604.5.1.2 Vertical Fixed Side Wall Grab Bars
JUMP TO FULL CODE CHAPTER
Vertical fixed side wall grab bars shall be 18 inches (455 mm) minimum in length and shall be mounted with the bottom of the bar located 39 inches (990 mm) minimum and 41 inches (1040 mm) maximum above the floor, with the centerline of the bar located 39 inches (990 mm) minimum and 41 inches (1040 mm) maximum from the rear wall.
Vertical fixed side wall grab bars primarily for children's use shall be 18 inches (455 mm) minimum in length and be mounted with the bottom of the bar located between 21 inches (535 mm) minimum and 30 inches (760 mm) maximum above the floor, with the centerline of the bar located between 34 inches (865 mm) minimum and 36 inches (915 mm) maximum from the rear wall.
Related Code Sections
604.5.1.2 Plumbing Elements and Facilities, Vertical Fixed Side Wall Grab Bars
Vertical fixed side wall grab bars shall be 18 inches (455 mm) minimum in length and shall be mounted with the bottom of the bar located 39 inches ...
Minnesota Accessibility Code 2015 > 6 Plumbing Elements and Facilities > 604 Water Closets and Toilet Compartments > 604.5 Grab Bars > 604.5.1 Fixed Side Wall Grab Bars > 604.5.1.2 Vertical Fixed Side Wall Grab Bars
604.5 Plumbing Elements and Facilities, Grab Bars
Fixed side-wall grab bars shall be 42 inches (1065 ...
Accessible and Usable Buildings and Facilities 2009 of Minnesota > 6 Plumbing Elements and Facilities > 604 Water Closets and Toilet Compartments > 604.5 Grab Bars
Section 607 Plumbing Elements and Facilities, Bathtubs
A vertical grab bar 18 inches (455 mm) minimum in length shall be provided on the control end wall 3 inches (75 mm) minimum and 6 inches (150 ...
607 Plumbing Elements and Facilities, Bathtubs
A vertical grab bar 18 inches (455 mm) minimum in length shall be provided on the control end wall 3 inches (75 mm) minimum and 6 inches (150 mm ...
Accessible and Usable Buildings and Facilities 2009 of Minnesota > 6 Plumbing Elements and Facilities > 607 Bathtubs
608.3 Plumbing Elements and Facilities, Grab Bars
A vertical grab bar 18 inches (455 mm) minimum in length shall be provided on the control end wall 3 inches ...
Minnesota Accessibility Code 2015 > 6 Plumbing Elements and Facilities > 608 Shower Compartments > 608.3 Grab Bars