3404.3.6 Wholesale and Retail Sales
JUMP TO FULL CODE CHAPTER
Flammable and combustible liquids in Group M occupancy wholesale and retail sales shall be in accordance with FC 3404.3.6.1 through 3404.3.6.5, or NFPA 30.
Containers for Class I liquids shall be metal.
Exception: In sprinklered buildings, an aggregate quantity of 120 gallons (454 L) of water-miscible Class IB and Class IC liquids is allowed in nonmetallic containers, each having a capacity of 16 ounces (0.473 L) or less.
Exception: In sprinklered buildings, an aggregate quantity of 120 gallons (454 L) of water-miscible Class IB and Class IC liquids is allowed in nonmetallic containers, each having a capacity of 16 ounces (0.473 L) or less.
Containers for Class I liquids shall not exceed a capacity of 5 gallons (19 L).
Exception: Metal containers not exceeding 55 gallons (208 L) are allowed to store up to 240 gallons (908 L) of the maximum allowable quantity per control area of Class IB and IC liquids in a control area. The building shall be protected throughout by a sprinkler system in accordance with FC Table 3404.3.4.1. The containers shall be provided with plastic caps without cap seals and shall be stored upright. Containers shall not be stacked or stored in racks and shall not be located in areas accessible to the public.
Exception: Metal containers not exceeding 55 gallons (208 L) are allowed to store up to 240 gallons (908 L) of the maximum allowable quantity per control area of Class IB and IC liquids in a control area. The building shall be protected throughout by a sprinkler system in accordance with FC Table 3404.3.4.1. The containers shall be provided with plastic caps without cap seals and shall be stored upright. Containers shall not be stacked or stored in racks and shall not be located in areas accessible to the public.
Related Code Sections
Reference Standard 9 Loads [PDF] (page 5)
……………………………………………………………………………………………….. Stores Wholesale sales………………………………………………………………………………………….. Retail sales Basement and first floor……………………………………………………………………………… Upper ...
414.2.5 Special Detailed Requirements Based on Use and Occupancy, Hazardous Material in Group M Display and Storage Areas and in Group S Storage Areas
) of this code. In Group M occupancy wholesale and retail sales uses, indoor storage of flammable and combustible liquids shall not exceed the maximum ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 414 Hazardous Materials > 414.2 Control Areas > 414.2.5 Hazardous Material in Group M Display and Storage Areas and in Group S Storage Areas
1607.9.1.3 Structural Design, Special Occupancies
Live loads of 100 psf(4.79 kN/m 2 ) or less shall not be reduced in public assembly occupancies or in areas used for retail or wholesale ...
NYC Building Code 2008 > 16 Structural Design > 1607 Live Loads > 1607.9 Reduction in Live Loads > 1607.9.1 General > 1607.9.1.3 Special Occupancies
1607.9.1.4 Structural Design, Special Occupancies
used for retail or wholesale sales ...
NYC Building Code 2014 > 16 Structural Design > 1607 Live Loads > 1607.9 Reduction in Live Loads > 1607.9.1 General > 1607.9.1.4 Special Occupancies
309.1 Use and Occupancy Classification, Mercantile Group M
facilities Retail or wholesale stores Sales rooms ...
NYC Building Code 2008 > 3 Use and Occupancy Classification > 309 Mercantile Goup M > 309.1 Mercantile Group M