F303.3.3 Vertical Joints Through Slabs
JUMP TO FULL CODE CHAPTER
Vertical joints through slabs shall be formed with a recess of not less than 1/4 inch by 1/4 inch (6.4 by 6.4 mm) and sealed with an approved sealant.
Exception: Slab-edge vertical joints occurring in slab poured into stem wall construction [see Section F303.2(2)]. The sealant (see Section F303.6) shall be applied according to the manufacturer's instructions.
(Note: most sealants require the concrete to be cured and dried.)
Related Code Sections
B303.3.3 Chapter 9B-52 F.A.C. Florida Standard for Passive Radon-Resistant Construction, Vertical Joints Through Slabs
Vertical joints through slabs shall be formed with a recess of not less than 1 / 4 inch by 1 / 4 inch (6.4 mm by 6.4 mm) and sealed ...
2020 FBC - Building, 7th edition > B Chapter 9B-52 F.A.C. Florida Standard for Passive Radon-Resistant Construction > B301 Construction Requirements for Passive Radon Control > B303 Floor Slab-On-Grade Buildings > B303.3 Sealing of Joints, Penetrations and Cracks in Slabs > B303.3.3 Vertical Joints Through Slabs
F303.3.3 Florida Standard for Passive Radon-Resistant New Residential Building Construction, Vertical Joints Through Slabs
Vertical joints through slabs shall be formed with a recess of not less than 1 / 4 inch by 1 / 4 inch (6.4 by 6.4 mm) and sealed with an approved ...
2017 FBC - Residential, 6th edition > F Florida Standard for Passive Radon-Resistant New Residential Building Construction > F303 Floor Slab-On-Grade Buildings > F303.3 Sealing of Joints, Penetrations and Cracks in Slabs > F303.3.3 Vertical Joints Through Slabs
F303.3.3 Florida Standard for Passive Radon-Resistant New Residential Building Construction, Vertical Joints Through Slabs
Vertical joints through slabs shall be formed with a recess of not less than 1 / 4 inch by 1 / 4 inch (6.4 by 6.4 mm) and sealed with an approved ...
2020 FBC - Residential, 7th edition > F Florida Standard for Passive Radon-Resistant New Residential Building Construction > F303 Floor Slab-On-Grade Buildings > F303.3 Sealing of Joints, Penetrations and Cracks in Slabs > F303.3.3 Vertical Joints Through Slabs
B303 Chapter 9B-52 F.A.C. Florida Standard for Passive Radon-Resistant Construction, Floor Slab-On-Grade Buildings
(Section B303.6). Vertical joints through slabs ...
2020 FBC - Building, 7th edition > B Chapter 9B-52 F.A.C. Florida Standard for Passive Radon-Resistant Construction > B301 Construction Requirements for Passive Radon Control > B303 Floor Slab-On-Grade Buildings
Chapter B301 Chapter 9B-52 F.A.C. Florida Standard for Passive Radon-Resistant Construction, Construction Requirements for Passive Radon Control
sealant (Section B303.6). Vertical joints through slabs ...
2020 FBC - Building, 7th edition > B Chapter 9B-52 F.A.C. Florida Standard for Passive Radon-Resistant Construction > B301 Construction Requirements for Passive Radon Control