605.3 Water Service Pipe
JUMP TO FULL CODE CHAPTER
Water service pipe shall conform to NSF 61 and shall conform to one of the standards listed in Table 605.3. Water service pipe or tubing, installed underground and outside of the structure, shall have a working pressure rating of not less than 160 psi (1100 kPa) at 73.4°F (23°C). Where the water pressure exceeds 160 psi (1100 kPa), piping material shall have a working pressure rating not less than the highest available pressure. Water service piping materials not third-party certified for water distribution shall terminate at or before the full open valve located at the entrance to the structure. Ductile iron water service piping shall be cement mortar lined in accordance with AWWA C104.
MATERIAL | STANDARD |
Acrylonitrile butadiene styrene (ABS) plastic pipe | ASTM D 1527; ASTM D 2282 |
Brass pipe | ASTM B 43 |
Chlorinated polyvinyl chloride (CPVC) plastic pipe | ASTM D 2846; ASTM F 441; ASTM F 442; CSA B137.6 |
Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride (CPVC/AL/CPVC) |
ASTM F 2855 |
Copper or copper-alloy pipe | ASTM B 42; ASTM B 302 |
Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM) | ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447 |
Cross-linked polyethylene (PEX) plastic pipe and tubing | ASTM F 876; ASTM F 877; AWWA C904; CSA B137.5 |
Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL- PEX) pipe | ASTM F 1281; ASTM F 2262; CSA B137.10 |
Cross-linked polyethylene/aluminum/high-density polyethylene (PEX-AL-HDPE) |
ASTM F 1986 |
Ductile iron water pipe | AWWA C151/A21.51; AWWA C115/A21.15 |
Galvanized steel pipe | ASTM A 53 |
Polyethylene (PE) plastic pipe | ASTM D 2239; ASTM D 3035; AWWA C901; CSA B137.11 |
Polyethylene (PE) plastic tubing | ASTM D 2737; AWWA C901; CSA B137.1 |
Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe | ASTM F 1282; CSA B137.9 |
Polyethylene of raised temperature (PE-RT) plastic tubing | ASTM F 2769 |
Polypropylene (PP) plastic pipe or tubing | ASTM F 2389; CSA B137.11 |
Polyvinyl chloride (PVC) plastic pipe | ASTM D 1785; ASTM D 2241; ASTM D 2672; CSA B137.3 |
Stainless steel pipe (Type 304/304L) | ASTM A 312; ASTM A 778 |
Stainless steel pipe (Type 316/316L) | ASTM A 312; ASTM A 778 |
Dual check-valve backflow preventers installed on the water supply system shall comply with ASSE 1024 or CSA B64.6.
Related Code Sections
605.3 Water and Supply Distribution, Water Service Pipe
Water service pipe shall conform to NSF 61 and shall conform to one of the standards listed in Table 605.3. All water service pipe or tubing ...
2010 Plumbing Code of NY > 6 Water and Supply Distribution > 605 Materials, Joints and Connections > 605.3 Water Service Pipe
605.3 Water Supply and Distribution, Water Service Pipe
Water service pipe shall conform to NSF 61 and shall conform to one of the standards listed in Table 605.3. Water service pipe or tubing, installed ...
2020 Plumbing Code of NYS > 6 Water Supply and Distribution > 605 Materials, Joints and Connections > 605.3 Water Service Pipe
605.3 Water Supply and Distribution, Water Service Pipe
Water service pipe shall conform to NSF 61 and shall conform to one of the standards listed in Table 605.3. Water service pipe or tubing, installed ...
Plumbing Code 2015 of New York State > 6 Water Supply and Distribution > 605 Materials, Joints and Connections > 605.3 Water Service Pipe
608.4 Water Supply and Distribution, Water Service Piping
Water service piping shall be protected in accordance with Sections 603.2 and 603.2.1 ...
Plumbing Code 2015 of New York State > 6 Water Supply and Distribution > 608 Protection of Potable Water Supply > 608.4 Water Service Piping
608.4 Water and Supply Distribution, Water Service Piping
Water service piping shall be protected in accordance with Sections 603.2 and 603.2.1 ...
2010 Plumbing Code of NY > 6 Water and Supply Distribution > 608 Protection of Potable Water Supply > 608.4 Water Service Piping