1028.6.3 Width of Means of Egress for Outdoor Smoke-Protected Assembly
JUMP TO FULL CODE CHAPTER
The clear width in inches (mm) of aisles and other means of egress shall be not less than the total occupant load served by the egress element multiplied by 0.08 (2.0 mm) where egress is by aisles and stairs and multiplied by 0.06 (1.52 mm) where egress is by ramps, corridors, tunnels or vomitories.
Exception: The clear width in inches (mm) of aisles and other means of egress shall be permitted to comply with Section 1028.6.2 for the number of seats in the outdoor smoke-protected assembly where Section 1028.6.2 permits less width.
Related Code Sections
1028.6.3 Means of Egress, Width of Means of Egress for Outdoor Smoke-Protected Assembly
1028.6.2 for the number of seats in the outdoor smoke-protected assembly where Section 1028.6.2 permits less width.
...
Fire Code 2009 of Alabama > 10 Means of Egress > 1028 Assembly > 1028.6 Width of Means of Egress for Assembly > 1028.6.3 Width of Means of Egress for Outdoor Smoke-Protected Assembly
1028.6.3 Means of Egress, Width of Means of Egress for Outdoor Smoke-Protected Assembly
1028.6.2 for the number of seats in the outdoor smoke-protected assembly where Section 1028.6.2 permits less width ...
Building Code 2009 of Alabama > 10 Means of Egress > 1028 Assembly > 1028.6 Width of Means of Egress for Assembly > 1028.6.3 Width of Means of Egress for Outdoor Smoke-Protected Assembly
Section 1028 Means of Egress, Assembly
The clear width of the means of egress for smoke-protected assembly seating shall not be less than the occupant load served ...
Section 1005 Means of Egress, Means of Egress Sizing
Facilities with outdoor smoke-protected assembly seating shall be permitted to the capacity factors in Section 1029.6.3 indicated for stepped aisles ...
Section 1005 Means of Egress, Means of Egress Sizing
Facilities with outdoor smoke-protected assembly seating shall be permitted to the capacity factors in Section 1029.6.3 indicated for stepped ...