604.13 Water Heater Connectors
JUMP TO FULL CODE CHAPTER
Flexible metallic
(copper and stainless steel), reinforced flexible, braided
stainless steel, or polymer braided with EPDM core connectors
that connect a water heater to the piping system shall
be in accordance with ASME A112.18.6/CSA B125.6.
Copper, copper alloy, or stainless steel flexible connectors
shall not exceed 24 inches (610 mm). PEX, PEX-AL-PEX,
PE-AL-PE, or PE-RT tubing shall not be installed within
the first 18 inches (4S7 mm) of piping connected to a water
heater.
[BSC, HCD 1 & HCD 2] PEX-AL-PEX is not adopted for use in potable water supply and distribution systems.
[BSC, HCD 1 & HCD 2] PEX-AL-PEX is not adopted for use in potable water supply and distribution systems.
Related Code Sections
604.13 Water Supply and Distribution, Water Heater Connectors
that connect a water heater to the piping system shall
be in accordance with ASME A112.18.6/CSA B125.6.
Copper, copper alloy, or stainless steel flexible ...
California Plumbing Code 2016 > 6 Water Supply and Distribution > 604.0 Materials > 604.13 Water Heater Connectors
604.13 Water Supply and Distribution, Water Heater Connectors
that
connect a water heater to the piping system shall comply with
ASME A 112.18.6/CSA B 125.6. Copper, copper alloy, or
stainless steel flexible connectors ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 604.0 Materials > 604.13 Water Heater Connectors
509.10.2 Water Heaters, Size of Vent Connector
A vent connector
for an appliance with a single draft hood or for a Category
I fan-assisted combustion system appliance shall be
sized and installed ...
California Plumbing Code 2019 > 5 Water Heaters > 509.0 Venting of Appliances > 509.10 Vent Connectors for Category I Appliances > 509.10.2 Size of Vent Connector
509.10.2 Water Heaters, Size of Vent Connector
A vent connector for an
appliance with a single draft hood or for a Category I fan-assisted
combustion system appliance shall be sized and
installed ...
California Plumbing Code 2016 > 5 Water Heaters > 509.0 Venting of Appliances > 509.10 Vent Connectors for Category I Appliances > 509.10.2 Size of Vent Connector
509.10.1 Water Heaters, Materials
A vent connector shall be made of
noncombustible, corrosion-resistant material capable of
withstanding the vent gas temperature produced ...
California Plumbing Code 2019 > 5 Water Heaters > 509.0 Venting of Appliances > 509.10 Vent Connectors for Category I Appliances > 509.10.1 Materials