M1505.4 Whole-House Mechanical Ventilation System
JUMP TO FULL CODE CHAPTER
(Equation 15-1)
Whole-house mechanical ventilation systems shall be designed in accordance with Sections M1505.4.1 through M1505.4.4.
The whole-house ventilation system shall consist of one or more supply or exhaust fans, or a combination of such, and associated ducts and controls. Local exhaust or supply fans are permitted to serve as such a system. Outdoor air ducts connected to the return side of an air handler shall be considered as providing supply ventilation.
The whole-house mechanical ventilation system shall be provided with controls that enable manual override.
The whole house mechanical ventilation system shall provide outdoor air at a continuous rate as determined in accordance with Table M1505.4.3(1) or Equation 15-1.

Exception: The whole-house mechanical ventilation system is permitted to operate intermittently where the system has controls that enable operation for not less than 25 percent of each 4-hour segment and the ventilation rate prescribed in Table M1505.4.3(1) is multiplied by the factor determined in accordance with Table M1505.4.3(2).
CONTINUOUS WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS
DWELLING UNIT FLOOR AREA (square feet) | NUMBER OF BEDROOMS | ||||
0 — 1 | 2 — 3 | 4 — 5 | 6 — 7 | > 7 | |
Airflow in CFM | |||||
< 1,500 | 30 | 45 | 60 | 75 | 90 |
1,501 — 3,000 | 45 | 60 | 75 | 90 | 105 |
3,001 — 4,500 | 60 | 75 | 90 | 105 | 120 |
4,501 — 6,000 | 75 | 90 | 105 | 120 | 135 |
6,001 — 7,500 | 90 | 105 | 120 | 135 | 150 |
> 7,500 | 105 | 120 | 135 | 150 | 165 |
For SI: 1 square foot = 0.0929 m2, 1 cubic foot per minute = 0.0004719 m3/s.
INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORSa, b
RUN-TIME PERCENTAGE IN EACH 4-HOUR SEGMENT | 25% | 33% | 50% | 66% | 75% | 100% |
Factora | 4 | 3 | 2 | 1.5 | 1.3 | 1.0 |
- For ventilation system run time values between those given, the factors are permitted to be determined by interpolation.
- Extrapolation beyond the table is prohibited.
Local exhaust systems shall be designed to have the capacity to exhaust the minimum airflow rate determined in accordance with Table M1505.4.4.
MINIMUM REQUIRED LOCAL EXHAUST RATES FOR ONE- AND TWO-FAMILY DWELLINGS
AREA TO BE EXHAUSTED | EXHAUST RATES |
Kitchens | 100 cfm intermittent or 25 cfm continuous |
Bathrooms-Toilet Rooms | Mechanical exhaust capacity of 50 cfm intermittent or 20 cfm continuous |
For SI: 1 cubic foot per minute = 0.0004719 m3/s.
Related Code Sections
M1505.4 Exhaust Systems, Whole-House Mechanical Ventilation System
Whole-house mechanical ventilation systems shall be designed in accordance with Sections M1505.4.1 through M1505.4.4 ...
Residential Code 2018 of Kansas > 15 Exhaust Systems > M1505 Mechanical Ventilation > M1505.4 Whole-House Mechanical Ventilation System
R403.6.1 [RE] Residential Energy Efficiency, Whole-House Mechanical Ventilation System Fan Efficacy
by an electronically commutated motor. TABLE R403.6.1 WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY a FAN LOCATION AIR FLOW RATE MINIMUM ...
Energy Conservation Code 2018 of Kansas > 4 [RE] Residential Energy Efficiency > R403 Systems > R403.6 Mechanical Ventilation (Mandatory) > R403.6.1 Whole-House Mechanical Ventilation System Fan Efficacy
N1103.6.1 [RE] Energy Efficiency, (R403.6.1) Whole-House Mechanical Ventilation System Fan Efficacy
by an electronically commutated motor.
TABLE N1103.6.1 (R403.6.1)
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY a FAN LOCATION ...
Residential Code 2018 of Kansas > 11 [RE] Energy Efficiency > N1103 (R403) Systems > N1103.6 (R403.6) Mechanical Ventilation (Mandatory) > N1103.6.1 (R403.6.1) Whole-House Mechanical Ventilation System Fan Efficacy
R403.6 [RE] Residential Energy Efficiency, Mechanical Ventilation (Mandatory)
by an electronically commutated motor. TABLE R403.6.1 WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY a FAN LOCATION AIR FLOW RATE ...
Energy Conservation Code 2018 of Kansas > 4 [RE] Residential Energy Efficiency > R403 Systems > R403.6 Mechanical Ventilation (Mandatory)
N1103.6 [RE] Energy Efficiency, (R403.6) Mechanical Ventilation (Mandatory)
)
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY a FAN LOCATION AIR FLOW RATE MINIMUM (CFM) MINIMUM EFFICACY (CFM/WATT) AIR ...
Residential Code 2018 of Kansas > 11 [RE] Energy Efficiency > N1103 (R403) Systems > N1103.6 (R403.6) Mechanical Ventilation (Mandatory)