603.18 Vibration Isolation Connectors
JUMP TO FULL CODE CHAPTER
Vibration isolation connectors in duct systems shall be made of an approved flame-retardant fabric or shall consist of sleeve joints with packing of approved material, each having a maximum flame spread index/rating of 25 and a maximum smoke developed rating of 50. The fabric shall have a maximum length of 10 inches (254 mm) in the direction of air flow.
Related Code Sections
603.18 Duct Systems, Vibration Isolation Connectors
Vibration isolation connectors in duct systems shall be made of an approved flame-retardant fabric or shall consist of sleeve joints with packing ...
NYC Mechanical Code 2008 > 6 Duct Systems > 603 Duct Construction and Installation > 603.18 Vibration Isolation Connectors
603.18 Duct Systems, Vibration Isolation Connectors
Vibration isolation connectors in duct systems shall be made of an approved flame-retardant fabric or shall consist of sleeve joints with packing ...
NYC Mechanical Code 2014 > 6 Duct Systems > 603 Duct Construction and Installation > 603.18 Vibration Isolation Connectors
506.3.2.4 Exhaust Systems, Vibration Isolation
A vibration isolation connector for connecting a duct to a fan shall consist of noncombustible packing in a metal sleeve joint of approved design ...
NYC Mechanical Code 2008 > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.2 Joints, Seams and Penetrations of Grease Ducts > 506.3.2.4 Vibration Isolation
506.3.2.4 Exhaust Systems, Vibration Isolation
A vibration isolation connector for connecting a duct to a fan shall consist of noncombustible packing in a metal sleeve joint of approved design ...
NYC Mechanical Code 2014 > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.2 Joints, Seams and Penetrations of Grease Ducts > 506.3.2.4 Vibration Isolation
Article 6 Ventilation [PDF] (page 10)
used to exhaust interior cooking spaces shall comply with Section C26-265.0-b of the Administrative Code. c. Vibration isolation connectors shall ...