Mtns) Anhui 30.13 N 118.15 E 6024 6723 1647 9 70 65
Huoshan Anhui 31.40 N 116.33 E 223 3516 4907 24 94 80
Changting Fujian 25.85 N 116.37 E 1020 1902 6289 30 91 77
Fuding Fujian 27.33 N 120.20 E 125 1868 6277 34 92 80
Fuzhou Fujian 26.08 N 119.28 E 279 1396 7047 40 94 80
Jiuxian Shan Fujian 25.72 N 118.10 E 5417 3923 2763 23 74 67
Longyan Fujian 25.10 N 117.02 E 1119 1120 7248 37 93 75
Nanping Fujian 26.65 N 118.17 E 420 1551 6986 35 95 78
Pingtan Fujian 25.52 N 119.78 E 102 1478 6550 43 87 79
Pucheng Fujian 27.92 N 118.53 E 902 2325 5940 29 93 78
Shaowu Fujian 27.33 N 117.43 E 630 2075 6232 29 94 78
Xiamen Fujian 24.48 N 118.08 E 456 1014 7,26 43 91 79
Yong'An Fujian 25.97 N 117.35 E 669 1570 6917 33 95 77
Dunhuang Gansu 40.15 N 94.68 E 3740 6531 3272 1 93 64
Hezuo Gansu 35.00 N 102.90 E 9547 9760 491 —5 70 54
Huajialing Gansu 35.38 N 105.00 E 8038 9275 871 4 70 56
Jiuquan/Suzhou Gansu 39.77 N 98.48 E 4849 7316 2473 —2 86 62
Lanzhou Gansu 36.05 N 103.88 E 4980 5849 2954 11 87 63
Mazong Shan (Mount) Gansu 41.80 N 97.03 E 5807 9187 1748 —9 84 55
Minqin Gansu 38.63 N 103.08 E 4485 7045 2830 0 89 61
Pingliang Gansu 35.55 N 106.67 E 4423 6248 2407 9 84 64
Ruo'ergai Gansu 33.58 N 102.97 E 11,289 10,826 232 —8 65 52
Tianshui Gansu 34.58 N 105.75 E 3750 5192 3073 17 87 67
Wudu Gansu 33.40 N 104.92 E 3540 3419 4250 28 90 68
Wushaoling (Pass) Gansu 37.20 N 102.87 E 9987 11,697 263 —5 64 50
Xifengzhen Gansu 35.73 N 107.63 E 4669 6471 2388 10 82 63
Yumenzhen Gansu 40.27 N 97.03 E 5010 7614 2367 —3 86 60
Zhangye Gansu 38.93 N 100.43 E 4865 7288 2439 —2 88 62
Fogang Guangdong 23.87 N 113.53 E 223 1063 7709 39 92 79
Gaoyao Guangdong 23.05 N 112.47 E 39 720 8493 44 93 80
Guangzhou/Baiyun Guangdong 23.13 N 113.32 E 26 737 8352 42 93 80
Heyuan Guangdong 23.73 N 114.68 E 135 902 8079 40 93 79
Lian Xian Guangdong 24.78 N 112.38 E 322 1660 7018 35 94 79
Lianping Guangdong 24.37 N 114.48 E 702 1301 7189 36 92 78
Meixian Guangdong 24.30 N 116.12 E 276 937 8016 39 94 79
Shangchuan Island Guangdong 21.73 N 112.77 E 59 514 8621 46 89 81
Shantou Guangdong 23.40 N 116.68 E 10 779 7743 45 90 80
Shanwei Guangdong 22.78 N 115.37 E 16 528 8272 46 89 79
Shaoguan Guangdong 24.80 N 113.58 E 223 1370 7565 37 94 79
Shenzhen Guangdong 22.55 N 114.10 E 59 531 8597 44 92 80
Xinyi Guangdong 22.35 N 110.93 E 276 570 8763 43 93 79
Yangjiang Guangdong 21.87 N 111.97 E 72 547 8470 45 90 80
Zhangjiang Guangdong 21.22 N 110.40 E 92 423 9002 46 92 80
Beihai Guangxi 21.48 N 109.10 E 52 621 8826 44 91 80
Bose Guangxi 23.90 N 106.60 E 794 716 8488 43 96 79
Guilin Guangxi 25.33 N 110.30 E 545 1971 6549 35 92 78
Guiping Guangxi 23.40 N 110.08 E 144 957 8084 42 93 80
Hechi/Jnchengjiang Guangxi 24.70 N 108.05 E 702 1229 7489 40 93 78
Lingling Guangxi 26.23 N 111.62 E 571 2608 5993 31 94 78
Liuzhou Guangxi 24.35 N 109.40 E 318 1370 7604 38 94 78
Longzhou Guangxi 22.37 N 106.75 E 423 681 8596 43 94 80
Mengshan Guangxi 24.20 N 110.52 E 476 1485 7125 36 92 79
Nanning/Wuxu Guangxi 22.82 N 108.35 E 240 857 8315 42 93 79
Napo Guangxi 23.30 N 105.95 E 2605 1283 6469 37 87 74
Qinzhou Guangxi 21.95 N 108.62 E 20 769 8415 43 91 80
Wuzhou Guangxi 23.48 N 111.30 E 394 1074 7934 39 94 80
Bijie Guizhou 27.30 N 105.23 E 4957 3837 3496 27 83 68
Dushan Guizhou 25.83 N 107.55 E 3340 3021 4530 27 83 71
Guiyang Guizhou 26.58 N 106.72 E 3524 2879 4689 28 85 70
Luodian Guizhou 25.43 N 106.77 E 1447 1351 7066 38 93 77
Rongjiang/Guzhou Guizhou 25.97 N 108.53 E 942 1967 6362 34 93 78
Sansui Guizhou 26.97 N 108.67 E 2005 3322 4659 28 88 75
Sinan Guizhou 27.95 N 108.25 E 1371 2494 5719 34 93 76
Weining Guizhou 26.87 N 104.28 E 7336 4632 2342 21 75 60
Xingren Guizhou 25.43 N 105.18 E 4524 2595 4527 30 83 68
Zunyi Guizhou 27.70 N 106.88 E 2772 3091 4673 30 88 73
Danxian/Nada Hainan 19.52 N 109.58 E 554 245 9606 48 94 78
Dongfang/Basuo Hainan 19.10 N 108.62 E 26 107 10,168 53 91 81
Haikou Hainan 20.03 N 110.35 E 49 211 9659 51 93 81
Qionghai/Jiaji Hainan 19.23 N 110.47 E 82 133 9882 52 93 81
Sanhu Island Hainan 16.53 N 111.62 E 16 0 11,282 69 90 83
Xisha Island Hainan 16.83 N 112.33 E 16 0 11,221 69 89 82
Yaxian/Sanya Hainan 18.23 N 109.52 E 23 7 10,735 60 90 80
Baoding Hebei 38.85 N 115.57 E 62 4949 4411 14 93 73
Cangzhou Hebei 38.33 N 116.83 E 36 4888 4504 14 92 74
Chengde Hebei 40.97 N 117.93 E 1227 6778 3356 0 89 69
Fengning/Dagezhen Hebei 41.22 N 116.63 E 2169 7891 2574 —5 86 66
Huailai/Shacheng Hebei 40.40 N 115.50 E 1765 6490 3403 5 89 67
Leting Hebei 39.43 N 118.90 E 39 5918 3562 8 87 74
Qinglong Hebei 40.40 N 118.95 E 748 6611 3261 0 88 71
Shijiazhuang Hebei 38.03 N 114.42 E 266 4695 4469 15 93 73
Tangshan Hebei 39.67 N 118.15 E 95 5675 3867 8 89 74
Weichang/Zhuizishan Hebei 41.93 N 117.75 E 2769 8600 2201 —6 83 65
Xingtai Hebei 37.07 N 114.50 E 256 4506 4626 18 93 73
Yu Xian Hebei 39.83 N 114.57 E 2986 7948 2545 —9 86 65
Zhangjiakou Hebei 40.78 N 114.88 E 2382 6823 3202 2 88 65
Aihui Heilongjiang 50.25 N 127.45 E 545 11,840 1840 —28 83 68
Anda Heilongjiang 46.38 N 125.32 E 492 10,066 2482 —20 86 69
Baoqing Heilongjiang 46.32 N 132.18 E 272 9731 2379 —17 85 69
Fujin Heilongjiang 47.23 N 131.98 E 213 10,265 2356 —18 85 70
Hailun Heilongjiang 47.43 N 126.97 E 787 11,017 2137 —24 83 68
Harbin Heilongjiang 45.75 N 126.77 E 469 9830 2482 —20 85 69
Hulin Heilongjiang 45.77 N 132.97 E 338 9977 2228 —17 82 70
Huma Heilongjiang 51.72 N 126.65 E 587 12,658 1760 —36 84 67
Jixi Heilongjiang 45.28 N 130.95 E 768 9518 2318 —14 84 69
Keshan Heilongjiang 48.05 N 125.88 E 778 11,108 2123 —25 84 68
Mudanjiang Heilongjiang 44.57 N 129.60 E 794 9464 2449 —16 85 69
Qiqihar Heilongjiang 47.38 N 123.92 E 486 9924 2514 —18 86 69
Shangzhi Heilongjiang 45.22 N 127.97 E 627 10,340 2189 —26 84 70
Suifenhe Heilongjiang 44.38 N 131.15 E 1634 10,219 1714 —16 82 68
Sunwu Heilongjiang 49.43 N 127.35 E 771 12,334 1585 —32 83 68
Tailai Heilongjiang 46.40 N 123.42 E 492 9431 2663 —16 87 69
Tonghe Heilongjiang 45.97 N 128.73 E 361 10,618 2210 —24 84 71
Yichun Heilongjiang 47.72 N 128.90 E 761 11,239 1965 —28 83 68
Anyang/Zhangde Henan 36.12 N 114.37 E 249 4318 4648 18 93 75
Boxian Henan 33.88 N 115.77 E 138 4006 4755 20 93 77
Gushi Henan 32.17 N 115.67 E 190 3567 4964 24 92 80
Lushi Henan 34.05 N 111.03 E 1870 4572 3865 17 90 73
Nanyang Henan 33.03 N 112.58 E 430 3779 4750 23 92 77
Xihua Henan 33.78 N 114.52 E 174 4032 4623 21 93 78
Xinyang Henan 32.13 N 114.05 E 377 3576 4922 24 92 78
Zhengzhou Henan 34.72 N 113.65 E 364 4146 4614 19 93 75
Zhumadian Henan 33.00 N 114.02 E 272 3885 4718 22 93 77
Fangxian Hubei 32.03 N 110.77 E 1427 3688 4483 24 91 75
Guanghua Hubei 32.38 N 111.67 E 299 3445 4989 26 93 79
Jiangling/Jingzhou Hubei 30.33 N 112.18 E 108 3064 5325 29 93 81
Macheng Hubei 31.18 N 114.97 E 194 3166 5363 27 94 80
Wuhan/Nanhu Hubei 30.62 N 114.13 E 75 3140 5433 28 94 81
Yichang Hubei 30.70 N 111.30 E 440 2812 5476 30 93 79
Zaoyang Hubei 32.15 N 112.67 E 417 3463 5034 25 93 78
Zhongxiang Hubei 31.17 N 112.57 E 217 3192 5240 28 92 80
Changde Hunan 29.05 N 111.68 E 115 2896 5520 30 95 81
Chenzhou Hunan 25.80 N 113.03 E 607 2496 6255 31 95 78
Nanyue Hunan 27.30 N 112.70 E 4196 4866 3090 17 77 71
Sangzhi Hunan 29.40 N 110.17 E 1056 2896 5229 30 93 77
Shaoyang Hunan 27.23 N 111.47 E 814 2794 5651 30 93 78
Tongdao/Shuangjiang Hunan 26.17 N 109.78 E 1302 2706 5440 30 90 76
Wugang Hunan 26.73 N 110.63 E 1115 2854 5424 30 92 77
Yuanling Hunan 28.47 N 110.40 E 469 2817 5442 30 93 78
Yueyang Hunan 29.38 N 113.08 E 171 2870 5681 30 92 81
Zhijiang Hunan 27.45 N 109.68 E 896 2857 5385 30 92 78
Abag Qi/Xin Hot Inner Mongolia 44.02 N 114.95 E 3701 11,253 1853 —25 84 60
Arxan Inner Mongolia 47.17 N 119.95 E 3373 13,802 964 —35 77 61
Bailing-Miao Inner Mongolia 41.70 N 110.43 E 4518 9399 2005 —15 85 59
Bayan Mod Inner Mongolia 40.75 N 104.50 E 4360 7762 2911 —6 89 59
Bugt Inner Mongolia 48.77 N 121.92 E 2425 12,243 1187 —22 79