2104.1.8 Weep Holes
Related Code Sections
2104.1.8 Masonry, Weep Holes
Weep holes shall be provided in the exterior wythe of masonry walls and shall be at a maximum spacing of 33 inches (838 mm) on center (o.c.). Weep ...
1405.4.2 Exterior Walls, Masonry
Flashing and weep holes in anchored veneer shall be located in the first course of masonry above finished ground level above the foundation wall ...
Appendix A Selected Rules of the Department of Buildings [PDF] (page 105)
the flashing, weep-holes and air circulation have been designed for water defense to prevent uncontrolled water infiltration. (iv)The prevention of electro ...
2512.1.2 Gypsum Board, Gypsum Panel Products and Plaster, Weep Screeds
A minimum 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage), corrosion-resistant weep screed with a minimum vertical attachment flange of 31/2 ...
2512.1.2 Gypsum Board and Plaster, Weep Screeds