Section 907 Vents for Stack Offsets

Go To Full Code Chapter
907.1 Vent for Horizontal Offset of Drainage Stack
Horizontal offsets of drainage stacks shall be vented where five or more branch intervals are located above the offset. The offset shall be vented by venting the upper section of the drainage stack and the lower section of the drainage stack.
907.2 Upper Section
The upper section of the drainage stack shall be vented as a separate stack with a vent stack connection installed in accordance with Section 904.4. The offset shall be considered to be the base of the stack.
907.3 Lower Section
The lower section of the drainage stack shall be vented by a yoke vent connecting between the offset and the next lower horizontal branch. The yoke vent connection shall be permitted to be a vertical extension of the drainage stack. The size of the yoke vent and connection shall be not less than the size required for the vent stack of the drainage stack.

Related Code Sections

Section 907 Vents, Vents for Stack Offsets
Horizontal offsets of drainage stacks shall be vented where five or more branch intervals are located above the offset. The offset shall be vented ...
Section 907 Vents, Vents for Stack Offsets
Horizontal offsets of drainage stacks shall be vented where five or more branch intervals are located above the offset. The offset shall be vented ...
Section 915 Vents, Vents for Stack Offsets
Horizontal offsets of drainage stacks shall be vented where five or more branch intervals are located above the offset. The offset shall be vented ...
907.3 Vents, Lower Section
The lower section of the drainage stack shall be vented by a yoke vent connecting between the offset and the next lower horizontal branch. The yoke ...
907.3 Vents, Lower Section