P3108.2 Vent Connections
JUMP TO FULL CODE CHAPTER
The dry vent connection to the wet vent shall be an individual vent or common vent to the lavatory, bidet, shower or bathtub. In vertical wet vent systems, the most upstream fixture drain connection shall be a dry-vented fixture drain connection. In horizontal wet-vent systems, not more than one wet-vented fixture drain shall discharge upstream of the dry-vented fixture drain connection.
Related Code Sections
909.2 Vents, Vent Connection
The dry-vent connection to the wet vent shall be an individual vent or common vent to the lavatory, bidet, shower or bathtub. In vertical wet-vent ...
911.2 Vents, Vent Connection
The circuit vent connection shall be located between the two most upstream fixture drains. The vent shall connect to the horizontal branch and shall ...
913.2 Vents, Vent Connection
The island fixture vent shall connect to the fixture drain as required for an individual or common vent. The vent shall rise vertically to above ...
914.2 Vents, Vent Connection
The circuit vent connection shall be located between the two most upstream fixture drains. The vent shall connect to the horizontal branch and shall ...
914.2 Vents, Vent Connection
The circuit vent connection shall be located between the two most upstream fixture drains. The vent shall connect to the horizontal branch and shall ...