811.2 Waste and Vent Pipes
Go To Full Code Chapter
Each waste pipe receiving or intended to receive the discharge of a fixture into which acid or corrosive chemical is placed, and each vent pipe connected thereto, shall be constructed of chlorinated polyvinyl chloride (CPVC), polypropylene (PP), polyvinylidene fluoride (PVDF), chemical-resistant glass, high-silicon iron pipe, or lead pipe with a wall thickness of not less than 1/8 of an inch (3.2 mm); an approved type of ceramic glazed or unglazed vitrified clay; or other approved corrosion-resistant materials. CPVC pipe and fittings shall comply with ASTM F2618. PP pipe and fittings shall comply with ASTM F1412 or CSA B181.3. PVDF pipe and fittings shall comply with ASTM F1673 or CSA B181.3. Chemical-resistant glass pipe and fittings shall comply with ASTM C1053. High-silicon iron pipe and fittings shall comply with ASTM A861.
Upcodes Diagrams
Related Code Sections
811.2 Indirect Wastes, Waste and Vent Pipes
Each waste pipe receiving or intended to receive the discharge of a fixture into which acid or corrosive chemical is placed, and each vent pipe ...
Section P3111 Vents, Combination Waste and Vent System
shall be considered to be the vent for those fixtures. The developed length of a fixture drain to the combination waste and vent system piping shall ...
P2911.12.1 Water Supply and Distribution, Collection Pipe and Vent Test
Drain, waste and vent piping used for on-site water reuse systems shall be tested in accordance with Section P2503 ...
P2912.15.3 Water Supply and Distribution, Collection Pipe and Vent Test
Drain, waste and vent piping used for rainwater collection and conveyance systems shall be tested in accordance with Section P2503 ...
1101.16 Storm Drainage, Leaders, Conductors, and Connections
Leaders or conductors shall not be used as soil, waste, or vent pipes nor shall soil, waste, or vent pipes be used as leaders or conductors ...