Section P3103 Vent Terminals

Jump To Full Code Chapter
P3103.1 Vent Pipes Terminating Outdoors
Vent pipes terminating outdoors shall be extended to the outdoors through the roof or a sidewall of the building in accordance with one of the methods identified in Sections P3103.1.1 through P3103.1.4.
P3103.1.1 Roof Extension
Open vent pipes that extend through a roof that do not meet the conditions of Section P3103.1.2 or P3103.1.3 shall terminate not less than 6 inches (150 mm) above the roof or 6 inches (150 mm) above the anticipated snow accumulation, whichever is greater.
P3103.1.2 Roof Used for Recreational Purposes
Where a roof is to be used for assembly, as a promenade, observation deck or sunbathing deck, or for similar purposes, open vent pipes shall terminate not less than 7 feet (2134 mm) above the roof.
P3103.1.3 Roof Extension Covered
Where an open vent pipe terminates above a sloped roof and is covered by either a roof-mounted panel (such as a solar collector or photovoltaic panel mounted over the vent opening) or a roof element (such as an architectural feature or a decorative shroud), the vent pipe shall terminate not less than 2 inches (51 mm) above the roof surface. Such roof elements shall be designed to prevent the adverse effects of snow accumulation and wind on the function of the vent. The placement of a panel over a vent pipe and the design of a roof element covering the vent pipe shall provide for an open area for the vent pipe to the outdoors that is not less than the area of the pipe, as calculated from the inside diameter of the pipe. Such vent terminals shall be protected by a method that prevents birds and rodents from entering or blocking the vent pipe opening.
P3103.1.4 Sidewall Vent Terminal
Vent terminals extending through the wall shall terminate not less than 10 feet (3048 mm) from a lot line and not less than 10 feet (3048 mm) above the highest grade elevation within 10 feet (3048 mm) in any direction horizontally of the vent terminal. Vent pipes shall not terminate under the overhang of a structure where the overhang includes soffit vents. Such vent terminals shall be protected by a method that prevents birds and rodents from entering or blocking the vent pipe opening and that does not reduce the open area of the vent pipe.
P3103.2 Frost Closure
Where the 97.5-percent value for outside design temperature is 0°F (-18°C) or less, vent extensions through a roof or wall shall be not less than 3 inches (76 mm) in diameter. Any increase in the size of the vent shall be made not less than 1 foot (304.8 mm) inside the thermal envelope of the building.
P3103.3 Flashings and Sealing
The juncture of each vent pipe with the roof line shall be made watertight by an approved flashing. Vent extensions in walls and soffits shall be made weathertight by caulking.
P3103.4 Prohibited Use
A vent terminal shall not be used for any purpose other than a vent terminal.
P3103.5 Location of Vent Terminal
An open vent terminal from a drainage system shall not be located less than 4 feet (1219 mm) directly beneath any door, openable window, or other air intake opening of the building or of an adjacent building, nor shall any such vent terminal be within 10 feet (3048 mm) horizontally of such an opening unless it is not less than 3 feet (914 mm) above the top of such opening.

Related Code Sections

Section 903 Vents, Vent Terminals
Open vent pipes that extend through a roof shall be terminated not less than [NUMBER] inches (mm) above the roof. Where a roof is to be used ...
904.3 Vents, Vent Termination
Vent stacks or stack vents shall terminate outdoors to the open air or to a stack-type air admittance valve in accordance with Section 918 ...
M2203.5 Special Piping and Storage Systems, Vent Termination
Vent piping shall terminate outside of buildings at a point not less than 2 feet (610 mm), measured vertically or horizontally, from any building ...
Section P3103 Vents, Vent Terminals
Vent pipes terminating outdoors shall be extended to the outdoors through the roof or a sidewall of the building in accordance with one ...
Section P3103 Vents, Vent Terminals
Vent pipes terminating outdoors shall be extended to the outdoors through the roof or a sidewall of the building in accordance with one ...