// CODE SNIPPET
Section G2427 (503) Venting of Appliances
Go To Full Code Chapter
FIGURE G2427.6.4 (503.6.5)
TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR
LESS IN SIZE NOT LESS THAN 8 FEET FROM A VERTICAL WALL
See More
G2427.1 (503.1) General
G2427.2 (503.2) Venting Systems Required
Except as permitted in Sections G2425.8, G2427.2.1 and G2427.2.2, all appliances shall be connected to venting systems.
G2427.2.1 (503.2.3) Direct-Vent Appliances
Listed direct-vent appliances shall be installed in accordance with the manufacturer's instructions. Through-the-wall vent terminations for listed direct-vent appliances shall be in accordance with Section G2427.8.
G2427.2.2 (503.2.4) Appliances With Integral Vents
Appliances incorporating integral venting means shall be installed in accordance with Section G2427.8, Items 1 and 2.
G2427.3 (503.3) Design and Construction
Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors.
G2427.3.1 (503.3.1) Appliance Draft Requirements
A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer's instructions.
G2427.3.2 (503.3.2) Design and Construction
Appliances required to be vented shall be connected to a venting system designed and installed in accordance with the provisions of Sections G2427.4 through G2427.16.
G2427.3.3 (503.3.3) Mechanical Draft Systems
Mechanical draft systems shall comply with the following:
- Mechanical draft systems shall be listed in accordance with UL 378 and shall be installed in accordance with the manufacturer's instructions for both the appliance and the mechanical draft system.
- Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced draft design.
- Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building.
- Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
- Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draft system is not performing so as to satisfy the operating requirements of the appliance for safe performance.
G2427.3.4 (503.3.5) Air Ducts and Furnace Plenums
Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum.
G2427.3.5 (503.3.6) Above-Ceiling Air-Handling Spaces
Where a venting system passes through an above-ceiling air-handling space or other nonducted portion of an air-handling system, the venting system shall conform to one of the following requirements:
- The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appliance or vent manufacturer's instructions.
- The venting system shall be installed such that fittings and joints between sections are not installed in the above-ceiling space.
- The venting system shall be installed in a conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space.
G2427.4 (503.4) Type of Venting System to Be Used
The type of venting system to be used shall be in accordance with Table G2427.4.
TABLE G2427.4 (503.4)
TYPE OF VENTING SYSTEM TO BE USEDAPPLIANCES | TYPE OF VENTING SYSTEM |
Listed Category I appliances Listed appliances equipped with draft hood Appliances listed for use with Type B gas vent |
Type B gas vent (Section G2427.6) Chimney (Section G2427.5) Single-wall metal pipe (Section G2427.7) Listed chimney lining system for gas venting (Section G2427.5.2) Special gas vent listed for these appliances (Section G2427.4.2) |
Listed vented wall furnaces | Type B-W gas vent (Sections G2427.6, G2436) |
Category II, Category III and Category IV appliances | As specified or furnished by manufacturers of listed appliances (Sections G2427.4.1, G2427.4.2) |
Unlisted appliances | Chimney (Section G2427.5) |
Decorative appliances in vented fireplaces | Chimney |
Direct-vent appliances | See Section G2427.2.1 |
Appliances with integral vent | See Section G2427.2.2 |
G2427.4.1 (503.4.1) Plastic Piping
Where plastic piping is used to vent an appliance, the appliance shall be listed for use with such venting materials and the appliance manufacturer's installation instructions shall identify the specific plastic piping material. The plastic pipe venting materials shall be labeled in accordance with the product standards specified by the appliance manufacturer or shall be listed in accordance with UL 1738.
G2427.4.1.1 (503.4.1.1) Plastic Vent Joints
Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer's instructions. Plastic pipe venting materials listed and labeled in accordance with UL 1738 shall be installed in accordance with the vent manufacturer's instructions. Where a primer is required, it shall be of a contrasting color.
G2427.4.2 (503.4.2) Special Gas Vent
G2427.5 (503.5) Masonry, Metal and Factory-Built Chimneys
G2427.5.1 (503.5.1) Factory-Built Chimneys
Factory-built chimneys shall be listed in accordance with UL 103. Factory-built chimneys used to vent appliances that operate at a positive vent pressure shall be listed for such application.
G2427.5.2 (503.5.3) Masonry Chimneys
Masonry chimneys shall be built and installed in accordance with NFPA 211 and shall be lined with an approved clay flue lining, a chimney lining system listed and labeled in accordance with UL 1777 or other approved material that will resist corrosion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F (982°C).
Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas appliances listed for use with Type B vents shall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer's instructions. A permanent identifying label shall be attached at the point where the connection is to be made to the liner. The label shall read: "This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel-burning appliances or incinerators."
G2427.5.3 (503.5.4) Chimney Termination
Chimneys for residential-type or low-heat appliances shall extend not less than 3 feet (914 mm) above the highest point where they pass through a roof of a building and not less than 2 feet (610 mm) higher than any portion of a building within a horizontal distance of 10 feet (3048 mm). Chimneys for medium-heat appliances shall extend not less than 10 feet (3048 mm) higher than any portion of any building within 25 feet (7620 mm). Chimneys shall extend not less than 5 feet (1524 mm) above the highest connected appliance draft hood outlet or flue collar. Decorative shrouds shall not be installed at the termination of factory-built chimneys except where such shrouds are listed and labeled for use with the specific factory-built chimney system and are installed in accordance with the manufacturer's instructions.
G2427.5.4 (503.5.5) Size of Chimneys
The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods:
- The provisions of Section G2428.
- The effective areas of the vent connector and chimney flue of a venting system serving a single appliance with a draft hood shall be not less than the area of the appliance flue collar or draft hood outlet, nor greater than seven times the draft hood outlet area.
- The effective area of a chimney flue or a venting system serving two appliances with draft hoods.
- Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods.
- Other approved engineering methods.
G2427.5.5 (503.5.6) Inspection of Chimneys
Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleaned if previously used for venting solid or liquid fuel-burning appliances or fireplaces.
G2427.5.5.1 (503.5.6.1) Chimney Lining
Chimneys shall be lined in accordance with NFPA 211.
G2427.5.5.2 (503.5.6.2) Cleanouts
Cleanouts shall be examined and where they do not remain tightly closed when not in use, they shall be repaired or replaced.
G2427.5.5.3 (503.5.6.3) Unsafe Chimneys
Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chimney to conform to NFPA 211 and it shall be suitable for the appliances to be vented.
G2427.5.6 (503.5.7) Chimneys Serving Appliances Burning Other Fuels
Chimneys serving appliances burning other fuels shall comply with Sections G2427.5.6.1 through G2427.5.6.4.
G2427.5.6.1 (503.5.7.1) Solid Fuel-Burning Appliances
G2427.5.6.2 (503.5.7.2) Liquid Fuel-Burning Appliances
Where one chimney flue serves gas appliances and liquid fuel-burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safety shutoff devices.
G2427.5.6.3 (503.5.7.3) Combination Gas- And Solid Fuel-Burning Appliances
A combination gas- and solid fuel-burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burner in the event of sustained backdraft or flue gas spillage. The chimney flue shall be sized to properly vent the appliance.
G2427.5.6.4 (503.5.7.4) Combination Gas- And Oil Fuel-Burning Appliances
G2427.5.7 (503.5.8) Support of Chimneys
All portions of chimneys shall be supported for the design and weight of the materials employed. Factory-built chimneys shall be supported and spaced in accordance with the manufacturer's installation instructions.
G2427.5.8 (503.5.9) Cleanouts
Where a chimney that formerly carried flue products from liquid or solid fuel-burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight-fitting cover and be installed so its upper edge is not less than 6 inches (152 mm) below the lower edge of the lowest chimney inlet opening.
G2427.5.9 (503.5.10) Space Surrounding Lining or Vent
The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent within the chimney as provided in this code and the liner or vent manufacturer's instructions shall not be prohibited.
The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory-built chimney shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct-vent appliances designed for installation in a solid fuel-burning fireplace and installed in accordance with the manufacturer's instructions.
G2427.5.10 (503.5.11) Insulation Shield
Where a factory-built chimney passes through insulated assemblies, an insulation shield constructed of steel having a thickness of not less than 0.0187 inch (0.475 mm) (nominal 26 gage) shall be installed to provide clearance between the chimney and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the chimney manufacturer's installation instructions. Where chimneys pass through attic space, the shield shall terminate not less than 2 inches (51 mm) above the installation materials and shall be secured in place to prevent displacement.
G2427.6 (503.6) Gas Vents
Gas vents shall comply with Sections G2427.6.1 through G2427.6.12. (See Section G2403, General Definitions.)
G2427.6.1 (503.6.1) Materials
Type B and BW gas vents shall be listed in accordance with UL 441. Vents for listed combination gas- and oil-burning appliances shall be listed in accordance with UL 641.
G2427.6.2 (503.6.2) Installation, General
Gas vents shall be installed in accordance with the manufacturer's instructions.
G2427.6.3 (503.6.3) Type B-W Vent Capacity
G2427.6.4 (503.6.5) Gas Vent Terminations
A gas vent shall terminate in accordance with one of the following:
- Gas vents that are 12 inches (305 mm) or less in size and located not less than 8 feet (2438 mm) from a vertical wall or similar obstruction shall terminate above the roof in accordance with Figure G2427.6.4.
- Gas vents that are over 12 inches (305 mm) in size or are located less than 8 feet (2438 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet (610 mm) above the highest point where they pass through the roof and not less than 2 feet (610 mm) above any portion of a building within 10 feet (3048 mm) horizontally.
- As provided for direct-vent systems in Section G2427.2.1.
- As provided for appliances with integral vents in Section G2427.2.2.
- As provided for mechanical draft systems in Section G2427.3.3.

ROOF SLOPE | H (minimum) ft |
---|---|
Flat to 6/12
|
1.0 |
Over 6/12 to 7/12
|
1.25 |
Over 7/12 to 8/12
|
1.5 |
Over 8/12 to 9/12
|
2.0 |
Over 9/12 to 10/12
|
2.5 |
Over 10/12 to 11/12
|
3.25 |
Over 11/12 to 12/12
|
4.0 |
Over 12/12 to 14/12
|
5.0 |
Over 14/12 to 16/12
|
6.0 |
Over 16/12 to 18/12
|
7.0 |
Over 18/12 to 20/12
|
7.5 |
Over 20/12 to 21/12
|
8.0 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
FIGURE G2427.6.4 (503.6.5)
LESS IN SIZE NOT LESS THAN 8 FEET FROM A VERTICAL WALL
Upcodes Diagrams
Related Code Sections
Section G2427 Fuel Gas, (503) Venting of Appliances
The venting of appliances shall be in accordance with Sections G2427.2 through G2427.16 ...
Section G2427 Fuel Gas, (503) Venting of Appliances
The venting of appliances shall be in accordance with Sections G2427.2 through G2427.16 ...
G2427.2 Fuel Gas, (503.2) Venting Systems Required
Except as permitted in Sections G2425.8, G2427.2.1 and G2427.2.2, all appliances shall be connected to venting systems ...
G2427.3 Fuel Gas, (503.3) Design and Construction
A venting system shall satisfy the draft requirements of the appliance in accordance ...
G2427.3 Fuel Gas, (503.3) Design and Construction
A venting system shall satisfy the draft requirements of the appliance in accordance ...