Access and working space shall be provided and maintained around all electrical equipment to permit ready and safe operation and maintenance of such equipment in accordance with this section and Figure E3405.1. (110.26)


For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
  1. Equipment, piping and ducts foreign to the electrical installation shall not be placed in the shaded areas extending from the floor to a height of 6 feet above the panelboard enclosure or to the structural ceiling, whichever is lower.
  2. The working space shall be clear and unobstructed from the floor to a height of 6.5 feet or the height of the equipment, whichever is greater.
  3. The working space shall not be designated for storage.
  4. Panelboards, service equipment and similar enclosures shall not be located in bathrooms, toilet rooms, clothes closets or over the steps of a stairway.
  5. Such work spaces shall be provided with artificial lighting where located indoors and shall not be controlled by automatic means only.
FIGURE E3405.1 a, b, c, d, e
WORKING SPACE AND CLEARANCES

Related Code Sections

603.4 Building Services and Systems, Working Space and Clearances
Working space around electrical equipment shall be provided in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000 volts ...
604.3 Building Services and Systems, Working Space and Clearance
A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided ...
306.1.1 General Regulations, Central Furnaces
Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76 mm) along the sides, back and top ...
(2) General, Outdoor
from accidental spillage or leakage from piping systems (b) Work Space. The working clearance space shall include the zone described in 110.26(A ...