1926.353(b) Welding, Cutting, and Heating in Confined Spaces
JUMP TO FULL CODE CHAPTER
Except as provided in paragraph (b)(2) of this section, and paragraph (c)(2) of this section, either general mechanical or local exhaust ventilation meeting the requirements of paragraph (a) of this section shall be provided whenever welding, cutting, or heating is performed in a confined space.
When sufficient ventilation cannot be obtained without blocking the means of access, employees in the confined space shall be protected by air line respirators in accordance with the requirements of Subpart E of this part, and an employee on the outside of such a confined space shall be assigned to maintain communication with those working within it and to aid them in an emergency.
Where a welder must enter a confined space through a manhole or other small opening, means shall be provided for quickly removing him in case of emergency. When safety belts and lifelines are used for this purpose they shall be so attached to the welder's body that his body cannot be jammed in a small exit opening. An attendant with a pre-planned rescue procedure shall be stationed outside to observe the welder at all times and be capable of putting rescue operations into effect.
Related Code Sections
1926.353(b) Welding and Cutting, Welding, Cutting, and Heating in Confined Spaces
meeting the requirements of paragraph (a) of this section shall be provided whenever welding, cutting, or heating is performed in a confined space ...
OSHA 1926 Construction > J Welding and Cutting > 1926.353 Ventilation and Protection in Welding, Cutting, and Heating > 1926.353(b) Welding, Cutting, and Heating in Confined Spaces
1926.352 Welding and Cutting, Fire Prevention
When practical, objects to be welded, cut, or heated shall be moved to a designated safe location or, if the objects to be welded, cut, or heated ...
1926.350(b) Welding and Cutting, Placing Cylinders
Cylinders shall be kept far enough away from the actual welding or cutting operation so that sparks, hot slag, or flame will not reach them. When ...
OSHA 1926 Construction > J Welding and Cutting > 1926.350 Gas Welding and Cutting > 1926.350(b) Placing Cylinders
1926.352(b) Welding and Cutting,
If the object to be welded, cut, or heated cannot be moved and if all the fire hazards cannot be removed, positive means shall be taken to confine ...
1926.352(g) Welding and Cutting,
be removed from the confined space. Open end fuel gas and oxygen hoses shall be immediately removed from enclosed spaces when they are disconnected from ...