Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

M1505.4 Whole-House Mechanical Ventilation System

Residential Code 2018 of Kansas > 15 Exhaust Systems > M1505 Mechanical Ventilation > M1505.4 Whole-House Mechanical Ventilation System
JUMP TO FULL CODE CHAPTER
Whole-house mechanical ventilation systems shall be designed in accordance with Sections M1505.4.1 through M1505.4.4.

M1505.4.1 System Design

The whole-house ventilation system shall consist of one or more supply or exhaust fans, or a combination of such, and associated ducts and controls. Local exhaust or supply fans are permitted to serve as such a system. Outdoor air ducts connected to the return side of an air handler shall be considered as providing supply ventilation.

M1505.4.2 System Controls

The whole-house mechanical ventilation system shall be provided with controls that enable manual override.

M1505.4.3 Mechanical Ventilation Rate

The whole house mechanical ventilation system shall provide outdoor air at a continuous rate as determined in accordance with Table M1505.4.3(1) or Equation 15-1.
(Equation 15-1)
Exception: The whole-house mechanical ventilation system is permitted to operate intermittently where the system has controls that enable operation for not less than 25 percent of each 4-hour segment and the ventilation rate prescribed in Table M1505.4.3(1) is multiplied by the factor determined in accordance with Table M1505.4.3(2).
TABLE M1505.4.3(1)
CONTINUOUS WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS
DWELLING UNIT
FLOOR AREA
(square feet)
NUMBER OF BEDROOMS
0 — 12 — 34 — 56 — 7> 7
Airflow in CFM
< 1,5003045607590
1,501 — 3,00045607590105
3,001 — 4,500607590105120
4,501 — 6,0007590105120135
6,001 — 7,50090105120135150
> 7,500105120135150165
For SI: 1 square foot = 0.0929 m2, 1 cubic foot per minute = 0.0004719 m3/s.
TABLE M1505.4.3(2)
INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORSa, b
RUN-TIME PERCENTAGE IN EACH 4-HOUR
SEGMENT
25%33%50%66%75%100%
Factora4321.51.31.0
  1. For ventilation system run time values between those given, the factors are permitted to be determined by interpolation.
  2. Extrapolation beyond the table is prohibited.

M1505.4.4 Local Exhaust Rates

Local exhaust systems shall be designed to have the capacity to exhaust the minimum airflow rate determined in accordance with Table M1505.4.4.
TABLE M1505.4.4
MINIMUM REQUIRED LOCAL EXHAUST RATES FOR ONE- AND TWO-FAMILY DWELLINGS
AREA TO BE
EXHAUSTED
EXHAUST RATES
Kitchens100 cfm intermittent or 25 cfm continuous
Bathrooms-Toilet
Rooms
Mechanical exhaust capacity of 50 cfm
intermittent or 20 cfm continuous
For SI: 1 cubic foot per minute = 0.0004719 m3/s.

Related Code Sections


M1505.4 Exhaust Systems, Whole-House Mechanical Ventilation System
Whole-house mechanical ventilation systems shall be designed in accordance with Sections M1505.4.1 through M1505.4.4 ...
Residential Code 2018 of Kansas > 15 Exhaust Systems > M1505 Mechanical Ventilation > M1505.4 Whole-House Mechanical Ventilation System
R403.6.1 [RE] Residential Energy Efficiency, Whole-House Mechanical Ventilation System Fan Efficacy
by an electronically commutated motor. TABLE R403.6.1 WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY a FAN LOCATION AIR FLOW RATE MINIMUM ...
Energy Conservation Code 2018 of Kansas > 4 [RE] Residential Energy Efficiency > R403 Systems > R403.6 Mechanical Ventilation (Mandatory) > R403.6.1 Whole-House Mechanical Ventilation System Fan Efficacy
N1103.6.1 [RE] Energy Efficiency, (R403.6.1) Whole-House Mechanical Ventilation System Fan Efficacy
by an electronically commutated motor. TABLE N1103.6.1 (R403.6.1) WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY a FAN LOCATION ...
Residential Code 2018 of Kansas > 11 [RE] Energy Efficiency > N1103 (R403) Systems > N1103.6 (R403.6) Mechanical Ventilation (Mandatory) > N1103.6.1 (R403.6.1) Whole-House Mechanical Ventilation System Fan Efficacy
R403.6 [RE] Residential Energy Efficiency, Mechanical Ventilation (Mandatory)
by an electronically commutated motor. TABLE R403.6.1 WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY a FAN LOCATION AIR FLOW RATE ...
Energy Conservation Code 2018 of Kansas > 4 [RE] Residential Energy Efficiency > R403 Systems > R403.6 Mechanical Ventilation (Mandatory)
N1103.6 [RE] Energy Efficiency, (R403.6) Mechanical Ventilation (Mandatory)
) WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY a FAN LOCATION AIR FLOW RATE MINIMUM (CFM) MINIMUM EFFICACY (CFM/WATT) AIR ...
Residential Code 2018 of Kansas > 11 [RE] Energy Efficiency > N1103 (R403) Systems > N1103.6 (R403.6) Mechanical Ventilation (Mandatory)
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING