P3105.4 Vertical Leg for Waste Fixture Drains
JUMP TO FULL CODE CHAPTER
A vertical leg (see Figure P3105.4) is permitted within a fixture drain of a waste fixture in accordance with the following criteria:
R 408.30534
FIGURE P3105.4
VERTICAL LEG FIXTURE DRAIN SCHEMATIC
R 408.30534
- Minimum trap diameter shall be in accordance with Table P3201.7 of the code.
- The diameter of section A shall be equal to the diameter of the trap.
- The length of Section A shall not be less than 8 inches (2032 mm) and in accordance with Table P3105.1 of the code.
- The diameter of Section B shall be 1 pipe size larger than the diameter of Section A.
- The length of Section B shall not be more than 36 inches (9144 mm).
- The diameter of section C shall be 1 pipe size larger than the diameter of Section B.
- The total length of Section A and Section C shall not exceed the distance allowed in Table P3105.1 of the code.
- Bends shall be the diameter of the largest connected section.
R 408.30534
VERTICAL LEG FIXTURE DRAIN SCHEMATIC
R 408.30534
Related Code Sections
P3105.4 Vents, Vertical Leg for Waste Fixture Drains
A vertical leg (see Figure P3105.4) is permitted within a fixture drain of a waste fixture in accordance with the following criteria:
Minimum ...
2015 Michigan Residential Code > 31 Vents > P3105 Fixture Vents > P3105.4 Vertical Leg for Waste Fixture Drains
Appendix N Venting Methods
part of the wet vent illustrates a portion of Section P3105.4 vertical leg for waste fixture drains.
FIGURE N3
TYPICAL HORIZONTAL WET VENTING ...
913.2 Vents, Stack Installation
The waste stack shall be vertical,
and both horizontal and vertical offsets shall be prohibited
between the lowest fixture drain connection ...
P3109.2 Vents, Stack Installation
The waste stack shall be vertical,
and both horizontal and vertical offsets shall be prohibited
between the lowest fixture drain connection ...
406.2 Fixtures, Faucets and Fixture Fittings, Waste Connection
sink. The trap and fixture drain for an automatic clothes
washer standpipe shall be not less than 2 inches (51 mm) in
diameter. The fixture drain ...
2015 Michigan Plumbing Code > 4 Fixtures, Faucets and Fixture Fittings > 406 Automatic Clothes Washers > 406.2 Waste Connection