3406.4.5.1.3 Vertical Cylindrical Tanks Over 50,000 Gallons (189 250 L) Storing a Combustible Liquid
JUMP TO FULL CODE CHAPTER
For vertical cylindrical tanks over 50,000 gallons (189 250 L) storing a combustible liquid, the distance shall not be less than 1/2 the greater dimension of height or diameter of the tank, up to a maximum distance of 175 feet (53 340 mm).
Related Code Sections
*1305.11.1.2 Fuel-Oil Piping and Storage, Inside of Buildings; Above Ground on the Lowest Floor
of not less than 2 hours. Where the aggregate fuel-oil storage on the lowest level of the building exceeds 50,000 gallons (189 250 L ...
NYC Mechanical Code 2014 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.11 Limitations on Quantities of Fuel-Oil Storage > 1305.11.1 Inside of Buildings > *1305.11.1.2 Inside of Buildings; Above Ground on the Lowest Floor
1305.14.2 Fuel-Oil Piping and Storage, Additional Construction Standards for Cylindrical Tanks Exceeding 275 Gallons (1041 L)
Cylindrical tanks, including oval, elongated oval, or round tanks, exceeding 275 gallons (1041 L) shall comply with the requirements of Section ...
NYC Mechanical Code 2008 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.14 Alternate Tank Design and Construction Standards > 1305.14.2 Additional Construction Standards for Cylindrical Tanks Exceeding 275 Gallons (1041 L)
§27-828 Heating and Combustion Equipment, Fuel Oil Storage Equipment
the temperature exceeds one hundred sixty-five degrees Fahrenheit. (b) Construction requirements, cylindrical tanks, except vertical tanks above ground outside ...
NYC 1968 Code (Vol I) > 14 Heating and Combustion Equipment > 17 Fuel Oil Equipment > §27-828 Fuel Oil Storage Equipment
1305.14.4 Fuel-Oil Piping and Storage, Additional Construction Standards for Tanks 275 Gallons (1041 L) or Less
Storage tanks with a capacity of less than or equal to 275 gallons (1041 L) shall have a minimum thickness of shell and head plates of No. 10 ...
NYC Mechanical Code 2014 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.14 Alternate Tank Design and Construction Standards > 1305.14.4 Additional Construction Standards for Tanks 275 Gallons (1041 L) or Less
1305.14.4 Fuel-Oil Piping and Storage, Additional Construction Standards for Tanks 275 Gallons (1041 L) or Less
Storage tanks with a capacity of less than or equal to 275 gallons (1041 L) shall have a minimum thickness of shell and head plates of No. 10 ...
NYC Mechanical Code 2008 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.14 Alternate Tank Design and Construction Standards > 1305.14.4 Additional Construction Standards for Tanks 275 Gallons (1041 L) or Less