1609.1.1.2 Wind Tunnel Test Limitations
JUMP TO FULL CODE CHAPTER
The lower limit on pressures for main wind-force-resisting systems and components and cladding shall be in accordance with Sections 1609.1.1.2.1 and 1609.1.1.2.2.
Base overturning moments determined from wind tunnel testing shall be limited to not less than 80 percent of the design base overturning moments determined in accordance with Section 6.5 of ASCE 7, unless specific testing is performed that demonstrates it is the aerodynamic coefficient of the building, rather than shielding from other structures, that is responsible for the lower values. The 80-percent limit shall be permitted to be adjusted by the ratio of the frame load at critical wind directions as determined from wind tunnel testing without specific adjacent buildings, but including appropriate upwind roughness, to that determined in Section 6.5 of ASCE 7.
The design pressures for components and cladding on walls or roofs shall be selected as the greater of the wind tunnel test results or 80 percent of the pressure obtained for Zone 4 for walls and Zone 1 for roofs as determined in Section 6.5 of ASCE 7, unless specific testing is performed that demonstrates it is the aerodynamic coefficient of the building, rather than shielding from nearby structures, that is responsible for the lower values. Alternatively, limited tests at a few wind directions without specific adjacent buildings, but in the presence of an appropriate upwind roughness, shall be permitted to be used to demonstrate that the lower pressures are due to the shape of the building and not to shielding.
Related Code Sections
1609.1.1.2 Structural Design, Wind Tunnel Test Limitations
from wind tunnel testing shall be limited to not less than 80 percent of the design base overturning moments determined in accordance with Section 6.5 ...
Ohio Building Code 2011 > 16 Structural Design > 1609 Wind Loads > 1609.1 Applications > 1609.1.1 Determination of Wind Loads > 1609.1.1.2 Wind Tunnel Test Limitations
1716.2.2 Structural Tests and Special Inspections, Wind Tunnel Testing
When roof tiles do not satisfy the limitations in Chapter 16 for rigid tile, a wind tunnel test shall be used to determine the wind characteristics ...
Ohio Building Code 2011 > 17 Structural Tests and Special Inspections > 1716 Material and Test Standards > 1716.2 Concrete and Clay Roof Tiles > 1716.2.2 Wind Tunnel Testing
1504.2.1.2 Roof Assemblies and Rooftop Structures, Wind Tunnel Testing
Where concrete and clay roof tiles do not satisfy the limitations in Chapter 16 for rigid tile, a wind tunnel test shall be used to determine ...
Ohio Building Code 2017 > 15 Roof Assemblies and Rooftop Structures > 1504 Performance Requirements > 1504.2 Wind Resistance of Clay and Concrete Tile > 1504.2.1 Testing > 1504.2.1.2 Wind Tunnel Testing
1504.2 Roof Assemblies and Rooftop Structures, Wind Resistance of Clay and Concrete Tile
, a wind tunnel test shall be used to determine the wind characteristics of the concrete or clay tile roof covering in accordance with SBCCI SSTD 11 ...
Ohio Building Code 2017 > 15 Roof Assemblies and Rooftop Structures > 1504 Performance Requirements > 1504.2 Wind Resistance of Clay and Concrete Tile
1609.1 Structural Design, Applications
structures and antennas. Wind tunnel tests in accordance with Section 6.6 of ASCE 7, subject to the limitations in Section 1609.1.1.2 ...