1216.6 Variable Gas Pressure
JUMP TO FULL CODE CHAPTER
Where the gas pressure exceeds
14 inches (3.5 kPa) or less than 6 inches (1.5 kPa) of
water column, or where diversity demand factors are used,
the design, pipe, sizing, materials, location, and use of such
systems first shall be approved by the Authority Having Jurisdiction.
Piping systems designed for pressures exceeding
the serving gas supplier's standard delivery pressure shall
have prior verification from the gas supplier of the availability
of the design pressure.
Related Code Sections
1215.6 Fuel Gas Piping, Variable Gas Pressure
Where the supply gas pressure exceeds 5 psi (34.6 kPa) for natural gas and 10 psi (69 kPa) for undiluted propane or is less than 6 inches (1.5 kPa ...
California Plumbing Code 2019 > 12 Fuel Gas Piping > 1215.0 Required Gas Piping Size > 1215.6 Variable Gas Pressure
1216.6 Fuel Gas Piping, Variable Gas Pressure
Where the gas pressure exceeds
14 inches (3.5 kPa) or less than 6 inches (1.5 kPa) of
water column, or where diversity demand factors are used ...
California Plumbing Code 2016 > 12 Fuel Gas Piping > 1216.0 Required Gas Piping Size > 1216.6 Variable Gas Pressure
1315.6 Fuel Gas Piping, Variable Gas Pressures
Where the supply gas
pressure exceeds 5 psi (34 kPa) for natural gas and 10 psi (69
kPa) for undiluted propane or is less than 6 inches (1.5 kPa ...
California Mechanical Code 2019 > 13 Fuel Gas Piping > 1315.0 Required Gas Piping Size > 1315.6 Variable Gas Pressures
1316.6 Fuel Gas Piping, Variable Gas Pressures
Where the gas pressure exceeds 14 inches (3.5 kPa) or less than 6 inches (1.5 kPa) of
water column, or where diversity demand factors are used ...
California Mechanical Code 2016 > 13 Fuel Gas Piping > 1316.0 Required Gas Piping Size > 1316.6 Variable Gas Pressures
A5.207.2.4.6 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Variable Flow Controls
Individual pumps serving variable flow systems and having a motor horsepower exceeding 5 hp shall have controls and/or devices (such as variable ...
California Green Building Standards Code 2019 > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.207 [OSHPD 1, 2 & 4] HVAC Design, Equipment and Installation > A5.207.2 Space Conditioning Systems > A5.207.2.4 Hydronic System Measures > A5.207.2.4.6 Variable Flow Controls