Section P3101 Vent Systems

Go To Full Code Chapter
P3101.1 General
This chapter shall govern the selection and installation of piping, tubing and fittings for vent systems. This chapter shall control the minimum diameter of vent pipes, circuit vents, branch vents and individual vents, and the size and length of vents and various aspects of vent stacks and stack vents. Additionally, this chapter regulates vent grades and connections, height above fixtures and relief vents for stacks and fixture traps, and the venting of sumps and sewers.
P3101.2 Trap Seal Protection
The plumbing system shall be provided with a system of vent piping that will allow the admission or emission of air so that the liquid seal of any fixture trap shall not be subjected to a pressure differential of more than 1 inch of water column (249 Pa).
P3101.2.1 Venting Required
Every trap and trapped fixture shall be vented in accordance with one of the venting methods specified in this chapter.
P3101.3 Use Limitations
The plumbing vent system shall not be used for purposes other than the venting of the plumbing system.
P3101.4 Extension Outside a Structure
In climates where the 97.5-percent value for outside design temperature is 0°F (-18°C) or less (ASHRAE 97.5-percent column, winter, see Chapter 3), vent pipes installed on the exterior of the structure shall be protected against freezing by insulation, heat or both. Vent terminals shall be protected from frost closure in accordance with Section P3103.2.
P3101.5 Flood Resistance
In flood hazard areas as established by Table R301.2, vents shall be located at or above the elevation required in Section R322.1 (flood hazard areas including A Zones) or R322.2 (coastal high-hazard areas including V Zones).

Related Code Sections

Section P3101 Vents, Vent Systems
This chapter shall govern the selection and installation of piping, tubing and fittings for vent systems. This chapter shall control the minimum ...
Section P3101 Vents, Vent Systems
This chapter shall govern the selection and installation of piping, tubing and fittings for vent systems. This chapter shall control the minimum ...
920.1 Vents, Design of Vent System
The sizing, design and layout of the vent system shall be permitted to be determined by approved computer program design methods ...
503.2 Chimneys and Vents, Venting Systems Required
Except as permitted in Sections 501.8 and 503.2.1 through 503.2.4, all appliances shall be connected to venting systems ...
Section 919 Vents, Engineered Vent Systems
Engineered vent systems shall comply with this section and the design, submittal, approval, inspection and testing requirements of Section 316 ...