// CODE SNIPPET
Section P-601 Vertical Piping
JUMP TO FULL CODE CHAPTER
Vertical piping shall be secured at sufficient intervals to keep the pipe in alignment and to carry the
weight of the pipe and contents.
Supports shall provide secure support for the pipe without excessive strain on joints or
connections and shall properly transmit the load to the building structure or to independent posts, piers, and
foundations.
All vertical drainage piping shall have base supports and, when more than 30 feet in height,
shall have intermediate supports spaced not more than 2 stories or 25 feet on centers. Closet bends, traps, trap-arms
and similar branches shall be firmly secured against movement in any direction.
Exception: No-hub cast iron soil pipe shall be supported with a riser clamp located at each floor. When the distance
between floors is greater than 10 feet, the vertical piping shall be supported every 10 feet using riser clamps where
possible or rigid supports securely fastened to the building structure.
Building drains shall not be installed or arranged so as to support load from vertical piping.
Pipe support shall be an approved type. Pipe hooks shall not be used.
Aluminum and plastic pipe shall be supported a minimum of at least 5 feet on
centers and closer, if required, to prevent horizontal deformation of the piping.
Related Code Sections
Section P-601 Pipe Supports, Vertical Piping
Vertical piping shall be secured at sufficient intervals to keep the pipe in alignment and to carry the
weight of the pipe and contents ...
917.4.3 Vents, Vertical Piping in Branch
The length of vertical piping in a fixture drain connecting to a horizontal branch shall not be considered in computing the fixture's distance ...
Plumbing Code 2018 of Philadelphia > 9 Vents > 917 Single-Stack Vent System > 917.4 Length of Horizontal Branches > 917.4.3 Vertical Piping in Branch
917.5 Vents, Minimum Vertical Piping Size From Fixture
The vertical portion of piping in a fixture drain to a horizontal branch shall be 2 inches (51 mm). The minimum size of the vertical portion ...
Plumbing Code 2018 of Philadelphia > 9 Vents > 917 Single-Stack Vent System > 917.5 Minimum Vertical Piping Size From Fixture
308.6 General Regulations, Sway Bracing
in the direction of pipe flow. A change of flow direction into a vertical pipe shall not require the upstream pipe to be braced ...
Plumbing Code 2018 of Philadelphia > 3 General Regulations > 308 Piping Support > 308.6 Sway Bracing
P3111.2 Vents, Installation
The only vertical pipe of a combination waste and vent system shall be the connection between the fixture drain and the horizontal combination waste ...
2018 Philadelphia Residential Code > 31 Vents > P3111 Combination Waste and Vent System > P3111.2 Installation