1224.4.9 Windows and Screens
JUMP TO FULL CODE CHAPTER
Patient room windows shall have sills not more than 36 inches (914 mm) above the floor. If operable windows are provided that require the use of tools or keys for operation, the tools or keys shall be located at the nurses' station.
Exception: Window sills in intensive-care units may be 60 inches (1524 mm) above the floor.
If operable windows are provided in airborne infection isolation or protective environment rooms, they shall only be operable by the use of tools or keys which shall be located at the nurses' station.
Safety glass or plastic glazing materials shall be used in windows in psychiatric patient areas.
Windows which may be frequently left in an open position shall be provided with insect screens of 16 meshes to the inch.
All portions of a building used by patients, personnel or other persons shall be provided with artificial light and a mechanically operated ventilating system as specified in the California Electrical Code and the California Mechanical Code.
Related Code Sections
1224.4.9 Interior Environment, Windows and Screens
Rooms approved for the housing
of patients shall be provided with natural light by
means of exterior glazed openings excluding clerestory
windows ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.4 General Construction > 1224.4.9 Windows and Screens
1224.4.9 Interior Environment, Windows and Screens
Rooms approved for the housing
of patients shall be provided with natural light
by means of exterior glazed openings excluding
clerestory windows ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.4 General Construction > 1224.4.9 Windows and Screens
1227.7 Interior Environment, Windows and Screens
When windows are operable, they shall be provided with insect screens of 16 meshes ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1227 [OSHPD 4] Correctional Treatment Centers > 1227.7 Windows and Screens
1227.7 Interior Environment, Windows and Screens
When windows are operable, they shall
be provided with insect screens of 16 meshes ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1227 [OSHPD 4] Correctional Treatment Centers > 1227.7 Windows and Screens
1228.4.9 Interior Environment, Windows and Screens
Windows located in patient care areas, or areas
used by patients, shall limit the opportunities for
patients to inflict harm to themselves ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.4 General Construction > 1228.4.9 Windows and Screens