• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

722.6 Wood Assemblies

Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.6 Wood Assemblies
JUMP TO FULL CODE CHAPTER
The provisions of this section contain procedures by which the fire-resistance ratings of wood assemblies are established by calculations.

722.6.1 General

This section contains procedures for calculating the fire-resistance ratings of walls, floor/ceiling and roof/ceiling assemblies based in part on the standard method of testing referenced in Section 703.2.

722.6.1.1 Maximum Fire-Resistance Rating

Fire-resistance ratings calculated for assemblies using the methods in Section 722.6 shall be limited to not more than 1 hour.

722.6.1.2 Dissimilar Membranes

Where dissimilar membranes are used on a wall assembly that requires consideration of fire exposure from both sides, the calculation shall be made from the least fire-resistant (weaker) side.

722.6.2 Walls, Floors and Roofs

These procedures apply to both load-bearing and nonload-bearing assemblies.

TABLE 722.6.2(1)
TIME ASSIGNED TO WALLBOARD MEMBRANESa, b, c, d
DESCRIPTION OF FINISH TIMEe(minutes)
3/8-inch wood structural panel bonded with exterior glue 5
15/32-inch wood structural panel bonded with exterior glue 10
19/32-inch wood structural panel bonded with exterior glue 15
3/8-inch gypsum wallboard 10
1/2-inch gypsum wallboard 15
5/8-inch gypsum wallboard 30
1/2-inch Type X gypsum wallboard 25
5/8-inch Type X gypsum wallboard 40
Double 3/8-inch gypsum wallboard 25
1/2-inch + 3/8-inch gypsum wallboard 35
Double 1/2-inch gypsum wallboard 40

For SI: 1 inch = 25.4 mm.
  1. These values apply only where membranes are installed on framing members that are spaced 16 inches o.c. or less.
  2. Gypsum wallboard installed over framing or furring shall be installed so that all edges are supported, except 5/8-inch Type X gypsum wallboard shall be permitted to be installed horizontally with the horizontal joints staggered 24 inches each side and unsupported but finished.
  3. On wood frame floor/ceiling or roof/ceiling assemblies, gypsum board shall be installed with the long dimension perpendicular to framing members and shall have all joints finished.
  4. The membrane on the unexposed side shall not be included in determining the fire resistance of the assembly. Where dissimilar membranes are used on a wall assembly, the calculation shall be made from the least fire-resistant (weaker) side.
  5. The time assigned is not a finished rating.
TABLE 722.6.2(2)
TIME ASSIGNED FOR CONTRIBUTION OF WOOD FRAME a, b, c
DESCRIPTION TIME ASSIGNED TO FRAME (minutes)
Wood studs 16 inches o.c. 20
Wood floor and roof joists 16 inches o.c. 10

For SI: 1 inch = 25.4 mm.
  1. This table does not apply to studs or joists spaced more than 16 inches o.c.
  2. All studs shall be nominal 2 × 4 and all joists shall have a nominal thickness of not less than 2 inches.
  3. Allowable spans for joists shall be determined in accordance with Sections 2308.4.2.1, 2308.7.1 and 2308.7.2.
TABLE 722.6.2(3)
MEMBRANEa ON EXTERIOR FACE OF WOOD STUD WALLS
SHEATHING PAPER EXTERIOR FINISH
5/8-inch T & G lumber
5/16-inch exterior glue wood structural panel
1/2-inch gypsum wallboard
5/8-inch gypsum wallboard
1/2-inch fiberboard
Sheathing paper Lumber siding
Wood shingles and shakes
1/4-inch fiber-cement lap, panel or shingle siding
1/4-inch wood structural panels-exterior type
1/4-inch hardboard
Metal siding
Stucco on metal lath
Masonry veneer
Vinyl siding
None — 3/8-inch exterior-grade wood structural panels

For SI: 1 inch = 25.4 mm.
  1. Any combination of sheathing, paper and exterior finish is permitted.
TABLE 722.6.2(4)
FLOORING OR ROOFING OVER WOOD FRAMINGa
ASSEMBLY STRUCTURAL
MEMBERS
SUBFLOOR OR ROOF DECK FINISHED FLOORING OR ROOFING
Floor Wood 15/32-inch wood structural panels or
11/16-inch T & G softwood
Hardwood or softwood flooring on building paper resilient flooring, parquet floor felted-synthetic fiber floor coverings, carpeting, or ceramic tile on 1/4-inch-thick fiber-cement underlayment or 3/8-inch-thick panel-type underlay
Ceramic tile on 11/4-inch mortar bed
Roof Wood 15/32-inch wood structural panels or
11/16-inch T & G softwood
Finished roofing material with or without insulation

For SI: 1 inch = 25.4 mm.
  1. This table applies only to wood joist construction. It is not applicable to wood truss construction.
TABLE 722.6.2(5)
TIME ASSIGNED FOR ADDITIONAL PROTECTION
DESCRIPTION OF ADDITIONAL PROTECTION FIRE RESISTANCE (minutes)
Add to the fire-resistance rating of wood stud walls if the spaces between the studs are completely filled with glass fiber mineral wool batts weighing not less than 2 pounds per cubic foot (0.6 pound per square foot of wall surface) or rockwool or slag material wool batts weighing not less than 3.3 pounds per cubic foot (1 pound per square foot of wall surface), or cellulose insulation having a nominal density not less than 2.6 pounds per cubic foot. 15

For SI: 1 pound/cubic foot = 16.0185 kg/m3.

722.6.2.1 Fire-Resistance Rating of Wood Frame Assemblies

The fire-resistance rating of a wood frame assembly is equal to the sum of the time assigned to the membrane on the fire-exposed side, the time assigned to the framing members and the time assigned for additional contribution by other protective measures such as insulation. The membrane on the unexposed side shall not be included in determining the fire resistance of the assembly.

722.6.2.2 Time Assigned to Membranes

Table 722.6.2(1) indicates the time assigned to membranes on the fire-exposed side.

722.6.2.3 Exterior Walls

For an exterior wall with a fire separation distance greater than 10 feet (3048 mm), the wall is assigned a rating dependent on the interior membrane and the framing as described in Tables 722.6.2(1) and 722.6.2(2). The membrane on the outside of the nonfire-exposed side of exterior walls with a fire separation distance greater than 10 feet (3048 mm) shall consist of sheathing, sheathing paper and siding as described in Table 722.6.2(3).

722.6.2.4 Floors and Roofs

In the case of a floor or roof, the standard test provides only for testing for fire exposure from below. Except as noted in Section 703.3, Item 5, floor or roof assemblies of wood framing shall have an upper membrane consisting of a subfloor and finished floor conforming to Table 722.6.2(4) or any other membrane that has a contribution to fire resistance of not less than 15 minutes in Table 722.6.2(1).

722.6.2.5 Additional Protection

Table 722.6.2(5) indicates the time increments to be added to the fire resistance where glass fiber, rockwool, slag mineral wool or cellulose insulation is incorporated in the assembly.

722.6.2.6 Fastening

Fastening of wood frame assemblies and the fastening of membranes to the wood framing members shall be done in accordance with Chapter 23.

Related Code Sections


722.6 Fire and Smoke Protection Features, Wood Assemblies
The provisions of this section contain procedures by which the fire-resistance ratings of wood assemblies are established by calculations ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.6 Wood Assemblies
722.6 Fire and Smoke Protection Features, Wood Assemblies
The provisions of this section contain procedures by which the fire-resistance ratings of wood assemblies are established by calculations ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.6 Wood Assemblies
722.6.2.1 Fire and Smoke Protection Features, Fire-Resistance Rating of Wood Frame Assemblies
The fire-resistance rating of a wood frame assembly is equal to the sum of the time assigned to the membrane on the fire-exposed side, the time ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.6 Wood Assemblies > 722.6.2 Walls, Floors and Roofs > 722.6.2.1 Fire-Resistance Rating of Wood Frame Assemblies
722.6.1.1 Fire and Smoke Protection Features, Maximum Fire-Resistance Rating
Fire-resistance ratings calculated for assemblies using the methods in Section 722.6 shall be limited to not more than 1 hour ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.6 Wood Assemblies > 722.6.1 General > 722.6.1.1 Maximum Fire-Resistance Rating
722.6.1.1 Fire and Smoke Protection Features, Maximum Fire-Resistance Rating
Fire-resistance ratings calculated for assemblies using the methods in Section 722.6 shall be limited to not more than 1 hour ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.6 Wood Assemblies > 722.6.1 General > 722.6.1.1 Maximum Fire-Resistance Rating
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING