(B) Warning Sign for Multiple Disconnecting Means
Go To Full Code Chapter
Where multiple disconnecting means are used and parts of the controllers remain energized from a source other than the one disconnected, a warning sign shall be mounted on or next to the disconnecting means. The sign shall be clearly legible and shall read as follows:
The warning sign(s) or label(s) shall comply with 110.21(B).