The openable area of the openings to the outdoors shall be not less than 4 percent of the floor area being ventilated.
1202.5.1.1 Adjoining Spaces
Where rooms and spaces without openings to the outdoors are ventilated through an adjoining room, the opening to the adjoining room shall be unobstructed and shall have an area of not less than 8 percent of the floor area of the interior room or space, but not less than 25 square feet (2.3 m2). The openable area of the openings to the outdoors shall be based on the total floor area being ventilated.
Exception: Exterior openings required for ventilation shall be allowed to open into a sunroom with thermal isolation or a patio cover provided that the openable area between the sunroom addition or patio cover and the interior room shall have an area of not less than 8 percent of the floor area of the interior room or space, but not less than 20 square feet (1.86 m2). The openable area of the openings to the outdoors shall be based on the total floor area being ventilated.
1202.5.1.2 Openings Below Grade
Where openings below grade provide required natural ventilation, the outside horizontal clear space measured perpendicular to the opening shall be one and one-half times the depth of the opening. The depth of the opening shall be measured from the average adjoining ground level to the bottom of the opening.

Related Code Sections

1202.5.1 Interior Environment, Ventilation Area Required
area being ventilated. Exception: Exterior openings required for ventilation shall be allowed to open into a sunroom with thermal isolation ...
1202.5.1 Interior Environment, Ventilation Area Required
area being ventilated. Exception: Exterior openings required for ventilation shall be allowed to open into a sunroom with thermal isolation ...
(B) Equipment for General Use, Arrangement
A vault ventilated by natural circulation of air shall be permitted to have roughly half of the total area of openings required for ventilation ...
(B) Equipment for General Use, Arrangement
A vault ventilated by natural circulation of air shall be permitted to have roughly half of the total area of openings required for ventilation ...
450.45 Equipment for General Use, Ventilation Openings
by natural circulation of air shall be permitted to have roughly half of the total area of openings required for ventilation in one or more openings near ...