2109.7.3.1 Wood Floor Joists
JUMP TO FULL CODE CHAPTER
Wood floor joists bearing on masonry walls shall be anchored to the wall at intervals not to exceed 72 inches (1829 mm) by metal strap anchors. Joists parallel to the wall shall be anchored with metal straps spaced not more than 72 inches (1829 mm) o.c. extending over or under and secured to at least three joists. Blocking shall be provided between joists at each strap anchor.
Related Code Sections
2109.7.3.1 Masonry, Wood Floor Joists
Wood floor joists bearing on masonry walls shall be anchored to the wall at intervals not to exceed 72 inches (1829 mm) by metal strap anchors ...
2010 Building Code of NY > 21 Masonry > 2109 Empirical Design of Masonry > 2109.7 Anchorage > 2109.7.3 Floor and Roof Anchorage > 2109.7.3.1 Wood Floor Joists
R502.3.2 Floors, Other Floor Joists
Table R502.3.1(2) shall be used to determine the maximum allowable span of floor joists that support other areas of the building, other than sleeping ...
Residential Code 2015 of New York State > 5 Floors > R502 Wood Floor Framing > R502.3 Allowable Joist Spans > R502.3.2 Other Floor Joists
R502.3.2 Floors, Other Floor Joists
Table R502.3.1(2) shall be used to determine the maximum allowable span of floor joists that support other areas of the building, other than sleeping ...
2020 Residential Code of New York State > 5 Floors > R502 Wood Floor Framing > R502.3 Allowable Joist Spans > R502.3.2 Other Floor Joists
R502.3.2 Floors, Other Floor Joists
Table R502.3.1(2) shall be used to determine the maximum allowable span of floor joists that support all other areas of the building, other than ...
2010 Residential Code of NY > 5 Floors > R502 Wood Floor Framing > R502.3 Allowable Joist Spans > R502.3.2 Other Floor Joists
R502.3.3 Floors, Floor Cantilevers
Floor cantilever spans shall not exceed the nominal depth of the wood floor joist. Floor cantilevers constructed in accordance with Table R502.3.3(1 ...