11B-802 Wheelchair Spaces, Companion Seats, and Designated Aisle Seats and Semi-Ambulant Seats
The floor or ground surface of wheelchair spaces shall comply with Section 11B-302. Changes in level are not permitted.
Exception: Slopes not steeper than 1:48 shall be permitted.
A single wheelchair space shall be 36 inches (914 mm) wide minimum. Where two adjacent wheel-chair spaces are provided, each wheelchair space shall be 33 inches (838 mm) wide minimum.
FIGURE 11B-802.1.2
WIDTH OF WHEELCHAIR SPACES
Where a wheelchair space can be entered from the front or rear, the wheelchair space shall be 48 inches (1219 mm) deep minimum. Where a wheel-chair space can be entered only from the side, the wheel-chair space shall be 60 inches (1524 mm) deep minimum.
FIGURE 11B-802.1.3
DEPTH OF WHEELCHAIR SPACES
Where spectators are provided lines of sight over the heads of spectators seated in the first row in front of their seats, spectators seated in wheelchair spaces shall be afforded lines of sight over the heads of seated spectators in the first row in front of wheelchair spaces.
FIGURE 11B-802.2.1.1
LINES OF SIGHT OVER THE HEADS OF SEATED SPECTATORS
Where spectators are provided lines of sight over the shoulders and between the heads of spectators seated in the first row in front of their seats, spectators seated in wheel-chair spaces shall be afforded lines of sight over the shoulders and between the heads of seated spectators in the first row in front of wheelchair spaces.
FIGURE 11B-802.2.1.2
LINES OF SIGHT BETWEEN THE HEADS OF SEATED SPECTATORS
Where standing spectators are provided lines of sight over the heads of spectators standing in the first row in front of their seats, spectators seated in wheelchair spaces shall be afforded lines of sight over the heads of standing spectators in the first row in front of wheelchair spaces.
FIGURE 11B-802.2.2.1
LINES OF SIGHT OVER THE HEADS OF STANDING SPECTATORS
Where standing spectators are provided lines of sight over the shoulders and between the heads of spectators standing in the first row in front of their seats, spectators seated in wheelchair spaces shall be afforded lines of sight over the shoulders and between the heads of standing spectators in the first row in front of wheelchair spaces.
FIGURE 11B-802.2.2.2
LINES OF SIGHT BETWEEN THE HEADS OF STANDING SPECTATORS