1106.3 Vertical Leader Sizing

Plumbing Code 2015 of Utah > 11 Storm Drainage > 1106 Size of Conductors, Leaders and Storm Drains > 1106.3 Vertical Leader Sizing
JUMP TO FULL CODE CHAPTER
Vertical leaders shall be sized based on the flow rate from horizontal gutters or the maximum flow rate through roof drains. The flow rate through vertical leaders shall not exceed that specified in Table 1106.3.

TABLE 1106.3 VERTICAL LEADER SIZING

SIZE OF LEADER (inches) CAPACITY
(gpm)
2 30
2 × 2 30
11/2 × 21/2 30
21/2 54
21/2 × 21/2 54
3 92
2 × 4 92
21/2×3 92
4 192
3 × 41/4 192
31/2 × 4 192
5 360
4 × 5 360
41/2 × 41/2 360
6 563
5 × 6 563
51/2 × 51/2 563
8 1208
6 × 8 1208

For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1106.3 Storm Drainage, Vertical leader sizing
Vertical leaders shall be sized based on the flow rate from horizontal gutters or the maximum flow rate through roof drains. The flow rate through ...
Plumbing Code 2018 of Utah > 11 Storm Drainage > 1106 Size of Conductors, Leaders and Storm Drains > 1106.3 Vertical leader sizing
1106.3 Storm Drainage, Vertical Leader Sizing
Vertical leaders shall be sized based on the flow rate from horizontal gutters or the maximum flow rate through roof drains. The flow rate through ...
Plumbing Code 2015 of Utah > 11 Storm Drainage > 1106 Size of Conductors, Leaders and Storm Drains > 1106.3 Vertical Leader Sizing
1106.1 Storm Drainage, General
The size of the vertical conductors and leaders, building storm drains , building storm sewers and any horizontal branches of such drains ...
Plumbing Code 2015 of Utah > 11 Storm Drainage > 1106 Size of Conductors, Leaders and Storm Drains > 1106.1 General
1106.2 Storm Drainage, Size of storm drain piping
Vertical and horizontal storm drain piping shall be sized based on the flow rate through the roof drain. The flow rate in storm drain piping shall ...
Plumbing Code 2018 of Utah > 11 Storm Drainage > 1106 Size of Conductors, Leaders and Storm Drains > 1106.2 Size of storm drain piping
1106.2 Storm Drainage, Size of Storm Drain Piping
Vertical and horizontal storm drain piping shall be sized based on the flow rate through the roof drain. The flow rate in storm drain piping ...
Plumbing Code 2015 of Utah > 11 Storm Drainage > 1106 Size of Conductors, Leaders and Storm Drains > 1106.2 Size of Storm Drain Piping
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US