// CODE SNIPPET
18.5* Visible Characteristics — Public Mode
Go To Full Code Chapter
18.5.1* Visible Signaling
18.5.1.1
Public mode visible signaling shall meet the requirements of Section 18.5 using visible notification appliances.
18.5.1.2*
The coverage area for visible occupant notification shall be as required by other governing laws, codes, or standards. Where the other governing laws, codes, or standards require visible occupant notification for all or part of an area or space, coverage shall only be required in occupiable areas as defined in 3.3.177.
18.5.2 Area of Coverage
18.5.2.1
The designer of the visible notification system shall document the rooms and spaces that will have visible notification and those where visible notification will not be provided.
18.5.2.2*
Unless otherwise specified or required by other sections of this Code, the required coverage area for visible occupant notification shall be as required by other governing laws, codes, or standards.
18.5.2.3
Where required by the authority having jurisdiction, documentation of the effective intensity (cd) of the visible appliances for the area of coverage shall be submitted for review and approval.
18.5.3 Light, Color, and Pulse Characteristics
18.5.3.1
The flash rate shall not exceed two flashes per second (2 Hz) nor be less than one flash every second (1 Hz) throughout the listed voltage range of the appliance.
18.5.3.2*
18.5.3.3
The pulse duration shall be defined as the time interval between initial and final points of 10 percent of maximum signal.
18.5.3.4*
Lights used for fire alarm signaling only or to signal the intent for complete evacuation shall be clear or nominal white and shall not exceed 1000 cd (effective intensity).
18.5.3.5
Lights used to signal occupants to seek information or instructions shall be clear, nominal white, or other color as required by the emergency plan and the authority having jurisdiction for the area or building.
18.5.3.6*
The strobe synchronization requirements of this chapter shall not apply where the visible notification appliances located inside the building are viewed from outside of the building.
18.5.4* Appliance Photometrics
The light output shall comply with the polar dispersion requirements of ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, or equivalent.
18.5.5 Appliance Location
18.5.5.1*
Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 in. (2.03 m) and not greater than 96 in. (2.44 m) above the finished floor or at the mounting height specified using the performance-based alternative of 18.5.5.6.
18.5.5.2
Where low ceiling heights do not permit wall mounting at a minimum of 80 in. (2.03 m), wall mounted visible appliances shall be mounted within 6 in. (150 mm) of the ceiling. The room size covered by a strobe of a given value shall be reduced by twice the difference between the minimum mounting height of 80 in. (2.03 m) and the actual lower mounting height.
18.5.5.3*
18.5.5.4* Spacing in Rooms
18.5.5.4.1
Spacing shall be in accordance with either Table 18.5.5.4.1(a) and Figure 18.5.5.4.1 or Table 18.5.5.4.1(b).
Table 18.5.5.4.1(a) Room Spacing for Wall-Mounted Visible Appliances
Maximum Room Size | Minimum Required Light Output [Effective Intensity (cd)] | |||
---|---|---|---|---|
ft | m | One Light per Room | Four Lights per Room (One Light per Wall) | |
20 × 20 | 6.10 × 6.10 | 15 | NA | |
28 × 28 | 8.53 × 8.53 | 30 | NA | |
30 × 30 | 9.14 × 9.14 | 34 | NA | |
40 × 40 | 12.2 × 12.2 | 60 | 15 | |
45 × 45 | 13.7 × 13.7 | 75 | 19 | |
50 × 50 | 15.2 × 15.2 | 94 | 30 | |
54 × 54 | 16.5 × 16.5 | 110 | 30 | |
55 × 55 | 16.8 × 16.8 | 115 | 30 | |
60 × 60 | 18.3 × 18.3 | 135 | 30 | |
63 × 63 | 19.2 × 19.2 | 150 | 37 | |
68 × 68 | 20.7 × 20.7 | 177 | 43 | |
70 × 70 | 21.3 × 21.3 | 184 | 60 | |
80 × 80 | 24.4 × 24.4 | 240 | 60 | |
90 × 90 | 27.4 × 27.4 | 304 | 95 | |
100 × 100 | 30.5 × 30.5 | 375 | 95 | |
110 × 110 | 33.5 × 33.5 | 455 | 135 | |
120 × 120 | 36.6 × 36.6 | 540 | 135 | |
130 × 130 | 39.6 × 39.6 | 635 | 185 | |
NA: Not allowable. |
Maximum Room Size | Maximum Lens Height* | Minimum Required Light Output (Effective Intensity); One Light (cd) | |||
---|---|---|---|---|---|
ft | m | ft | m | ||
20 × 20 | 6.1 × 6.1 | 10 | 3.0 | 15 | |
30 × 30 | 9.1 × 9.1 | 10 | 3.0 | 30 | |
40 × 40 | 12.2 × 12.2 | 10 | 3.0 | 60 | |
44 × 44 | 13.4 × 13.4 | 10 | 3.0 | 75 | |
20 × 20 | 6.1 × 6.1 | 20 | 6.1 | 30 | |
30 × 30 | 9.1 × 9.1 | 20 | 6.1 | 45 | |
44 × 44 | 13.4 × 13.4 | 20 | 6.1 | 75 | |
46 × 46 | 14.0 × 14.0 | 20 | 6.1 | 80 | |
20 × 20 | 6.1 × 6.1 | 30 | 9.1 | 55 | |
30 × 30 | 9.1 × 9.1 | 30 | 9.1 | 75 | |
50 × 50 | 15.2 × 15.2 | 30 | 9.1 | 95 | |
53 × 53 | 16.2 × 16.2 | 30 | 9.1 | 110 | |
55 × 55 | 16.8 × 16.8 | 30 | 9.1 | 115 | |
59 × 59 | 18.0 × 18.0 | 30 | 9.1 | 135 | |
63 × 63 | 19.2 × 19.2 | 30 | 9.1 | 150 | |
68 × 68 | 20.7 × 20.7 | 30 | 9.1 | 177 | |
70 × 70 | 21.3 × 21.3 | 30 | 9.1 | 185 | |
*This does not preclude mounting lens at lower heights. |

FIGURE 18.5.5.4.1 Room Spacing for Wall-Mounted Visible Appliances.
18.5.5.4.2
Visible notification appliances shall be installed in accordance with Table 18.5.5.4.1(a) or Table 18.5.5.4.1(b) using one of the following:
- A single visible notification appliance.
- *Two groups of visible notification appliances, where visual appliances of each group are synchronized, in the same room or adjacent space within the field of view. This shall include synchronization of strobes operated by separate systems.
- More than two visible notification appliances or groups of synchronized appliances in the same room or adjacent space within the field of view that flash in synchronization.
18.5.5.4.3
Room spacing in accordance with Table 18.5.5.4.1(a) and Figure 18.5.5.4.1 for wall-mounted appliances shall be based on locating the visible notification appliance at the halfway distance of the wall.
18.5.5.4.4
In square rooms with appliances not centered or in nonsquare rooms, the effective intensity (cd) from one visible wall-mounted notification appliance shall be determined by maximum room size dimensions obtained either by measuring the distance to the farthest wall or by doubling the distance to the farthest adjacent wall, whichever is greater, as required by Table 18.5.5.4.1(a) and Figure 18.5.5.4.1.
18.5.5.4.5
If a room configuration is not square, the square room size that allows the entire room to be encompassed or allows the room to be subdivided into multiple squares shall be used.
18.5.5.4.6*
If ceiling heights exceed 30 ft (9.14 m), ceiling-mounted visible notification appliances shall be suspended at or below 30 ft (9.14 m) or at the mounting height determined using the performance-based alternative of 18.5.5.6, or wall-mounted visible notification appliances shall be installed in accordance with Table 18.5.5.4.1(a).
18.5.5.4.7
Table 18.5.5.4.1(b) shall be used if the ceiling-mounted visible notification appliance is at the center of the room. If the ceiling-mounted visible notification appliance is not located at the center of the room, the effective intensity (cd) shall be determined by doubling the distance from the appliance to the farthest wall to obtain the maximum room size.
18.5.5.5* Spacing in Corridors
18.5.5.5.1
The installation of visible notification appliances in corridors 20 ft (6.1 m) or less in width shall be in accordance with the requirements of either 18.5.5.4 or 18.5.5.5.
18.5.5.5.2
Paragraph 18.5.5.5 shall apply to corridors not exceeding 20 ft (6.1 m) in width.
18.5.5.5.3
In a corridor application, visible appliances shall be rated not less than 15 cd.
18.5.5.5.4
18.5.5.5.5*
Visible notification appliances shall be located not more than 15 ft (4.57 m) from the end of the corridor with a separation not greater than 100 ft (30.5 m) between appliances.
18.5.5.5.6
If there is an interruption of the concentrated viewing path, such as a fire door, an elevation change, or any other obstruction, the area shall be treated as a separate corridor.
18.5.5.5.7
In corridors where more than two visible notification appliances are in any field of view, they shall flash in synchronization.
18.5.5.5.8
Wall-mounted visible notification appliances in corridors shall be permitted to be mounted on either the end wall or the side wall of the corridor in accordance with spacing requirements of 18.5.5.5.5.
18.5.5.6* Performance-Based Alternative
18.5.5.6.1
Any design that provides a minimum of 0.0375 lumens/ft2 (0.4036 lumens/m2) of illumination at any point within the covered area at all angles specified by the polar dispersion planes for wall- or ceiling-mounted visual appliances in ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, or equivalent, as calculated for the maximum distance from the nearest visual notification appliance, shall be permitted in lieu of the requirements of 18.5.5, excluding 18.5.5.7.
18.5.5.6.2
Documentation provided to the authority having jurisdiction shall include the following:
- Inverse Square Law calculations using each of the vertical and horizontal polar distribution angles in ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, or equivalent.
- The calculations shall account for the effects of polar distribution using one of the following:
- The percentages from the applicable table(s) in ANSI/UL 1971, Standard for Signaling Devices for the Hearing Impaired, or equivalent
- The actual results of laboratory tests of the specific appliance to be used as recorded by the listing organization
18.5.5.7 Sleeping Areas
18.5.5.7.1
Combination smoke detectors and visible notification appliances or combination smoke alarms and visible notification appliances shall be installed in accordance with the applicable requirements of Chapters 17, 18, and 29.
18.5.5.7.2*
Table 18.5.5.7.2 shall apply to sleeping areas.
Table 18.5.5.7.2 Effective Intensity Requirements for Sleeping Area Visible Notification Appliances
Distance from Ceiling to Top of Lens | Minimum Intensity (cd) | |
---|---|---|
in. | mm | |
≥24 | ≥610 | 110 |
<24 | <610 | 177 |
18.5.5.7.3
For rooms with a linear dimension greater than 16 ft (4.87 m), the visible notification appliance shall be located within 16 ft (4.87 m) of the pillow.
18.5.6 Location of Visible Notification Appliances for Wide Area Signaling
Visible notification appliances for wide area signaling shall be installed in accordance with the requirements of the authority having jurisdiction, approved design documents, and the manufacturer's instructions to achieve the required performance.
Related Code Sections
18.5* Notification Appliances, Visible Characteristics — Public Mode
Public mode visible signaling shall meet the requirements of Section 18.5 using visible notification appliances ...
18.5.6 Notification Appliances, Location of Visible Notification Appliances for Wide Area Signaling
Visible notification appliances for wide area signaling shall be installed in accordance with the requirements of the authority having jurisdiction ...
18.5.1.1 Notification Appliances,
Public mode visible signaling shall meet the requirements of Section 18.5 using visible notification appliances ...
18.5.1.2* Notification Appliances,
The coverage area for visible occupant notification shall be as required by other governing laws, codes, or standards. Where the other governing laws ...
18.5.2.1 Notification Appliances,
The designer of the visible notification system shall document the rooms and spaces that will have visible notification and those where visible ...