1926.408(a)(1) Wiring Methods for Fixed Installations
JUMP TO FULL CODE CHAPTER
Above-ground conductors shall be installed in rigid metal conduit, in intermediate metal conduit, in cable trays, in cablebus, in other suitable raceways, or as open runs of metal-clad cable designed for the use and purpose. However, open runs of non-metallic-sheathed cable or of bare conductors or busbars may be installed in locations which are accessible only to qualified persons. Metallic shielding components, such as tapes, wires, or braids for conductors, shall be grounded. Open runs of insulated wires and cables having a bare lead sheath or a braided outer covering shall be supported in a manner designed to prevent physical damage to the braid or sheath.
Conductors emerging from the ground shall be enclosed in raceways. Raceways installed on poles shall be of rigid metal conduit, intermediate metal conduit, PVC schedule 80 or equivalent extending from the ground line up to a point 8 feet (2.44 m) above finished grade. Conductors entering a building shall be protected by an enclosure from the ground line to the point of entrance. Metallic enclosures shall be grounded.
Related Code Sections
1926.408(a)(1) Electrical, Wiring Methods for Fixed Installations
or busbars may be installed in locations which are accessible only to qualified persons. Metallic shielding components, such as tapes, wires, or braids ...
OSHA 1926 Construction > K Electrical > 1926.408 Special Systems > 1926.408(a) Systems Over 600 Volts, Nominal > 1926.408(a)(1) Wiring Methods for Fixed Installations
1926.405(a) Electrical, Wiring Methods
of any type shall be installed in ducts used to transport dust, loose stock or flammable vapors. No wiring system of any type shall be installed in any ...
OSHA 1926 Construction > K Electrical > 1926.405 Wiring Methods, Components, and Equipment for General Use > 1926.405(a) Wiring Methods
1926.404(f)(8) Electrical, Methods of Grounding Equipment
Noncurrent-carrying metal parts of fixed equipment, if required to be grounded by this subpart, shall be grounded by an equipment grounding conductor ...
OSHA 1926 Construction > K Electrical > 1926.404 Wiring Design and Protection > 1926.404(f) Grounding > 1926.404(f)(8) Methods of Grounding Equipment
1926.407(b) Electrical, Electrical Installations
Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be approved as intrinsically safe or approved ...
OSHA 1926 Construction > K Electrical > 1926.407 Hazardous (Classified) Locations > 1926.407(b) Electrical Installations
1926.405(a)(2)(ii)(B) Electrical,
branch-circuit conductors shall be laid on the floor. Each branch circuit that supplies receptacles or fixed equipment shall contain a separate equipment ...
OSHA 1926 Construction > K Electrical > 1926.405 Wiring Methods, Components, and Equipment for General Use > 1926.405(a) Wiring Methods > 1926.405(a)(2) Temporary Wiring > 1926.405(a)(2)(ii) General Requirements for Temporary Wiring > 1926.405(a)(2)(ii)(B)