705.8.6 Vertical Exposure

Building Code 2015 of Utah > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.8 Openings > 705.8.6 Vertical Exposure
JUMP TO FULL CODE CHAPTER
For buildings on the same lot, opening protectives having a fire protection rating of not less than 3/4 hour shall be provided in every opening that is less than 15 feet (4572 mm) vertically above the roof of an adjacent building or structure based on assuming an imaginary line between them. The opening protectives are required where the fire separation distance between the imaginary line and the adjacent building or structure is less than 15 feet (4572 mm).

Exceptions:
  1. Opening protectives are not required where the roof assembly of the adjacent building or structure has a fire-resistance rating of not less than 1 hour for a minimum distance of 10 feet (3048 mm) from the exterior wall facing the imaginary line and the entire length and span of the supporting elements for the fire-resistance-rated roof assembly has a fire-resistance rating of not less than 1 hour.
  2. Buildings on the same lot and considered as portions of one building in accordance with Section 705.3 are not required to comply with Section 705.8.6.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


705.8.6 Fire and Smoke Protection Features, Vertical Exposure
that is less than 15 feet (4572 mm) vertically above the roof of an adjacent building or structure based on assuming an imaginary line between them ...
Building Code 2015 of Utah > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.8 Openings > 705.8.6 Vertical Exposure
705.8.6 Fire and Smoke Protection Features, Vertical exposure
that is less than 15 feet (4572 mm) vertically above the roof of an adjacent building or structure based on assuming an imaginary line between them ...
Building Code 2018 of Utah > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.8 Openings > 705.8.6 Vertical exposure
R703.6.1 Wall Covering, Application
overlaps in the membrane of not less than 2 inches (51 mm) and vertical overlaps of not less than 6 inches (152 mm). Where horizontal furring strips are used ...
Residential Code 2015 of Utah > 7 Wall Covering > R703 Exterior Covering > R703.6 Wood Shakes and Shingles > R703.6.1 Application
Section 1904 Concrete, Durability Requirements
stories above grade plane, the specified compressive strength, f´ c , for concrete in basement walls, foundation walls, exterior walls and other vertical ...
Building Code 2018 of Utah > 19 Concrete > 1904 Durability Requirements
Section 1904 Concrete, Durability Requirements
vertical surfaces exposed to the weather shall be not less than 3,000 psi (20.7 MPa ...
Building Code 2015 of Utah > 19 Concrete > 1904 Durability Requirements
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US