// CODE SNIPPET
3109.4.2 Walls Below the 100-Year Storm Elevation
JUMP TO FULL CODE CHAPTER
No substantial walls or partitions shall be constructed below the level of the first finished floor of habitable structures. All other walls shall be designed to break away.
Exceptions:
- Stairways and stairwells;
- Shear walls perpendicular to the shoreline;
- Shear walls parallel to the shoreline, which are limited to a maximum of 20 percent of the building length in the direction running parallel to the shore;
- Shear walls parallel to the shoreline, which exceed 20 percent of the total building length (including any attached major structure) when they meet the following criteria:
- A certification is provided by a Florida-registered professional engineer that certifies that the increased length of shear walls, over 20 percent, are located landward of the 100-year erosion limit;
- A hydraulic analysis is provided and certified by a Florida-registered professional engineer that evaluates the potential impact of flow increase on the subject parcel and adjacent properties;
- The hydraulic analysis demonstrates that although the overall shearwall coverage is more than 20 percent, the increased shearwall length will not result in substantial increase of flow velocities and drag forces on the structural components of the proposed structure and neighboring structures; and
- The provisions under Section 3109.4.2 (Exception 4) do not include any low-rise building as defined in Section 1609.2.
- Wind or sand screens constructed of fiber or wire mesh;
- Light, open lattice partitions with individual, wooden lattice strips not greater than 3/4-inch (19 mm) thick and 3-inches (76 mm) wide;
- Elevator shafts;
- Small mechanical and electrical rooms; and
- Break-away or frangible walls.
Related Code Sections
3109.4.2 Special Construction, Walls Below the 100-Year Storm Elevation
No substantial walls or partitions shall be constructed below the level of the first finished floor of habitable structures. All other walls shall ...
2014 FBC - Building, 5th edition > 31 Special Construction > 3109 Structures Seaward of a Coastal Construction Control Line > 3109.4 Construction Standards > 3109.4.2 Walls Below the 100-Year Storm Elevation
3109.3 Special Construction, Design and Construction
Structural slabs below the 100-year storm elevation and below the lowest floor are not required ...
2017 FBC - Building, 6th edition > 31 Special Construction > 3109 Structures Seaward of a Coastal Construction Control Line > 3109.3 Design and Construction
3109.3 Special Construction, Design and Construction
Structural slabs below the 100-year storm elevation and below the lowest floor are not required ...
2020 FBC - Building, 7th edition > 31 Special Construction > 3109 Structures Seaward of a Coastal Construction Control Line > 3109.3 Design and Construction
3109.2 Special Construction, Definitions
of Section 3109.3.4, use of enclosures above, or with dry floodproofing to, the elevation specified in ASCE 24 and below the 100-year storm elevation ...
2020 FBC - Building, 7th edition > 31 Special Construction > 3109 Structures Seaward of a Coastal Construction Control Line > 3109.2 Definitions
Section 3109 Special Construction, Structures Seaward of a Coastal Construction Control Line
-parallel structural member which supports floor, wall or column loads and transmits them to the pile foundation. ONE-HUNDRED-YEAR STORM ELEVATION. The ...
2014 FBC - Building, 5th edition > 31 Special Construction > 3109 Structures Seaward of a Coastal Construction Control Line