// CODE SNIPPET
1207.6.1.2 Ventilation Based on Exhaust Rate
Go To Full Code Chapter
Mechanical exhaust ventilation shall be provided at a rate of not less than 1 ft3/min/ft2 (5.1 L/sec/m2) of floor area of the room, area or walk-in unit. The ventilation shall be either continuous or shall be activated by a gas detection system in accordance with Section 1207.6.1.2.4.
1207.6.1.2.1 Standby Power
Mechanical exhaust ventilation shall be provided with a minimum of 2 hours of standby power in accordance with Section 1203.2.5.
1207.6.1.2.2 Installation Instructions
Required mechanical exhaust ventilation systems shall be installed in accordance with the manufacturer's installation instructions and the International Mechanical Code.
1207.6.1.2.3 Supervision
1207.6.1.2.4 Gas Detection System
Where required by Section 1207.6.1.2, rooms, areas and walk-in units containing ESS shall be protected by an approved continuous gas detection system that complies with Section 916 and with the following:
- The gas detection system shall be designed to activate the mechanical ventilation system when the level of flammable gas in the room, area or walk-in unit exceeds 25 percent of the LFL.
- The mechanical ventilation system shall remain on until the flammable gas detected is less than 25 percent of the LFL.
- The gas detection system shall be provided with a minimum of 2 hours of standby power in accordance with Section 1203.2.5.
- Failure of the gas detection system shall annunciate a trouble signal at an approved central station, proprietary or remote station service in accordance with NFPA 72, or shall initiate an audible and visible trouble signal at an approved constantly attended on-site location.
Related Code Sections
1207.6.1.2 Energy Systems, Ventilation Based on Exhaust Rate
Mechanical exhaust ventilation shall be provided at a rate of not less than 1 ft3/min/ft2 (5.1 L/sec/m2) of floor area of the room, area or walk ...
1105.6 Refrigeration, Ventilation
Location of the openings shall be based on the relative density of the refrigerant to air. The free-aperture cross section for the ventilation ...
1105.6 Refrigeration, Ventilation
be provided. Location of the openings shall be based on the relative density of the refrigerant to air. The free-aperture cross section for the ventilation ...
415.11.1.6 Special Detailed Requirements Based on Occupancy and Use, Ventilation
Mechanical exhaust ventilation at the rate of not less than 1 cubic foot per minute per square foot [0.0051 m3/(s × m2)] of floor area shall ...
415.11.1.6 Special Detailed Requirements Based on Use and Occupancy, Ventilation
Mechanical exhaust ventilation at the rate of not less than 1 cubic foot per minute per square foot [0.0051 m3/(s • m2)] of floor area shall ...