Section P2706 Waste Receptors
JUMP TO FULL CODE CHAPTER
For other than hub drains that receive only clear-water waste and standpipes, a removable strainer or basket shall cover the waste outlet of waste receptors. Waste receptors shall not be installed in concealed spaces. Waste receptors shall not be installed in plenums, attics, crawl spaces or interstitial spaces above ceilings and below floors. Waste receptors shall be readily accessible.
Hub drains shall be in the form of a hub or a pipe that extends not less than 1 inch (25.4 mm) above a water-impervious floor.
Standpipes shall extend not less than 18 inches (457 mm) and not greater than 42 inches (1067 mm) above the trap weir.
Where a laundry tray waste line connects into a standpipe for an automatic clothes washer drain, the standpipe shall extend not less than 30 inches (762 mm) above the standpipe trap weir and shall extend above the flood level rim of the laundry tray. The outlet of the laundry tray shall not be greater than 30 inches (762 mm) horizontally from the standpipe trap.
Related Code Sections
802.4 Indirect/Special Waste, Waste Receptors
receptors. Waste receptors shall not be installed in concealed spaces. Waste receptors shall not be installed in plenums, crawl spaces, attics, interstitial ...
Plumbing Code 2018 of Colorado > 8 Indirect/Special Waste > 802 Indirect Wastes > 802.4 Waste Receptors
Section P2706 Plumbing Fixtures, Waste Receptors
receptors. Waste receptors shall not be installed in concealed spaces. Waste receptors shall not be installed in plenums, attics, crawl spaces ...
Section P2706 Plumbing Fixtures, Waste Receptors
receptors. Waste receptors shall not be installed in concealed spaces. Waste receptors shall not be installed in plenums, attics, crawl spaces ...
709.4 Sanitary Drainage, Values for Indirect Waste Receptor
The drainage fixture unit load of an indirect waste receptor receiving the discharge of indirectly connected fixtures shall be the sum ...
Plumbing Code 2018 of Colorado > 7 Sanitary Drainage > 709 Fixture Units > 709.4 Values for Indirect Waste Receptor